Product Catalog Water Source Heat Pump Axiom™ Horizontal/Vertical—GEH/GEV 6 to 25Tons—60 Hz August 2014 WSHP-PRC016E-EN
Introduction The 6 through 25 ton horizontal and vertical water-source heat pump is used in a broad range of applications. Schools, office buildings, health care/rehabilitation facilities, condominiums and retirement facilities are just a few of the types of buildings utilizing the energy conscious watersource design.
Introduction Revision History WSHP-PRC016E-EN (08 August 2014) • Edited Model Number, Electrical Data, Fan Performance - 2 speed motor change WSHP-PRC016D-EN (15 November 2013) • WSHP-PRC016E-EN Added BACnet® 3
Table of Contents Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Cabinet Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Airflow Combinations . .
Features and Benefits Cabinet Description The cabinet design incorporates sturdy (non-painted) galvanized metal for maximum durability and corrosive resistive exterior.The equipment offers superior installation flexibility with service accessibility. The cabinet front allows service access for the controls.The horizontal and vertical design offers four product variations of return-air and supply-air combinations. All combinations are order specific and may not be modified at the job site. See Figure 1, p.
Features and Benefits Air-side filter The air-side filter incorporates a 1-inch thick (nominal) or 2-inch thick (nominal), MERV 8 or MERV 13 disposable fiberglass option.These filters include an average synthetic dust weight arrestance of approximately 75%.This dust holding capability includes a colorless, odorless adhesive to retain dirt particles within the filter media after fiber contact. Blower housing The blower housing is constructed of non-corrosive galvanized steel.
Features and Benefits Isolation for the hanging bracket is provided with a rubber grommet design as an accessory.This isolation device helps prevent sound vibration from reaching the structural support members of the building during compressor start and stop. Refrigeration piping Unit copper tubing is created from a 99% pure copper formation that conforms to the American Society ofTesting Materials (ASTM) B743 for seamless, light-annealed processing.
Features and Benefits Electric heat system COOLING TOWER AIR SEPARATOR CIRCULATING PUMP SYSTEM PUMPS PLATE-FRAME HEAT EXCHANGER WSHP WSHP WSHP WSHP WSHP WSHP WSHP WSHP WSHP BELOW 55 F, ELECTRIC HEAT IS ENERGIZED. ABOVE 60 F, COMPRESSOR IS ENERGIZED. With the boilerless electric heat option, the 6–25 ton models will contain boilerless controls ONLY to interface for a field provided supplemental electric heat selection.
Features and Benefits drop. Where as, the core are of a building may require cooling in summer or in winter based upon lighting, people, and equipment. Waterside economizer system If the water-source system design contained an economizing coil option, the moderate temperature loop water circulated through a core water-source system can provide an inexpensive means to satisfy room comfort without operating the water-source heat pump’s compressor.
Features and Benefits Common reheat applications The hot gas reheat option is designed to support building applications requiring fresh-air ventilation units delivering unconditioned-air directly to the space. It also provides dehumidification to large latent load spaces such as auditoriums, theaters and classrooms, or anywhere humidity control is a problem. Dos and Don’ts in Design Water-source heat pumps with hot gas reheat should not be used as a make-up air unit.
Application Considerations Water-source heat pump systems are used to provide comfort in a wide range of building types and climates.The system utilizes energy-conserving, heat-recovery capabilities to transfer heat from one area to another to meet individual zone requirements. When used with system design and control strategies, these high-performance systems reduce operating costs for the building owner and improve occupant comfort.
Application Considerations During moderate weather, such as spring or fall, the heat pumps serving the sunny side and interior of the building often operate in cooling mode and reject heat into the water loop.The heat pumps serving the shady side of the building often operate in heating mode and absorb heat from the water loop. Heat rejected by the units operating in cooling mode is used to offset the heat absorbed by the units in heating mode.
Application Considerations A hybrid system may also be used in existing buildings with existing ground loops as additional rooms or buildings are added to the system. A cooling tower may be the solution to off-load the peak demand of the new building addition as an example. Other additions may include a requirement for fresh-air ventilation. A fresh-air, air handler, along with a water to water unit may be introduced to the closed loop system to allow tempered fresh-air into the building.
Model Number Description Digits 1-3 - Unit Configuration GEH = High Efficiency Horizontal GEV = High Efficiency Vertical Digit 4 - Development Sequence E = R-410A Digits 5-7 - Nominal Capacity 072 = 6Ton 090 = 7½Ton 120 = 10Ton 150 = 12½Ton 180 = 15Ton 240 = 20Ton 300 = 25Ton Digit 8 - Voltage (Volts/Hz/Phase) Digit 15 - Supply-Air Arrangement B = Back Supply-Air Arrangement F = Front Supply-Air Arrangement L = Left Supply-Air Arrangement R = Right Supply-Air Arrangement T =Top Supply-Air Arrangement
General Data Table 2.
General Data Table 5. Air-to-Refrigerant coil (2-compressor circuit) - 6-25 tons Unit Size 072 090 120 150 180 240 300 Working Pressure 650 650 650 650 650 650 650 (GEH) 18 (GEV) 24 (GEH) 18 (GEV) 28 (GEH) 18 (GEV) 36 (GEH) 24 (GEV) 28 (GEH) 24 (GEV) 32 (GEV) 36 (GEV) 36 4 4 4 (GEH) 4 (GEV) 2 (GEH) 4 (GEV) 3 (GEV) 4 (GEV) 4 No.
Performance Data Table 6. ARI-ISO WLHP, GWHP and GLHP performance(a) Water Loop Heat Pump Ground Water Heat Pump Rated Rated Cooling 86°F Heating 68°F Cooling 59°F Heating 50°F Model GPM CFM Capacity Capacity Capacity Capacity Btuh EER Btuh COP Btuh EER Btuh EER GEH072 GEH090 GEH120 GEH150 GEH180 18.0 22.5 30.0 37.5 45.0 2100 2625 3500 4375 5250 75,500 88,100 115,900 152,800 180,800 13.40 14.10 13.35 14.30 13.10 83,800 99,200 147,100 175,000 222,700 4.80 4.68 4.60 4.40 4.
Performance Data Table 7. Gross cooling capacities - 6 tons GEH*072 EWT GPM Gross Cap. Mbtuh Gross Sen. Mbtuh SHR 45 45 45 45 45 55 55 55 55 55 59 59 59 59 59 68 68 68 68 68 77 77 77 77 77 86 86 86 86 86 95 95 95 95 95 105 105 105 105 105 115 115 115 115 115 120 120 9.0 12.0 15.0 18.0 21.0 9.0 12.0 15.0 18.0 21.0 9.0 12.0 15.0 18.0 21.0 9.0 12.0 15.0 18.0 21.0 9.0 12.0 15.0 18.0 21.0 9.0 12.0 15.0 18.0 21.0 9.0 12.0 15.0 18.0 21.0 9.0 12.0 15.0 18.0 21.0 9.0 12.0 15.0 18.0 21.0 18.0 21.0 91.3 92.
Performance Data Table 8. Heating capacities (gross) - 6 tons GEH*072 EWT GPM Gross Cap Mbtuh Absorb Mbtuh Comp Power kW LWT Feet Head 25 25 25 32 32 32 32 32 45 45 45 45 45 50 50 50 50 50 55 55 55 55 55 68 68 68 68 68 75 75 75 75 75 86 86 86 86 86 15.0 18.0 21.0 9.0 12.0 15.0 18.0 21.0 9.0 12.0 15.0 18.0 21.0 9.0 12.0 15.0 18.0 21.0 9.0 12.0 15.0 18.0 21.0 9.0 12.0 15.0 18.0 21.0 9.0 12.0 15.0 18.0 21.0 9.0 12.0 15.0 18.0 21.0 43.7 44.2 44.9 47.2 48.8 49.9 50.7 51.3 57.2 59.2 60.7 61.7 62.4 62.
