Installation and Maintenance Manual

Installation: Electrical
38 GTND-SVX01B-EN
Thermostat Heat Anticipator Adjustments. The
initial heat anticipator setpoint should equal the
thermostat’s current amperage draw when the unit is
firing. This setpoint should be measured for the best
results. Use the recommended ranges as a guide. If further
information is needed, consult your thermostat
manufacturer’s instructions.
Recommended Heat Anticipator Settings:
Note: Should any high limit wires have to be replaced,
they must be replaced with wiring material having
a temperature rating of 200°C minimum.
Figure 38. All unit sizes: Low-voltage thermostat wiring
(Two stage)
Figure 39. All unit sizes: T834H or T843N Thermostat
wiring
Unit Size: 30–200 250–400
For Tubular Units: 0.35 Amps 0.65 Amps
RGW1W2
WR
G
D6922C