Split System Cooling Product Data XB14 4TTB4 1 1/2 - 5 Tons (018E - 061E) PUB. NO.
Features and Benefits • • • • • • • • • • • © 2012 Trane CLIMATUFF® compressor Efficiency up to 16.
Features and Benefits General Data Product Specifications A-Weighted Sound Power Level [dB(A)] Accessory Description and Usage AHRI Standard Capacity Rating Conditions 2 4 4 4 6 6 Model Nomenclature 7 Electrical Data 8 Dimensions 13 Mechanical Specification Options 16 22-1833-09 3
General Data Product Specifications Model No. 1 4TTB4018E1 4TTB4024E1 4TTB4030E1 Electrical Data V/Ph/Hz 2 208/230/1/60 208/230/1/60 208/230/1/60 Min Cir Ampacity 9 9 12 Max Fuse Size (Amps) 15 15 20 ® ® Compressors CLIMATUFF CLIMATUFF CLIMATUFF® No. Used - No. Stages 1-1 1-1 1-1 RL AMPS - LR AMPS 6.4 - 38.6 6.8 - 38.6 9.1 - 57.8 Outdoor Fan FL Amps 0.74 0.74 0.93 Fan HP 1/8 1/8 1/5 Fan Dia (inches) 23 23 27.
General Data Product Specifications Model No. 1 4TTB4042E1 Electrical Data V/Ph/Hz 2 208/230/1/60 Min Cir Ampacity 23 Max Fuse Size (Amps) 40 Compressors CLIMATUFF® - SCROLL No. Used - No. Stages 1-1 RL AMPS - LR AMPS 17.9 - 112 Outdoor Fan FL Amps 0.93 Fan HP 1/5 Fan Dia (inches) 27.6 Coil Spine Fin™ Refrigerant R-410A 8/4-LB/OZ Line Size - (in.) O.D. Gas 3 7/8 Line Size - (in.) O.D. Liquid 3 3/8 Dimensions H x W x D (Crated) 46.4 x 35.1 x 38.
General Data AHRI Standard Capacity Rating Conditions Accessory Description and Usage Anti-Short Cycle Timer — Solid state timing device that prevents compressor recycling until 5 minutes have elapsed after satisfying call or power interruptions. Use in area with questionable power delivery, commercial applications, long lineset, etc.
Model Nomenclature Outdoor Units Gas Furnaces 4 T T B 4 0 3 6 E 1 0 0 0 A A T U D 2 B 0 8 0 A C V 3 2 A A Refrigerant Type 2 = R-22 4 = R-410A TRANE Product Type W = Split Heat Pump T = Split Cooling Product Family Z = Leadership – Two Stage X = Leadership R = Replacement/Retail B = Basic A = Light Commercial Family SEER 0 = 10 3 = 13 1 = 11 4 = 14 2 = 12 5 = 15 6 = 16 8 = 18 9 = 19 Split System Connections 1-6 Tons 0 = Brazed Nominal Capacity in 000s of BTUs Major Design Modifications Power Supply 1
Electrical Data Schematic Diagrams 4TTB4018, 4TTB4024, 4TTB4030 From Drawing D157123P01REV0 8 22-1833-09
Electrical Data Schematic Diagrams 4TTB4036, 4TTB4042 From Drawing D157124P01 22-1833-09 9
Electrical Data Schematic Diagrams 4TTB4048, 4TTB4049 From Drawing D157125P01 10 22-1833-09
Electrical Data Schematic Diagrams 4TTB4060 From Drawing D157126P01 22-1833-09 11
Electrical Data Schematic Diagrams 4TTB4061 From Drawing D156975p01 12 22-1833-09
Dimensions 4TTB4 Outline Drawing Note: All dimensions are in MM (Inches).
Notes 14 22-1833-09
Notes 22-1833-09 15
Mechanical Specification Options General Condenser Coil The 4TTB4 is fully charged from the factory for up to 15 feet of piping. This unit is designed to operate at outdoor ambient temperatures as high as 115°F. Cooling capacities are matched with a wide selection of air handlers and furnace coils that are AHRI certified. The unit is certified to UL 1995. Exterior is designed for outdoor application. The outdoor coil provides low airflow resistance and efficient heat transfer.