Catalogue

UH-PRC002-EN 21
General Data
Figure 6. 30° nozzle
Table 4. 30-degree nozzle—approximate distance of throw at nominal airflow
Distance From Floor
to Bottom of Unit “H”
ft (m)
Unit Size
Input MBh (kW)
100 125 150 175 200 225 250 300 350 400
(29.3) (36.6) (43.9) (51.2) (58.6) (65.9) (73.2) (87.8) (102.5) (117.1)
8 65707580859095115120125
(2.4) (19.8) (21.3) (22.9) (24.4) (25.9) (27.4) (29.0) (35.1) (36.6) (38.1)
10 57 60 64 68 72 78 86 99 105 110
(3.0) (17.4) (18.3) (19.5) (20.7) (21.9) (23.8) (26.2) (30.2) (32.0) (33.5)
12 50 54 57 60 64 70 77 88 94 100
(3.7) (15.2) (16.5) (17.4) (18.3) (19.5) (21.3) (23.5) (26.8) (28.7) (30.5)
15 — 45 48 50 53 59 64 74 79 84
(4.6) (13.7) (14.6) (15.2) (16.2) (18.0) (19.5) (22.6) (24.1) (25.6)
20 — — — 44 47 53 58 66 71 75
(6.1) (13.4) (14.3) (16.2) (17.7) (20.1) (21.6) (22.9)
Notes:
1. All throw data figures are approximate.
2. — = not recommended at these mounting heights.
3. Nozzles are not available on units below size 100 MBh.
4. Nozzles are available for high-efficiency units. Specify High Efficiency when ordering due to difference in nozzle configuration.
Figure 7. 60° nozzle
Table 5. 60-degree nozzle—approximate distance of throw at nominal airflow
Distance From Floor
to Bottom of Unit “H”
ft (m)
Unit Size
Input MBh (kW)
100 125 150 175 200 225 250 300 350 400
(29.3) (36.6) (43.9) (51.2) (58.6) (65.9) (73.2) (87.8) (102.5) (117.1)
8 7580859095100110125130138
(2.4) (22.9) (24.4) (25.9) (27.4) (29.0) (30.5) (33.5) (38.1) (39.6) (42.1)
10 65 70 75 79 83 88 95 109 115 120
(3.0) (19.8) (21.3) (22.9) (24.1) (25.3) (26.8) (29.0) (33.2) (35.1) (36.6)
12 60 64 68 72 76 80 84 100 103 108
(3.7) (18.3) (19.8) (20.7) (21.9) (23.2) (24.4) (25.6) (30.5) (31.4) (32.9)
15 50 54 56 61 65 68 71 85 88 94
(4.6) (15.2) (16.5) (17.1) (18.6) (19.8) (20.7) (21.6) (25.9) (26.8) (28.7)
20 — 49 52 55 59 61 65 77 81 85