Performance Data Table 10. Gross cooling capacities - 7½ tons GEH*090 EWT GPM Gross Cap Mbtuh Gross Sen Mbtuh SHR 45 45 45 45 45 55 55 55 55 55 59 59 59 59 59 68 68 68 68 68 77 77 77 77 77 86 86 86 86 86 95 95 95 95 95 105 105 105 105 105 115 115 115 115 115 120 120 11.3 15.0 18.8 22.5 26.3 11.3 15.0 18.8 22.5 26.3 11.3 15.0 18.8 22.5 26.3 11.3 15.0 18.8 22.5 26.3 11.3 15.0 18.8 22.5 26.3 11.3 15.0 18.8 22.5 26.3 11.3 15.0 18.8 22.5 26.3 11.3 15.0 18.8 22.5 26.3 11.3 15.0 18.8 22.5 26.3 22.5 26.
Performance Data Table 11. Heating capacities (gross) - 7½ tons GEH*090 EWT GPM Gross Cap Mbtuh Absorb Mbtuh Comp Power kW LWT Feet Head 25 25 25 32 32 32 32 32 45 45 45 45 45 50 50 50 50 50 55 55 55 55 55 68 68 68 68 68 75 75 75 75 75 86 86 86 86 86 18.8 22.5 26.3 11.3 15.0 18.8 22.5 26.3 11.3 15.0 18.8 22.5 26.3 11.3 15.0 18.8 22.5 26.3 11.3 15.0 18.8 22.5 26.3 11.3 15.0 18.8 22.5 26.3 11.3 15.0 18.8 22.5 26.3 11.3 15.0 18.8 22.5 26.3 58.5 59.6 60.7 60.9 62.3 64.2 65.2 65.8 72.8 75.5 77.2 78.
Performance Data Table 13. Gross cooling capacities - 10 tons - GEH*120 EWT GPM Gross Cap Mbtuh Gross Sen Mbtuh SHR 45 45 45 45 45 55 55 55 55 55 59 59 59 59 59 68 68 68 68 68 77 77 77 77 77 86 86 86 86 86 95 95 95 95 95 105 105 105 105 105 115 115 115 115 115 120 120 15.0 20.0 25.0 30.0 35.0 15.0 20.0 25.0 30.0 35.0 15.0 20.0 25.0 30.0 35.0 15.0 20.0 25.0 30.0 35.0 15.0 20.0 25.0 30.0 35.0 15.0 20.0 25.0 30.0 35.0 15.0 20.0 25.0 30.0 35.0 15.0 20.0 25.0 30.0 35.0 15.0 20.0 25.0 30.0 35.0 30.0 35.
Performance Data Table 14. Heating capacities (gross) - 10 tons GEH*120 EWT GPM Gross Cap Mbtuh Absorb Mbtuh Comp Power kW LWT Feet Head 25 25 25 32 32 32 32 32 45 45 45 45 45 50 50 50 50 50 55 55 55 55 55 68 68 68 68 68 75 75 75 75 75 86 86 86 86 86 25.0 30.0 35.0 15.0 20.0 25.0 30.0 35.0 15.0 20.0 25.0 30.0 35.0 15.0 20.0 25.0 30.0 35.0 15.0 20.0 25.0 30.0 35.0 15.0 20.0 25.0 30.0 35.0 15.0 20.0 25.0 30.0 35.0 15.0 20.0 25.0 30.0 35.0 73.7 74.5 75.4 79.2 80.6 81.5 81.4 81.9 94.3 95.5 96.1 97.
Performance Data Table 16. Gross cooling capacities - 12½ tons GEH*150 EWT GPM Gross Cap Mbtuh Gross Sen Mbtuh SHR 45 45 45 45 45 55 55 55 55 55 59 59 59 59 59 68 68 68 68 68 77 77 77 77 77 86 86 86 86 86 95 95 95 95 95 105 105 105 105 105 115 115 115 115 115 120 120 18.8 25.0 31.3 37.5 43.8 18.8 25.0 31.3 37.5 43.8 18.8 25.0 31.3 37.5 43.8 18.8 25.0 31.3 37.5 43.8 18.8 25.0 31.3 37.5 43.8 18.8 25.0 31.3 37.5 43.8 18.8 25.0 31.3 37.5 43.8 18.8 25.0 31.3 37.5 43.8 18.8 25.0 31.3 37.5 43.8 37.5 43.
Performance Data Table 17. Heating capacities (gross) - 12½ tons GEH*150 EWT GPM Gross Cap Mbtuh Absorb Mbtuh Comp Power kW LWT Feet Head 25 25 25 32 32 32 32 32 45 45 45 45 45 50 50 50 50 50 55 55 55 55 55 68 68 68 68 68 75 75 75 75 75 86 86 86 86 86 31.3 37.5 43.8 18.8 25.0 31.3 37.5 43.8 18.8 25.0 31.3 37.5 43.8 18.8 25.0 31.3 37.5 43.8 18.8 25.0 31.3 37.5 43.8 18.8 25.0 31.3 37.5 43.8 18.8 25.0 31.3 37.5 43.8 18.8 25.0 31.3 37.5 43.8 104.1 105.2 106.1 109.0 112.6 114.8 116.4 117.6 128.7 133.
Performance Data Table 19. Gross cooling capacities - 15 tons GEH*180 EWT GPM Gross Cap Mbtuh Gross Sen Mbtuh SHR 45 45 45 45 45 55 55 55 55 55 59 59 59 59 59 68 68 68 68 68 77 77 77 77 77 86 86 86 86 86 95 95 95 95 95 105 105 105 105 105 115 115 115 115 115 120 120 22.5 30.0 37.5 45.0 52.5 22.5 30.0 37.5 45.0 52.5 22.5 30.0 37.5 45.0 52.5 22.5 30.0 37.5 45.0 52.5 22.5 30.0 37.5 45.0 52.5 22.5 30.0 37.5 45.0 52.5 22.5 30.0 37.5 45.0 52.5 22.5 30.0 37.5 45.0 52.5 22.5 30.0 37.5 45.0 52.5 45.0 52.
Performance Data Table 20. Heating capacities (gross) - 15 tons GEH*180 EWT GPM Gross Cap Mbtuh Absorb Mbtuh Comp Power kW LWT Feet Head 25 25 32 32 32 32 32 45 45 45 45 45 50 50 50 50 50 55 55 55 55 55 68 68 68 68 68 75 75 75 75 75 86 86 86 86 86 45.0 52.5 22.5 30.0 37.5 45.0 52.5 22.5 30.0 37.5 45.0 52.5 22.5 30.0 37.5 45.0 52.5 22.5 30.0 37.5 45.0 52.5 22.5 30.0 37.5 45.0 52.5 22.5 30.0 37.5 45.0 52.5 22.5 30.0 37.5 45.0 52.5 133.1 133.9 138.7 142.6 144.3 145.9 146.3 161.7 166.5 169.2 170.
Performance Data Table 22. Gross cooling capacities - 6 tons GEV*072 EWT GPM Gross Cap Mbtuh Gross Sen Mbtuh SHR 45 45 45 45 45 55 55 55 55 55 59 59 59 59 59 68 68 68 68 68 77 77 77 77 77 86 86 86 86 86 95 95 95 95 95 105 105 105 105 105 115 115 115 115 115 120 120 9.0 12.0 15.0 18.0 21.0 9.0 12.0 15.0 18.0 21.0 9.0 12.0 15.0 18.0 21.0 9.0 12.0 15.0 18.0 21.0 9.0 12.0 15.0 18.0 21.0 9.0 12.0 15.0 18.0 21.0 9.0 12.0 15.0 18.0 21.0 9.0 12.0 15.0 18.0 21.0 9.0 12.0 15.0 18.0 21.0 18.0 21.0 88.8 90.
