Modular Multi-position Air Handlers GAT2A0B42S31SA GAT2A0C48S41SA GAT2A0C60S51SA PUB. NO.
Features and Benefits • Unique Cabinet Design - Double Wall Foamed and Formed Cabinet System - Water Proof Cabinet Design - R-4.2 Insulating Value (Avg. Insulating Value R-8.
Contents Features and Benefits Optional Equipment 2 4 Unique Cabinet Design Features and Benefits 5 General Data 6 Pub. No.
Optional Equipment OPTIONAL EQUIPMENT FOR AIR HANDLERS Accessory Number Description Fits Cabinet Size BAYEAAC05BK1A Electric Heater, 5kW, Breaker, 24V Control, 1 Ph A to C BAYEAAC05LG1A Electric Heater, 5kW, Lugs, 24V Control, 1 Ph A to C BAYEAAC08BK1A Electric Heater, 8kW, Breaker, 24V Control, 1 Ph A to C BAYEAAC08LG1A Electric Heater, 8kW, Lugs, 24V Control, 1 Ph A to C BAYEAAC10BK1A Electric Heater, 10kW, Breaker, 24V Control, 1 Ph A to C BAYEAAC10LG1A Electric Heater, 10kW, Lugs, 24
Unique Cabinet Design Features and Benefits 2 Precision Durable Door Seals 1 Unique Cabinet Design 0 Thermal Expansion Valve (TXV) 5 Conduit Connections 3 Refrigeration Connections e Integrated Horizontal Drain Pans 8 All Aluminum Coil 4 Condensate Connections r Safety Door Switch 7 VorticaTM Blower and Deck 6 Tool-less Door Fasteners 9 Labeled Panels and Connections w Compact 20.8” Depth with Doors Removed q Maximum width is 23.
General Data PRODUCT SPECIFICATIONS MODEL RATED VOLTS/PH/HZ. RATINGS 1 INDOOR COIL — Type Rows — F.P.I. Face Area (sq. ft.) Tube Size (in.) Refrigerant Control Drain Conn. Size (in.) 2 DUCT CONNECTIONS INDOOR FAN — Type Diameter-Width (In.) No. Used Drive - No. Speeds CFM vs. in. w.g. No. Motors — H.P. Motor Speed RPM Volts/Ph/Hz F.L. Amps - L.R. Amps FILTER Filter Furnished? Type Recommended No.-Size-Thickness REFRIGERANT Ref. Line Connections Coupling or Conn. Size — in. Gas Coupling or Conn. Size — in.
General Data GAT2A0B42 AIRFLOW PERFORMANCE TABLE AIRFLOW PERFORMANCE GAT2A0B42S31SA EXTERNAL STATIC (in w.g) AIRFLOW (CFM) Speed Taps - 230 VOLTS Speed Taps - 208 VOLTS 3 2† 1 3 2† 1 0 1646 1495 1358 1522 1298 1138 0.1 1599 1464 1335 1489 1285 1137 0.2 1546 1421 1313 1449 1260 1120 0.3 1488 1380 1280 1401 1233 1099 0.4 1425 1329 1233 1348 1193 1065 0.5 1353 1264 1178 1281 1140 1023 0.6 1259 1182 1108 1202 1075 958 0.
Performance Data GAT2A0C48 AIRFLOW PERFORMANCE TABLE AIRFLOW PERFORMANCE GAT2A0C48S41SA EXTERNAL STATIC (in w.g) AIRFLOW (CFM) Speed Taps - 230 VOLTS Speed Taps - 208 VOLTS 3 2† 1 3 2† 1 0 1904 1711 1541 1652 1455 1305 0.1 1881 1687 1529 1640 1450 1288 0.2 1844 1666 1511 1619 1425 1271 0.3 1806 1637 1485 1592 1410 1249 0.4 1766 1602 1454 1559 1381 1231 0.5 1716 1560 1420 1524 1351 1198 0.6 1659 1513 1380 1484 1321 1165 0.
Performance Data GAT2A0C60 AIRFLOW PERFORMANCE TABLE AIRFLOW PERFORMANCE GAT2A0C60S51SA EXTERNAL STATIC (in w.g) AIRFLOW (CFM) Speed Taps - 230 VOLTS Speed Taps - 208 VOLTS 5 4† 3 2 1 5 4† 3 2 1 0 2169 1956 1874 1739 1633 2165 2033 1871 1736 1629 0.1 2161 1916 1839 1696 1588 2155 1990 1833 1690 1582 0.2 2130 1889 1803 1667 1554 2121 1961 1795 1659 1545 0.3 2102 1850 1774 1628 1523 2090 1919 1763 1617 1511 0.
