Data
Table PD-33 — Belt Drive Evaporator Fan Performance — 6-Ton — TSC072,AK — Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied Low Static Drive (1) 2-HP Standard Motor & Drive
1920 - - - - 573 0.34 630 0.41 680 0.48 726 0.55 769 0.62 811 0.70 851 0.78 889 0.87
2160 - - 548 0.35 602 0.42 656 0.50 706 0.58 751 0.65 792 0.73 832 0.81 871 0.90 908 0.99
2400 - - 584 0.45 635 0.52 682 0.60 732 0.69 777 0.77 818 0.86 856 0.95 893 1.04 930 1.13
2640 569 0.47 621 0.56 670 0.64 715 0.72 758 0.81 802 0.91 845 1.01 883 1.10 919 1.20 953 1.29
2880 612 0.60 660 0.69 706 0.78 749 0.86 789 0.96 830 1.06 870 1.16 909 1.27 945 1.37 979 1.48
For Standard Evaporator Fan Speed (RPM), reference Table PD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
Table PD-33 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2- HP Standard Motor & Drive 2-HP Standard Motor & High Static Drive
1920 925 0.95 960 1.03 994 1.11 1026 1.19 1057 1.27 1087 1.36 1116 1.44 1144 1.52 1173 1.61 1200 1.70
2160 944 1.08 978 1.17 1010 1.26 1043 1.36 1073 1.44 1104 1.54 1133 1.63 1162 1.72 1189 1.81 1216 1.91
2400 964 1.22 998 1.32 1030 1.42 1063 1.53 1092 1.63 1123 1.73 1151 1.83 1179 1.93 1206 2.03 1233 2.13
2640 986 1.39 1019 1.49 1051 1.60 1082 1.71 1112 1.81 1141 1.92 1169 2.03 1198 2.15 1225 2.26 - -
2880 1011 1.58 1043 1.69 1073 1.79 1103 1.90 1133 2.02 1161 2.13 1190 2.26 - - - - - -
2- HP Standard Motor & High Static Drive
Trane’s factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
Table PD-34 — Belt Drive Evaporator Fan Performance — 6-Ton — TSC072,AK — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied Low Static Drive (1) 2-HP Standard Motor & Drive
1920 - - 565 0.31 627 0.39 679 0.45 726 0.52 771 0.60 814 0.69 857 0.77 899 0.85 939 0.93
2160 566 0.35 609 0.41 663 0.48 716 0.57 762 0.64 804 0.72 843 0.80 883 0.90 922 0.99 960 1.08
2400 619 0.47 660 0.54 701 0.60 751 0.69 798 0.78 839 0.87 877 0.95 914 1.04 950 1.14 984 1.24
2640 672 0.61 710 0.68 745 0.76 788 0.83 833 0.93 875 1.04 914 1.13 949 1.22 984 1.31 1016 1.42
2880 726 0.77 762 0.86 795 0.94 828 1.02 869 1.11 911 1.21 950 1.33 986 1.44 1019 1.53 1051 1.63
For Standard Evaporator Fan Speed (RPM), reference Table PD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
Table PD-34 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & High Static Drive
1920 978 1.02 1015 1.11 1051 1.20 1086 1.30 1118 1.39 1150 1.49 1180 1.58 1209 1.68 1236 1.77 1263 1.86
2160 996 1.17 1034 1.27 1069 1.36 1103 1.46 1136 1.56 1169 1.67 1199 1.77 1229 1.88 1258 1.98 - -
2400 1020 1.35 1055 1.45 1089 1.55 1122 1.66 1154 1.76 1186 1.86 1216 1.97 1246 2.08 1276 2.20 - -
2640 1049 1.53 1081 1.65 1113 1.76 1144 1.87 1176 1.98 1207 2.10 1237 2.21 - - - - - -
2880 1081 1.74 1112 1.86 1141 1.97 1170 2.10 1199 2.22 - - --------
2- HP Standard Motor & High Static Drive
Trane’s factory supplied motors, in commercial equipment, are definite purpose
motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range
of our fan motors as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our product’s warranty will not be
affected.
2- HP Standard
Motor & Drive