Table PD-25 — Belt Drive Evaporator Fan Performance — 3 Ton — TSC036A3,A4,AW — Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor
& Field Supplied
Low Static Drive (1) 1-HP Standard Motor & Drive
960 528 0.12 599 0.16 658 0.20 713 0.24 763 0.29 810 0.33 855 0.38 898 0.43 939 0.49
1080 557 0.15 625 0.19 685 0.24 738 0.28 786 0.33 832 0.38 876 0.43 917 0.48 957 0.54
1200 588 0.19 652 0.23 712 0.28 764 0.33 811 0.38 856 0.43 898 0.48 939 0.54 978 0.59
1320 552 0.18 622 0.23 681 0.27 738 0.32 790 0.38 838 0.44 882 0.49 923 0.55 962 0.60 1000 0.66
1440 588 0.23 657 0.28 713 0.33 765 0.37 817 0.43 865 0.50 909 0.56 949 0.62 987 0.68 1024 0.74
For Standard Evaporator Fan Speed (RPM), reference Table PD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK69 required. Field Supplied Belt may be necessary.
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt may be necessary.
Table PD-25 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive
960 978 0.54 1016 0.60 1052 0.66 1086 0.72 1120 0.78
1080 995 0.59 1033 0.65 1069 0.71 1103 0.78 1136 0.84
1200 1015 0.65 1051 0.71 1086 0.77 1120 0.84 1154 0.91
1320 1036 0.72 1072 0.78 1106 0.85 1138 0.91 1171 0.98
1440 1060 0.80 1094 0.86 1128 0.93 1160 1.00 1192 1.07
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown in
our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.
1-HP Standard Motor &
Field Supplied High Static Drive (2)
Table PD-26 — Belt Drive Evaporator Fan Performance — 3 Ton — TSC036A3,A4,AW — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
960 588 0.15 661 0.19 725 0.24 782 0.29 832 0.35 878 0.40 919 0.46 958 0.51 996 0.56
1080 531 0.13 622 0.18 694 0.24 756 0.29 813 0.34 864 0.40 910 0.46 954 0.52 993 0.59 1031 0.65
1200 570 0.17 654 0.23 727 0.28 787 0.34 843 0.40 895 0.46 942 0.52 986 0.59 1026 0.66 1064 0.73
1320 610 0.22 687 0.28 760 0.34 821 0.40 875 0.46 925 0.53 973 0.59 1017 0.66 1058 0.73 1095 0.81
1440 651 0.27 723 0.33 793 0.40 855 0.47 908 0.53 956 0.60 1003 0.67 1047 0.75 1088 0.82 1127 0.89
For Standard Evaporator Fan Speed (RPM), reference Table PD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories.
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK69 required. Field Supplied Belt may be necessary.
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt may be necessary.
Table PD-26 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive
960 1032 0.62 1066 0.67 1101 0.73 1133 0.79 1166 0.86
1080 1065 0.70 1099 0.76 1132 0.82 1164 0.89 1194 0.95
1200 1099 0.80 1133 0.86 1166 0.93 1197 0.99 1227 1.06
1320 1132 0.88 1167 0.96 1200 1.04 1230 1.11 1261 1.19
1440 1164 0.97 1199 1.05 1232 1.14 1263 1.22 1294 1.30
1-HP Standard Motor &
Field Supplied High Static Drive (2)
1-HP Standard Motor &
Field Supplied High Static Drive (2)
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.