Performance Data Table 23. Heating capacities (gross) - 6 tons GEV*072 EWT GPM Gross Cap Mbtuh Absorb Mbtuh Comp Power kW LWT Feet Head 25 25 25 32 32 32 32 32 45 45 45 45 45 50 50 50 50 50 55 55 55 55 55 68 68 68 68 68 75 75 75 75 75 86 86 86 86 86 15.0 18.0 21.0 9.0 12.0 15.0 18.0 21.0 9.0 12.0 15.0 18.0 21.0 9.0 12.0 15.0 18.0 21.0 9.0 12.0 15.0 18.0 21.0 9.0 12.0 15.0 18.0 21.0 9.0 12.0 15.0 18.0 21.0 9.0 12.0 15.0 18.0 21.0 46.2 47.1 47.8 49.1 50.9 51.8 52.6 53.1 58.9 61.2 62.5 63.4 64.
Performance Data Table 25. Gross cooling capacities - 7½ tons - GEV*090 EWT GPM Gross Cap Mbtuh Gross Sen Mbtuh SHR 45 45 45 45 45 55 55 55 55 55 59 59 59 59 59 68 68 68 68 68 77 77 77 77 77 86 86 86 86 86 95 95 95 95 95 105 105 105 105 105 115 115 115 115 115 120 120 11.3 15.0 18.8 22.5 26.3 11.3 15.0 18.8 22.5 26.3 11.3 15.0 18.8 22.5 26.3 11.3 15.0 18.8 22.5 26.3 11.3 15.0 18.8 22.5 26.3 11.3 15.0 18.8 22.5 26.3 11.3 15.0 18.8 22.5 26.3 11.3 15.0 18.8 22.5 26.3 11.3 15.0 18.8 22.5 26.3 22.5 26.
Performance Data Table 26. Heating capacities (gross) - 7½ tons GEV*090 EWT GPM Gross Cap Mbtuh Absorb Mbtuh Comp Power kW LWT Feet Head 25 25 25 32 32 32 32 32 45 45 45 45 45 50 50 50 50 50 55 55 55 55 55 68 68 68 68 68 75 75 75 75 75 86 86 86 86 86 18.8 22.5 26.3 11.3 15.0 18.8 22.5 26.3 11.3 15.0 18.8 22.5 26.3 11.3 15.0 18.8 22.5 26.3 11.3 15.0 18.8 22.5 26.3 11.3 15.0 18.8 22.5 26.3 11.3 15.0 18.8 22.5 26.3 11.3 15.0 18.8 22.5 26.3 55.7 57.0 58.9 59.1 61.1 62.4 63.3 64.5 70.7 73.1 74.7 75.
Performance Data Table 28. Gross cooling capacities - 10 tons GEV*120 EWT GPM Gross Cap Mbtuh Gross Sen Mbtuh SHR 45 45 45 45 45 55 55 55 55 55 59 59 59 59 59 68 68 68 68 68 77 77 77 77 77 86 86 86 86 86 95 95 95 95 95 105 105 105 105 105 115 115 115 115 115 120 120 15.0 20.0 25.0 30.0 35.0 15.0 20.0 25.0 30.0 35.0 15.0 20.0 25.0 30.0 35.0 15.0 20.0 25.0 30.0 35.0 15.0 20.0 25.0 30.0 35.0 15.0 20.0 25.0 30.0 35.0 15.0 20.0 25.0 30.0 35.0 15.0 20.0 25.0 30.0 35.0 15.0 20.0 25.0 30.0 35.0 30.0 35.
Performance Data Table 29. Heating capacities (gross) - 10 tons GEV*120 EWT GPM Gross Cap Mbtuh Absorb Mbtuh Comp Power kW LWT Feet Head 25 25 25 32 32 32 32 32 45 45 45 45 45 50 50 50 50 50 55 55 55 55 55 68 68 68 68 68 75 75 75 75 75 86 86 86 86 86 25.0 30.0 35.0 15.0 20.0 25.0 30.0 35.0 15.0 20.0 25.0 30.0 35.0 15.0 20.0 25.0 30.0 35.0 15.0 20.0 25.0 30.0 35.0 15.0 20.0 25.0 30.0 35.0 15.0 20.0 25.0 30.0 35.0 15.0 20.0 25.0 30.0 35.0 74.7 75.8 76.5 78.5 81.1 82.8 84.0 84.9 93.1 96.2 98.5 100.
Performance Data Table 31. Gross cooling capacities - 12½ tons GEV*150 EWT GPM Gross Cap Mbtuh Gross Sen Mbtuh SHR 45 45 45 45 45 55 55 55 55 55 59 59 59 59 59 68 68 68 68 68 77 77 77 77 77 86 86 86 86 86 95 95 95 95 95 105 105 105 105 105 115 115 115 115 115 120 120 18.8 25.0 31.3 37.5 43.8 18.8 25.0 31.3 37.5 43.8 18.8 25.0 31.3 37.5 43.8 18.8 25.0 31.3 37.5 43.8 18.8 25.0 31.3 37.5 43.8 18.8 25.0 31.3 37.5 43.8 18.8 25.0 31.3 37.5 43.8 18.8 25.0 31.3 37.5 43.8 18.8 25.0 31.3 37.5 43.8 37.5 43.
Performance Data Table 32. Heating capacities (gross) - 12½ tons GEV*150 EWT GPM Gross Cap Mbtuh Absorb Mbtuh Comp Power kW LWT Feet Head 25 25 25 32 32 32 32 32 45 45 45 45 45 50 50 50 50 50 55 55 55 55 55 68 68 68 68 68 75 75 75 75 75 86 86 86 86 86 31.3 37.5 43.8 18.8 25.0 31.3 37.5 43.8 18.8 25.0 31.3 37.5 43.8 18.8 25.0 31.3 37.5 43.8 18.8 25.0 31.3 37.5 43.8 18.8 25.0 31.3 37.5 43.8 18.8 25.0 31.3 37.5 43.8 18.8 25.0 31.3 37.5 43.8 106.0 107.2 108.3 111.2 114.8 116.5 118.1 119.1 131.3 135.
Performance Data Table 34. Gross cooling capacities - 15 tons GEV*180 EWT GPM Gross Cap Mbtuh Gross Sen Mbtuh SHR 45 45 45 45 45 55 55 55 55 55 59 59 59 59 59 68 68 68 68 68 77 77 77 77 77 86 86 86 86 86 95 95 95 95 95 105 105 105 105 105 115 115 115 115 115 120 120 22.5 30.0 37.5 45.0 52.5 22.5 30.0 37.5 45.0 52.5 22.5 30.0 37.5 45.0 52.5 22.5 30.0 37.5 45.0 52.5 22.5 30.0 37.5 45.0 52.5 22.5 30.0 37.5 45.0 52.5 22.5 30.0 37.5 45.0 52.5 22.5 30.0 37.5 45.0 52.5 22.5 30.0 37.5 45.0 52.5 45.0 52.
Performance Data Table 35. Heating capacities (gross) - 15 tons GEV*180 EWT GPM Gross Cap Mbtuh Absorb Mbtuh Comp Power kW LWT Feet Head 25 25 32 32 32 32 32 45 45 45 45 45 50 50 50 50 50 55 55 55 55 55 68 68 68 68 68 75 75 75 75 75 86 86 86 86 86 45.0 52.5 22.5 30.0 37.5 45.0 52.5 22.5 30.0 37.5 45.0 52.5 22.5 30.0 37.5 45.0 52.5 22.5 30.0 37.5 45.0 52.5 22.5 30.0 37.5 45.0 52.5 22.5 30.0 37.5 45.0 52.5 22.5 30.0 37.5 45.0 52.5 132.2 133.2 137.3 141.0 143.6 144.8 145.9 160.8 165.4 168.5 170.