Performance Data WIRING DATA GAT2A0B42S31SA 240 VOLT Heater Model No. No. of Circuits kW BTUH Heater Amps per Circuit Capacity 208 VOLT Minimum Circuit Ampacity Maximum Overload Protection kW BTUH Heater Amps per Circuit Capacity Minimum Circuit Ampacity Maximum Overload Protection No Heater - - - 2.7** 3 15 - - 2.7** 3 15 BAYEAAC05++ 1 4.80 16400 20 28 30 3.60 12300 17.3 25 25 BAYEAAC08++ 1 7.68 26200 32 43 45 5.76 19700 27.7 38 40 BAYEAAC10++ 1 9.
Performance Data WIRING DATA GAT2A0C48S41SA 240 VOLT Heater Model No. No. of Circuits BTUH Heater Amps per Circuit Capacity kW 208 VOLT Minimum Circuit Ampacity Maximum Overload Protection BTUH Heater Amps per Circuit Capacity kW Minimum Circuit Ampacity Maximum Overload Protection No Heater - - - 3.1** 4 15 - - 3.1** 4 15 BAYEAAC05++ 1 4.80 16400 20.0 29 30 3.60 12300 17.3 26 30 BAYEAAC08++ 1 7.68 26200 32.0 44 45 5.76 19700 27.7 38 40 BAYEAAC10++ 1 9.
Performance Data WIRING DATA GAT2A0C60S51SA 240 VOLT Heater Model No. No. of Circuits kW No Heater - - BAYEAAC05++ 1 BAYEAAC08++ 1 BAYEAAC10++ 1 208 VOLT BTUH Heater Amps per Circuit Minimum Circuit Ampacity Maximum Overload Protection BTUH Heater Amps per Circuit Minimum Circuit Ampacity Maximum Overload Protection kW - 7.6** 10 15 - - 7.6** 10 15 4.80 16400 20.0 35 35 7.68 26200 32.0 50 50 3.60 12300 17.3 31 35 5.76 19700 27.7 44 45 9.60 32800 40.
WIRING DIAGRAM FOR GAT2A0B42 AND GAT2A0C48 AIR HANDLERS
WIRING DIAGRAM FOR GAT2A0C60 AIR HANDLERS
Field Wiring GAT2 AIR HANDLERS WITH SINGLE SPEED COOLING Air Handler Hook-up Diagram Cooling W2 Pink W3 Brown W1 White Green Red Blue Air Handler Comfort Control White Green Yellow Orange Red Blue W G Y O R B White Green Yellow Air Conditioner Blue Red Blue B - Blue Y - Yellow Field wiring •• * For multiple stages of electric heat, jumper W1, W2, and W3 together if comfort control has only one stage of heat. Pub. No.
Field Wiring GAT2 AIR HANDLERS WITH SINGLE SPEED HEAT PUMP Air Handler Hook-up Diagram HP Heat Pump W2 Pink W3 Brown W1 White Green Red Blue Air Handler Comfort Control White Green Yellow Orange Red Blue W G Y O R B Field wiring Black (X2) Orange White Green Yellow Orange Red Blue Yellow Red Blue R - Red B - Blue Y - Yellow •• * For multiple stages of electric heat, jumper W1, W2, and W3 together if comfort control has only one stage of heat 16 Pub. No.
GAT2 Convertibility * Note: No internal modifications required for any position. 1 Badge rotation will keep brand in correct position Multi-position Air Handler 1 Refrigerant Connections Airflow Upflow Condensate Drains Vertical Upflow* (as shipped) Refrigerant Connections Refrigerant Connections 1 Airflow 1 Airflow Horizontal Right Condensate Drains Horizontal Left Condensate Drains Horizontal Right* Horizontal Left* Pub. No.
Dimensions GAT2 AIR HANDLER DIMENSIONAL DATA W H Model No. H W D GAT2A0B42 55.7 21.3 21.75 GAT2A0C48 56.9 23.5 21.75 GAT2A0C60 61.7 23.5 21.75 D GAT2 AIR HANDLERS ARE ALL TWO PIECE CABINETS. 18 Pub. No.
GAT2 OUTLINE DRAWING MODEL NO. A B C D E F H FLOW CONTROL GAS LINE BRAZE GAT2A0B42 55.7 45.5 18.4 21.3 18.4 9.2 24.8 TXV 7/8 GAT2A0C48 56.9 46.7 20.5 23.5 20.5 10.3 24.2 TXV 7/8 GAT2A0C60 61.7 51.5 20.5 23.5 20.5 10.3 27.0 TXV 7/8 Pub. No.
Trane 6200 Troup Highway Tyler, TX 75707 www.trane.com 03/12 The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice.