user manual

Digital/Bus settings
Name Par. Number Default Value Setting for BACnet
Coasting Select 8-50 Logic-or Logic-or
Quick Stop Select 8-51 Logic-or Logic-or
DC Brake Select 8-52 Logic-or Logic-or
Start Select 8-53 Logic-or Logic-or
Reversing Select 8-54 Logic-or Logic-or
Set-up Select 8-55 Logic-or Logic-or
Preset reference Select 8-56 Logic-or Logic-or
BACnet settings
Name Par. Number Default Value Setting for BACnet
BACnet device instance 8-71 1 1
MS/TP Max Masters 8-73 127
Depent on the Number of
Masters in the system
“I am” Service 8-74 At power-up At power-up
Initialization Password 8-75 “admin” “admin”
Control Word Timeout Function
par.8-03 Control Timeout Time and par.8-04 Control Timeout Function are not enabled in this version of the
BACnet option.
BIBBs
Bibb's
ReadProperty Service
ReadPropertyMultiple Service
WriteProperty Service
WritePropertyMultiple Service
ConfirmedEventNotification Service
UnconfirmedEventNotification Service
GetEventInformation Service
AcknowledgeAlarm Service
ReinitializeDevice Service
DeviceCommunicationControl Service
I-Have Service
Who-Has Service
Who-Is Service
I-am Service
TimeSynchronization
How to Configure the System
4-2 TR200 BACnet