Performance Data Table 37. Gross cooling capacities - 20 tons GEV*240 EWT GPM Gross Cap Mbtuh Gross Sen Mbtuh SHR 45 45 45 45 45 55 55 55 55 55 59 59 59 59 59 68 68 68 68 68 77 77 77 77 77 86 86 86 86 86 95 95 95 95 95 105 105 105 105 105 115 115 115 115 115 120 120 30.0 40.0 50.0 60.0 70.0 30.0 40.0 50.0 60.0 70.0 30.0 40.0 50.0 60.0 70.0 30.0 40.0 50.0 60.0 70.0 30.0 40.0 50.0 60.0 70.0 30.0 40.0 50.0 60.0 70.0 30.0 40.0 50.0 60.0 70.0 30.0 40.0 50.0 60.0 70.0 30.0 40.0 50.0 60.0 70.0 60.0 70.
Performance Data Table 38. Heating capacities (gross) - 20 tons GEV*240 EWT GPM Gross Cap Mbtuh Absorb Mbtuh Comp Power kW LWT Feet Head 25 25 25 32 32 32 32 32 45 45 45 45 45 50 50 50 50 50 55 55 55 55 55 68 68 68 68 68 75 75 75 75 75 86 86 86 86 86 50.0 60.0 70.0 30.0 40.0 50.0 60.0 70.0 30.0 40.0 50.0 60.0 70.0 30.0 40.0 50.0 60.0 70.0 30.0 40.0 50.0 60.0 70.0 30.0 40.0 50.0 60.0 70.0 30.0 40.0 50.0 60.0 70.0 30.0 40.0 50.0 60.0 70.0 154.9 157.0 158.6 162.8 168.1 171.6 173.9 175.7 192.9 199.
Performance Data Table 40. Gross cooling capacities - 25 tons GEV*300 EWT GPM Gross Cap Mbtuh Gross Sen Mbtuh SHR 45 45 45 45 45 55 55 55 55 55 59 59 59 59 59 68 68 68 68 68 77 77 77 77 77 86 86 86 86 86 95 95 95 95 95 105 105 105 105 105 115 115 115 115 115 120 120 37.5 50.0 62.5 75.0 87.5 37.5 50.0 62.5 75.0 87.5 37.5 50.0 62.5 75.0 87.5 37.5 50.0 62.5 75.0 87.5 37.5 50.0 62.5 75.0 87.5 37.5 50.0 62.5 75.0 87.5 37.5 50.0 62.5 75.0 87.5 37.5 50.0 62.5 75.0 87.5 37.5 50.0 62.5 75.0 87.5 75.0 87.
Performance Data Table 41. Heating capacities (gross) - 25 tons GEV*300 EWT GPM Gross Cap Mbtuh Absorb Mbtuh Comp Power kW LWT Feet Head 25 25 25 32 32 32 32 32 45 45 45 45 45 50 50 50 50 50 55 55 55 55 55 68 68 68 68 68 75 75 75 75 75 86 86 86 86 86 62.5 75.0 87.5 37.5 50.0 62.5 75.0 87.5 37.5 50.0 62.5 75.0 87.5 37.5 50.0 62.5 75.0 87.5 37.5 50.0 62.5 75.0 87.5 37.5 50.0 62.5 75.0 87.5 37.5 50.0 62.5 75.0 87.5 37.5 50.0 62.5 75.0 87.5 206.6 209.3 211.4 216.0 223.0 227.6 230.9 233.3 254.4 263.
Performance Data Table 43. Cooling Entering Air WB F 44.5 49.4 56.3 60.3 63.2 66.2 72.1 77.1 Correction factors for variation in entering air temperature - 6 tons GEH*072 Cooling Capacity Cooling Comp Power Watts 65.6 70.6 75.6 80.6 85.6 0.926 0.926 0.927 0.928 0.953 1.000 1.114 1.214 0.982 0.982 0.982 0.983 0.989 1.000 1.020 1.029 0.951 0.952 0.798 0.619 0.492 — — — 1.020 1.021 0.997 0.835 0.705 0.573 — — 1.092 1.093 1.094 1.049 0.922 0.789 0.518 — * * * * 1.140 1.000 0.731 0.
Performance Data Table 47. Cooling Entering Air WB F 44.5 49.4 56.3 60.3 63.2 66.2 72.1 77.1 Correction factors for variation in entering air temperature - 15 tons GEH*180 Cooling Capacity Cooling Comp Power Watts 65.6 70.6 75.6 80.6 85.6 0.940 0.941 0.942 0.943 0.962 1.000 1.094 1.185 0.985 0.985 0.986 0.986 0.991 1.000 1.022 1.038 1.004 1.005 0.808 0.607 0.461 — — — 1.067 1.068 1.038 0.839 0.689 0.536 — — 1.132 1.133 1.135 1.072 0.923 0.766 0.457 — * * * * 1.158 1.000 0.687 0.
Performance Data Table 51. Cooling Entering Air WB F 44.5 49.4 56.3 60.3 63.2 66.2 72.1 77.1 Correction factors for variation in entering air temperature - 12½ tons GEV*150 Cooling Capacity Cooling Comp Power Watts 65.6 70.6 75.6 80.6 85.6 0.936 0.937 0.938 0.938 0.961 1.000 1.088 1.171 0.994 0.994 0.994 0.994 0.996 1.000 1.008 1.015 1.018 1.018 0.809 0.603 0.449 — — — 1.081 1.214 1.047 0.841 0.683 0.522 — — 1.147 1.147 1.149 1.077 0.924 0.758 0.431 — * * * * 1.162 1.000 0.672 0.
Fan Performance Data Figure 2. Fan performance curve - GEH*072(a) 3.0 2.5 Total Static Pressure (in H20) 1300 RPM 2.0 1200 RPM 55%WO 60%WO 1100 RPM 70% WO 1.5 1000 RPM 80% WO 900 RPM 1.0 800 RPM 700 RPM 90% WO 1.50 bhp 2.00 bhp 60 0 RPM 1.00 bhp 0.5 0.0 0 500 1000 1500 2000 Airflow (cfm) 2500 3000 3500 4000 4500 (a) Includes wet coil, no filter Table 55.
Fan Performance Data Figure 3. Fan performance curve - GEH*090(a) 3.0 1400 RPM 2.5 55%WO 60%WO Total Static Pressure (in H20) 1300 RPM 2.0 1200 RPM 70% WO 1100 RPM 1.5 80% WO 1000 RPM 900 RPM 1.0 800 RPM 90% WO 700 RPM 3.00 bhp 2.00 bhp 1.50 bhp 60 0 RPM 1.00 bhp 0.5 0.0 0 500 1000 1500 2000 2500 Airflow (cfm) 3000 3500 4000 4500 5000 (a) Includes wet coil, no filter Table 56. 46 Fan performance curve - GEH*090 (includes wet coil, no filter) 0.
Fan Performance Data Figure 4. Fan performance curve - GEH*120(a) 4.0 3.5 1600 RPM 55%WO 60%WO Total Static Pressure (in H20) 1500 RPM 3.0 70% WO 1400 RPM 2.5 1300 RPM 80% WO 2.0 1200 RPM 1100 RPM 1.5 90% WO 1000 RPM 900 RPM 5.00 bhp 3.00 bhp 2.00 bhp 1.00 bhp 0.5 1.50 bhp 1.0 0.0 0 500 1000 1500 2000 2500 3000 Airflow (cfm) 3500 4000 4500 5000 5500 6000 (a) Includes wet coil, no filter Table 57.
Fan Performance Data Figure 5. Fan performance curve - GEH*150(a) 4.0 3.5 1200 RPM 40%WO 50%WO Total Static Pressure (in H20) 3.0 1100 RPM 60%WO 2.5 1000 RPM 70% WO 2.0 900 RPM 80% WO 1.5 800 RPM 700 RPM 90% WO 1.0 600 RPM 5.00 bhp 3.00 bhp 2.00 bhp 1.00 bhp 1.50 bhp 500 RPM 0.5 0.0 0 1000 2000 3000 4000 5000 Airflow (cfm) 6000 7000 8000 9000 (a) Includes wet coil, no filter Table 58.
Fan Performance Data Figure 6. 4.0 Fan performance curve - GEH*180(a) 1300 RPM 40%WO 50%WO 3.5 1200 RPM Total Static Pressure (in H20) 60%WO 3.0 1100 RPM 70% WO 2.5 1000 RPM 2.0 1.5 80% WO 900 RPM 800 RPM 90% WO 700 RPM 1.0 7.50 bhp 5.00 bhp 3.00 bhp 2.00 bhp 1.00 bhp 0.5 1.50 bhp 600 RPM 0.0 0 1000 2000 3000 4000 5000 Airflow (cfm) 6000 7000 8000 9000 10000 (a) Includes wet coil, no filter Table 59.
Fan Performance Data Figure 7. Fan performance curve (top supply) - GEV*072(a) 3.0 1300 RPM Total Static Pressure (in H20) 2.5 45%WO 1200 RPM 50%WO 2.0 60%WO 1100 RPM 70% WO 1.5 1000 RPM 900 RPM 80% WO 1.0 800 RPM 700 RPM 90% WO 2.00 bhp 1.50 bhp 600 RPM 1.00 bhp 0.5 0.0 0 500 1000 1500 2000 2500 Airflow (cfm) 3000 3500 4000 4500 (a) Includes wet coil, no filter Table 60.
Fan Performance Data Figure 8. Fan performance curve (front/back supply) - GEV*072(a) 3.0 1300 RPM Total Static Pressure (in H20) 2.5 1200 RPM 45%WO 2.0 50%WO 1100 RPM 60%WO 1000 RPM 1.5 70% WO 900 RPM 1.0 80% WO 800 RPM 700 RPM 90% WO 2.00 bhp 1.50 bhp 600 RPM 1.00 bhp 0.5 0.0 0 500 1000 1500 2000 2500 Airflow (cfm) 3000 3500 4000 4500 (a) Includes wet coil, no filter Table 61.
Fan Performance Data Figure 9. Fan performance curve (top supply) - GEV*090(a) 3.0 1400 RPM 45%WO 50%WO 1300 RPM 2.5 Total Static Pressure (in H20) 60%WO 1200 RPM 2.0 70% WO 1100 RPM 1.5 1000 RPM 80% WO 900 RPM 1.0 800 RPM 3.00 bhp 700 RPM 600 RPM 2.00 bhp 1.50 bhp 1.00 bhp 0.5 90% WO 0.0 0 500 1000 1500 2000 2500 3000 Airflow (cfm) 3500 4000 4500 5000 5500 (a) Includes wet coil, no filter Table 62.
Fan Performance Data Figure 10. Fan performance curve (front/back supply) - GEV*090(a) 3.0 Total Static Pressure (in H20) 45%WO 1300 RPM 2.5 50%WO 1200 RPM 60%WO 2.0 1100 RPM 70% WO 1.5 1000 RPM 80% WO 900 RPM 1.0 800 RPM 3.00 bhp 700 RPM 600 RPM 2.00 bhp 1.50 bhp 1.00 bhp 0.5 90% WO 0.0 0 500 1000 1500 2000 2500 3000 Airflow (cfm) 3500 4000 4500 5000 5500 (a) Includes wet coil, no filter Table 63.
Fan Performance Data Figure 11. Fan performance curve (top supply) - GEV*120(a) 4.0 1600 RPM 45%WO 50%WO 3.5 1500 RPM 1400 RPM 70% WO 2.5 1300 RPM 1200 RPM 2.0 80% WO 1100 RPM 1.5 1000 RPM 900 RPM 1.0 90% WO 800 RPM 5.00 bhp Total Static Pressure (in H20) 60%WO 3.0 3.00 bhp 1.50 bhp 0.5 2.00 bhp 700 RPM 0.0 0 1000 2000 3000 4000 Airflow (cfm) 5000 6000 7000 (a) Includes wet coil, no filter Table 64.
Fan Performance Data Figure 12. Fan performance curve (front/back supply) - GEV*120(a) 4.0 45%WO 3.5 50%WO Total Static Pressure (in H20) 1500 RPM 3.0 2.5 60%WO 1400 RPM 1300 RPM 70% WO 1200 RPM 2.0 80% WO 1100 RPM 1.5 1000 RPM 900 RPM 90% WO 800 RPM 5.00 bhp 1.0 3.00 bhp 1.50 bhp 2.00 bhp 700 RPM 0.5 0.0 0 1000 2000 3000 Airflow (cfm) 4000 5000 6000 7000 (a) Includes wet coil, no filter Table 65.
Fan Performance Data Figure 13. Fan performance curve (top supply) - GEV*150(a) 4.0 3.5 1200 RPM 40%WO Total Static Pressure (in H20) 3.0 50%WO 1100 RPM 60%WO 2.5 1000 RPM 70% WO 2.0 900 RPM 80% WO 1.5 800 RPM 700 RPM 1.0 90% WO 600 RPM 500 RPM 5.00 bhp 3.00 bhp 2.00 bhp 1.50 bhp 0.5 0.0 0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 Airflow (cfm) (a) Includes wet coil, no filter Table 66.
Fan Performance Data Figure 14. Fan performance curve (front/back supply) - GEV*150(a) 40%WO 50%WO 3.0 1200 RPM 60%WO 2.5 1100 RPM Total Static Pressure (in H20) 70% WO 1000 RPM 2.0 80% WO 900 RPM 1.5 800 RPM 700 RPM 1.0 90% WO 600 RPM 500 RPM 27 0 1000 2000 3000 4000 5000 6000 3.00 bhp 1.50 bhp 0.0 2.00 bhp 5.00 bhp 0.5 7000 8000 9000 10000 11000 Airflow (cfm) (a) Includes wet coil, no filter Table 67.
Fan Performance Data Figure 15. Fan performance curve (top supply) - GEV*180(a) 4.0 40%WO 1300 RPM 50%WO 3.5 1200 RPM 60%WO Total Static Pressure (in H20) 3.0 1100 RPM 70% WO 2.5 1000 RPM 2.0 80% WO 900 RPM 1.5 800 RPM 700 RPM 90% WO 1.0 600 RPM 500 RPM 10.0 bhp 7.50 bhp 5.00 bhp 3.00 bhp 2.00 bhp 0.5 0.0 0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 11000 12000 Airflow (cfm) (a) Includes wet coil, no filter Table 68.
Fan Performance Data Figure 16. Fan performance curve (front/back supply) - GEV*180(a) 40%WO 4.0 50%WO 1300 RPM 3.5 60%WO 1200 RPM 3.0 Total Static Pressure (in H20) 70% WO 1100 RPM 2.5 1000 RPM 80% WO 2.0 900 RPM 1.5 800 RPM 90% WO 1.0 700 RPM 500 RPM 7.50 bhp 5.00 bhp 3.00 bhp 2.00 bhp 0.5 10.0 bhp 600 RPM 0.0 0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 11000 12000 Airflow (cfm) (a) Includes wet coil, no filter Table 69.
Fan Performance Data Figure 17. Fan performance curve (top supply) - GEV*240(a) 5.0 1800 RPM 4.5 1700 RPM 52%WO 4.0 1600 RPM 60%WO Total Static Pressure (in H20) 3.5 1500 RPM 3.0 1400 RPM 70% WO 2.5 1300 RPM 1200 RPM 80% WO 2.0 1100 RPM 1.5 1000 RPM 1.0 800 RPM 900 RPM 90% WO 10.0hp 7.50 bhp 5.00 bhp 600 RPM 500 RPM 3.00 bhp 0.5 15.0 bhp 700 RPM 0.0 0 2500 5000 7500 10000 12500 15000 Airflow (cfm) (a) Includes wet coil, no filter Table 70.
Fan Performance Data Figure 18. Fan performance curve (front/back supply) - GEV*240(a) (a) Includes wet coil, no filter Table 71. Std Airflow CFM 6400 7200 8000 8800 9600 Std Airflow CFM 6400 7200 8000 8800 9600 Std Airflow CFM 6400 7200 8000 8800 9600 Std Airflow CFM 6400 7200 8000 8800 9600 Std Airflow CFM 6400 7200 8000 8800 9600 Legend (a) (b) (c) (d) (e) (g) Fan performance curve (front/back supply) - GEV*240 (includes wet coil, no filter) 0.1 RPM — — 933(a) 1021(a) 1109(c) BHP — — 3.58(a) 4.
Fan Performance Data Figure 19. Fan performance curve (with 11x15 blower wheel) - GEV*300(a) 5.0 1500 RPM 4.5 1400 RPM 4.0 1300 RPM 62%WO Total Static Pressure (in H20) 3.5 1200 RPM 70% WO 3.0 1100 RPM 2.5 1000 RPM 80% WO 2.0 900 RPM 1.5 800 RPM 90% WO 700 RPM 1.0 15.0 bhp 600 RPM 500 RPM 0 2500 5000 7500 10000 10.0hp 0.0 7.50 bhp 5.00 bhp 0.5 12500 15000 17500 20000 Airflow (cfm) (a) Includes wet coil, no filter Table 72.
Fan Performance Data Figure 20. Fan performance curve (top supply with 12x12 blower wheel) - GEV*300(a) 5.0 1800 RPM 4.5 1700 RPM 52%WO 4.0 1600 RPM 60%WO Total Static Pressure (in H20) 3.5 1500 RPM 3.0 1400 RPM 70% WO 2.5 1300 RPM 1200 RPM 80% WO 2.0 1100 RPM 1.5 1000 RPM 1.0 800 RPM 900 RPM 90% WO 10.0hp 7.50 bhp 5.00 bhp 600 RPM 500 RPM 3.00 bhp 0.5 15.0 bhp 700 RPM 0.0 0 2500 5000 7500 10000 12500 15000 Airflow (cfm) (a) Includes wet coil, no filter Table 73.
Fan Performance Data Figure 21. Fan performance curve (front/back supply with 11x15 blower wheel) - GEV*300(a) (a) Includes wet coil, no filter Table 74. Std Airflow CFM 8000 9000 10000 11000 12000 Std Airflow CFM 8000 9000 10000 11000 12000 Std Airflow CFM 8000 9000 10000 11000 12000 Std Airflow CFM 8000 9000 10000 11000 12000 Legend (a) (b) (c) (d) (e) 64 Fan performance curve (front/back supply with 11x15 blower wheel) - GEV*300 (includes wet coil, no filter) 0.
Fan Performance Data Figure 22. Fan performance curve (front/back supply with 12x12 blower wheel) - GEV*300(a) (a) Includes wet coil, no filter Table 75. Fan performance curve (front/back supply with 12x12 blower wheel) - GEV*300 (includes wet coil, no filter) Std Airflow CFM 8000 9000 10000 11000 12000 Std Airflow CFM 8000 9000 10000 11000 12000 Unit External Static Pressure inches W.G. (Wet Coil, 3% Drive Loss Included & No Return Air Filter) 2.0 2.1 2.2 2.3 1.8 1.
Fan Performance Data Waterside Economizer Performance Data Table 76. Waterside economizer performance data(a) (6 to 25 Tons) Input Data Tonnage Unit of Heat Model Pump Number SCFM 6.00 7.50 10.00 12.50 15.00 6.00 7.50 10.00 12.50 15.00 20.00 25.00 Output Data GPM Air Total Sensible LVG. Air LVG. Air Standard LVG.Fluid Fluid PD Fluid PD Velocity Capacity Capacity DB WB APD Temp. Coil In Coil Out (SFPM) (MBh) (MBh) (Deg F) (Deg F) (IN WG) (Deg F) (FT H2O) (FT H2O) GEH*072 2400 13.2 400 65.
Fan Performance Data Table 77. Antifreeze correction factors 10% 20% Methanol Concentration by Volume 30% 40% 50% Cool Capacity Heat Capacity Pressure Drop .9980 .9950 1.023 .9965 .9898 1.057 .9949 .9846 1.091 .9932 .9794 1.122 .9915 .9742 1.160 Cool Capacity Heat Capacity Pressure Drop .9955 .9925 1.024 .9912 .9848 1.068 .9870 .9770 1.124 .9830 .9690 1.188 .9790 .9610 1.263 Cool Capacity Heat Capacity Pressure Drop .9934 .9863 1.040 .9804 .9603 1.174 .9739 .9477 1.273 .9681 .9350 1.
Electrical Data Table 78. Model No. Electrical data: 6 to 25 tons - single speed blower motor Volts Total FLA Comp RLA (ea) Comp LRA (ea) No. of Comp. Maximum Blower Blower Fan Minimum Overcurrent Motor Motor Motor Circuit Protective Cmp MCC FLA HP No. Ampacity Device GEH - Horizontal Units GEH072 208/60/1 39.9 16.7 79 2 26 6.5 1.0 1 44.08 60 GEH072 230/60/1 39.9 16.7 79 2 26 6.5 1.0 1 44.08 60 GEH072 208/60/1 42.7 16.7 79 2 26 9.3 1.5 1 46.
Electrical Data Table 78. Electrical data: 6 to 25 tons - single speed blower motor (continued) Maximum Blower Blower Fan Minimum Overcurrent Motor Motor Motor Circuit Protective Cmp MCC FLA HP No. Ampacity Device Model No. Volts Total FLA Comp RLA (ea) Comp LRA (ea) GEH120 230/60/3 36.8 16 110 2 24.9 4.8 1.5 1 40.80 50 GEH120 380-415/50/3 24.2 10.6 74 2 16.5 3.0 1.5 1 26.85 35 GEH120 460/60/3 18.0 7.8 52 2 12.1 2.4 1.5 1 19.95 25 GEH120 208/60/3 39.
Electrical Data Table 78. Electrical data: 6 to 25 tons - single speed blower motor (continued) Maximum Blower Blower Fan Minimum Overcurrent Motor Motor Motor Circuit Protective Cmp MCC FLA HP No. Ampacity Device Model No. Volts Total FLA Comp RLA (ea) Comp LRA (ea) GEH180 230/60/3 58.2 25 164 2 39 8.2 3.0 1 64.45 80 GEH180 460/60/3 28.5 12.2 100 2 19 4.1 3.0 1 31.55 40 GEH180 575/60/3 21.3 9 78 2 14 3.3 3.0 1 23.55 30 GEH180 208/60/3 64.0 25 164 2 39 14.
Electrical Data Table 78. Electrical data: 6 to 25 tons - single speed blower motor (continued) Maximum Blower Blower Fan Minimum Overcurrent Motor Motor Motor Circuit Protective Cmp MCC FLA HP No. Ampacity Device Model No. Volts Total FLA Comp RLA (ea) Comp LRA (ea) GEV090 208/60/3 32.0 14.5/10.4 98/73 2 22.6/16.3 7.1 2.0 1 35.63 GEV090 230/60/3 31.1 14.5/10.4 98/73 2 22.6/16.3 6.2 2.0 1 34.73 45 GEV090 380-415/50/3 22.6 9.6 64 2 15 3.4 2.0 1 25.
Electrical Data Table 78. Electrical data: 6 to 25 tons - single speed blower motor (continued) Maximum Blower Blower Fan Minimum Overcurrent Motor Motor Motor Circuit Protective Cmp MCC FLA HP No. Ampacity Device Model No. Volts Total FLA Comp RLA (ea) Comp LRA (ea) GEV150 380-415/50/3 32.6 12.2 101 2 19 8.2 5.0 1 35.65 45 GEV150 460/60/3 27.7 10.6 75 2 16.5 6.5 5.0 1 30.35 40 GEV150 575/60/3 20.7 7.7 54 2 12 5.3 5.0 1 22.63 30 GEV180 208/60/3 59.
Electrical Data Table 78. Electrical data: 6 to 25 tons - single speed blower motor (continued) Maximum Blower Blower Fan Minimum Overcurrent Motor Motor Motor Circuit Protective Cmp MCC FLA HP No. Ampacity Device Model No. Volts Total FLA Comp RLA (ea) Comp LRA (ea) GEV300 460/60/3 43.7 18.6 125 2 29 6.5 5.0 1 48.35 GEV300 575/60/3 34.7 14.7 100 2 23 5.3 5.0 1 38.38 50 GEV300 208/60/3 116.2 48.1 245 2 75 20.0 7.5 1 128.23 175 GEV300 230/60/3 115.6 48.
Electrical Data Table 79. Electrical data: 6 to 25 tons - two speed blower motor (continued) Maximum Blower Blower Fan Minimum Overcurrent Motor Motor Motor Circuit Protective Cmp MCC FLA HP No. Ampacity Device Model No. Volts Total FLA Comp RLA (ea) Comp LRA (ea) GEH090 460/60/3 16.6 6.3 55 2 9.9 4.0 3.0 1 18.18 20 GEH120 208/60/3 36.9 16 110 2 24.9 4.9 1.5 1 40.90 50 GEH120 230/60/3 36.4 16 110 2 24.9 4.4 1.5 1 40.40 50 GEH120 460/60/3 17.8 7.8 52 2 12.
Electrical Data Table 79. Electrical data: 6 to 25 tons - two speed blower motor (continued) Maximum Blower Blower Fan Minimum Overcurrent Motor Motor Motor Circuit Protective Cmp MCC FLA HP No. Ampacity Device Model No. Volts Total FLA Comp RLA (ea) Comp LRA (ea) GEV072 460/60/3 13.1 5.8 38 2 9 1.5 1.0 1 14.55 20 GEV072 208/60/3 25.7 10.4 73 2 16.3 4.9 1.5 1 28.30 35 GEV072 230/60/3 25.2 10.4 73 2 16.3 4.4 1.5 1 27.80 35 GEV072 460/60/3 13.8 5.8 38 2 9 2.
Electrical Data Table 79. Electrical data: 6 to 25 tons - two speed blower motor (continued) Maximum Blower Blower Fan Minimum Overcurrent Motor Motor Motor Circuit Protective Cmp MCC FLA HP No. Ampacity Device Model No. Volts Total FLA Comp RLA (ea) Comp LRA (ea) GEV180 208/60/3 58.8 25 164 2 39 8.8 3.0 1 65.05 90 GEV180 230/60/3 58.0 25 164 2 39 8.0 3.0 1 64.25 80 GEV180 460/60/3 28.4 12.2 100 2 19 4.0 3.0 1 31.45 40 GEV180 208/60/3 64.6 25 164 2 39 14.
Dimensional Data Figure 24. GEH 6-10 tons (072-120)—right return, left supply 20" (508) SERVICE CLEARANCE 36" (914) SERVICE CLEARANCE 4 5/8" (117) 79" (2007) 74 1/2" (1892) 1 3/4" (44) 36" (914) 2 1/8" (54) 23 7/8" (606) BLOWER ACCESS PANEL 40 5/8" (1032) 7 5/8" (194) TOP VIEW 18 3/8" (467) 81" (2057) 85" (2159) 1" (25.4) 24 VOLT 1 1/8" (28.6) DIA. 1 1/2" (38) ) 4 7/8" (124) 1 1/4" (32) 5/8" (16) W.O.
Dimensional Data Figure 25. GEH 6-10 tons (072-120)—right return/back supply 36" (914) SERVICE CLEARANCE 74 1/2" (1892) 1 3/4" (44) 81" (2057) 85" (2159) BLOWER ACCESS PANEL 40 5/8" (1032) 36" (914) 18 3/8" (467) 6 1/8" (156) 2 1/8" (54) 23 7/8" (606) 4 5/8" (117) 79" (2007) 20" (508) SERVICE CLEARANCE TOP VIEW 1 1/4" (32) 5/8" (16) W.O. "D" NPTI 4 7/8" (124) 24 VOLT 1 1/8" (28.6) DIA.
Dimensional Data Figure 26. GEH 6-10 tons (072-120) - left return/right supply 36" (914) SERVICE CLEARANCE 79" (2007) 4 5/8" (117) 40 5/8" (1032) 20" (508) SERVICE CLEARANCE 74 1/2" (1892) 1 3/4" (44) 36" (914) 24 3/4" (629) 1 1/4" (32) 7 5/8" (194) TOP VIEW BLOWER ACCESS PANEL 18 3/8" (467) 81" (2057) 85" (2159) 23 1/4" (591) 16 1/2" (419) A 1" (25.4) 5/8" (16) 24 VOLT 1 1/8" (28.6) DIA. 1 1/4" (32) W.O.
Dimensional Data GEH 6-10 tons (072-120) - left return/back supply 36" (914) SERVICE CLEARANCE 4 5/8" (117) 79" (2007) 1 3/4" (44) 36" (914) 18 3/8" (467) 81" (2057) 85" (2159) 20" (508) SERVICE CLEARANCE 6 1/8" (156) 40 5/8" (1032) 74 1/2" (1892) 24 3/4" (629) 1 1/4" (32) Figure 27. TOP VIEW BLOWER ACCESS PANEL 23 1/4" (591) 16 1/2" (419) A 5/8" (16) 24 VOLT 1 1/8" (28.6) DIA. 1 1/4" (32) W.O.
Dimensional Data Figure 28. GEH 12½-15 tons (150-180) - right return/left supply 20" (508) SERVICE CLEARANCE 36" (914) SERVICE CLEARANCE 4 5/8" (117) 85" (2159) 74 1/2" (1892) 2" (51) 46 5/8" 42" (1184) (1067) 2 1/4" (57) 29 3/4" (756) BLOWER ACCESS PANEL 7 1/8" (181) TOP VIEW 21 3/8" (467) 61 1/4" (1556) W.O. 1 1/2" (38) NPTI 24 VOLT 1 1/8" (28.6) DIA.
Dimensional Data Figure 29. GEH 12½-15 tons (150-180) - right return/back supply 36" (914) SERVICE CLEARANCE 74 1/2" (1892) 2" (41) 46 5/8" 42" (1184) (1067) 21 3/8" (543) 87" (2210) 91" (2311) 7 1/8" (181) 2 1/4" (57) 29 3/4" (756) 4 5/8" (117) 85" (2159) 20" (508) SERVICE CLEARANCE TOP VIEW W.O. 1 1/2" (38) NPTI 24 VOLT 1 1/8" (28.6) DIA.
Dimensional Data Figure 30. GEH 12½-15 tons (150-180) - left return/right supply 36" (914) SERVICE CLEARANCE 85" (2159) 4 5/8" (117) 74 1/2" (1892) 2" (51) 42" (1067) 29 3/4" (756) 7 1/8" (181) TOP VIEW 2 1/4" (57) 46 5/8" (1184) 20" (508) SERVICE CLEARANCE BLOWER ACCESS PANEL 21 3/8" (543) 87" (2210) 39 1/2" (1003) 1" (25.4) 4 7/8" (124) 16 3/4" (425) WCI mounting location 23 3/4" (603) HIGH VOLTAGE 7/8" (22.2) DIA.
Dimensional Data GEH 12½-15 tons (150-180) - left return/back supply 36" (914) SERVICE CLEARANCE 46 5/8" (1184) 74 1/2" (1892) 2" (51) 42" (1067) 21 3/8" (543) 87" (2210) 91" (2311) 20" (508) SERVICE CLEARANCE 29 3/4" (756) 2 1/4" (57) 4 5/8" (117) 85" (2159) 7 1/8" (181) Figure 31. TOP VIEW BLOWER ACCESS PANEL 4 7/8" (124) 16 3/4" (425) WCI mounting location 23 3/4" (603) HIGH VOLTAGE 7/8" (22.2) DIA. LEFT SIDE W.I.
Dimensional Data Figure 32. GEH 6-10 tons (072-120) - right return with waterside economizer(a) 9 7/8" (251) 18 1/2" (470) 50 5/8" (1286) 36" (914) 2 1/8" (54) 23 7/8" (606) C "A" NPTI FOR FIELD RETURN PIPING D E (a) See Figure 50, p. 101 for waterside economizer coil piping diagram. Figure 33.
Dimensional Data Figure 34. GEH 12½-15 tons (150-180) - right return with waterside economizer(a) 9 7/8" (251) 18 1/2" (470) 56 1/2" (1435) 42" (1067) 2 1/4" (57) 29 3/4" (756) 48 3/4" (1238) 1 1/2" (38) NPTI FOR FIELD RETURN PIPING 12" (305) 5 3/8" (137) (a) See Figure 50, p. 101 for waterside economizer coil piping diagram. Figure 35.
Dimensional Data Figure 36. GEV 6-10 tons (072-120) - front return/back supply 15 3/4 (400) ACCESS PANEL FOR SHEAVES AND BELTS SUPPLY OPENING 1" (25.4) DUCT FLANGE 13 18" (333) 31 3/8" 36 1/4" (797) (921) 36" (914) SERVICE CLEARANCE 39 5/8" (1006) 42" (1067) 4 7/8" (124) 20" (508) SERVICE CLEARANCE 1 (25.4) 13 1/2" (343) 38 7/8" (987) 62 5/8" (1591) W.O. "C" NPTI 24 VOLT 1 1/8" (28.6) DRAIN 3/4" NPTI 46 1/2" (1181) WCI mounting location 15" (381) A 3/4" (19) 5" (127) HIGH VOLTAGE 7/8" (22.
Dimensional Data GEV 6-10 tons (072-120) - front return/top supply ACCESS PANEL FOR SHEAVES AND BELTS 15 5/8 (397) 1 1/8" (29) Figure 37. 13 1/4" (337) 13 3/8" (343) 36" (914) SERVICE CLEARANCE 39 5/8" (1006) 42" (1067) 1" (25.4) 20" (508) SERVICE CLEARANCE 4 7/8" (124) 31 3/8" 36 1/4" (797) (921) 63" (1600) 38 7/8" (987) W.O. "C" NPTI 24 VOLT 1 1/8" (28.6) HIGH VOLTAGE 7/8" (22.2) DIA.
Dimensional Data 4 7/8" (124) Figure 38. GEV 6-10 tons (072-120)—back return/front supply 39 5/8" (1006) ACCESS PANEL FOR SHEAVES AND BELTS 36 1/4" 31 3/8" (921) (797) 1 1/8" (29) 13 1/8" (333) 15 3/4 (400) 20" (508) SERVICE CLEARANCE 36" (914) SERVICE CLEARANCE 42" (1067) 13 1/2" (343) 1" (25.4) 38 7/8" (987) W.O. "C" NPTI 24 VOLT 1 1/8" (28.6) DRAIN 3/4" NPTI WCI mounting location 15" (381) HIGH VOLTAGE 7/8" (22.2) DIA.
Dimensional Data 4 7/8" (124) Figure 39. GEV 6-10 tons (072-120) - back return/top supply 39 5/8" (1006) ACCESS PANEL FOR SHEAVES AND BELTS 36 1/4" 31 3/8" (921) (797) 13 1/2" (343) 15 5/8 (397) 36" (914) SERVICE CLEARANCE 42" (1067) 1" (25.4) 20" (508) SERVICE CLEARANCE 1 1/8" (29) 13 1/4" (337) 38 7/8" (987) W.O. "C" NPTI 63" 24 VOLT (1600) 1 1/8" (28.6) WCI mounting location 15" (381) HIGH VOLTAGE 7/8" (22.2) DIA.
Dimensional Data 13" (330) C Figure 40. GEV 6-10 tons (072-120) - waterside economizer 13 1/4" (337) A = TO FIELD RETURN PIPING 2 1/4" (57) Unit GEV A (in.) B (in.) 072,090 1-3/8 (35) 1-3/8 (35) 4 (102) 120 1-5/8 (41) 1-5/8 (41) 4-3/8 (111) WSHP-PRC016E-EN C (in.
Dimensional Data Figure 41. GEV 12½-15 tons (150-180) - front return/back supply 31 1/2" (800) 36 1/4" (921) 10" (254) 74 1/2" (1892) 4 3/4" (121) 81 5/8" (2073) TOP VIEW 18 5/8" (473) 31 1/2" (800) 24 VOLT 1 1/8" (29) O.D. 15 7/8" (403) 38 7/8" (987) W.O. 1 1/2" (38) NPTI 67 5/8" (1718) 6 7/8" (175) DRAIN 3/4" (19) NPTI 49 1/8" (1248) WCI mounting location 20 1/2" (521) HIGH VOLTAGE 7/8" (22) O.D. 27 1/8" (537) 12 1/2" (318) 1" (25.
Dimensional Data Figure 42. GEV 12½-15 tons (150-180) - back return/front supply 81 5/8" (2073) 4 3/4" (121) 36 1/4" (921) 74 1/2" (1892) 31 1/2" (800) 10" (254) TOP VIEW 18 5/8" (473) 31 1/2" (800) 15 7/8" (403) 38 7/8" (987) W.O. 1 1/2" (38) NPTI 1" (25.4) 24 VOLT 1 1/8" (29) O.D. WCI mounting location DRAIN 3/4" (19) NPTI 49 1/8" (1248) 20 1/2" 2 (521) 27 1/8" (537) 6 7/8" (175) 67 5/8" (1718) HIGH VOLTAGE 7/8" (22) O.D. CONTROL BOX ACCESS 12 1/2" (318) FRONT VIEW W.I.
Dimensional Data Figure 43. GEV 12½-15 tons (150-180) - front return/top supply 15 7/8" (403) 31 1/2" (800) 36 1/4" (921) 10" (254) 14 3/8" (365) 74 1/2" (1892) 4 3/4" (121) 81 5/8" (2073) TOP VIEW 18 5/8" (473) 31 1/2" (800) 38 7/8" (98 (987) W.O. 1 1/2" (38) NPTI WCI mounting location 20 1/2" (521) 24 VOLT 1 1/8" (29) O.D. 6 7/8" (175) 68" (1727) HIGH VOLTAGE 7/8" (22) O.D. CONTROL BOX ACCESS 27 1 1/8" (53 (537) 12 1/2" (318) 1" (25.4) SIDE VIEW DRAIN 3/4" (19) NPTI FRONT VIEW W.I.
Dimensional Data Figure 44. GEV 12½-15 tons (150-180) - back return/top supply 81 5/8" (2073) 4 3/4" (121) 74 1/2" (1892) 14 3/8" (365) 36 1/4" (921) 31 1/2" (800) 10" (254) 15 7/8 7/8" (403 (403) TOP VIEW 18 5/8" (473) 31 1/2" (800) 38 7/8" (987) W.O. 1 1/2" (38) NPTI 68" (1727) 1" (25.4) 6 7/8" (175) 24 VOLT 1 1/8" WCI mounting (29) O.D. location HIGH VOLTAGE 7/8" (22) O.D. SIDE VIEW CONTROL BOX ACCESS 20 1/2" 2 (521) 7 1/8" 27 (537) DRAIN 3/4" (19) NPTI 12 1/2" (318) FRONT VIEW W.I.
Dimensional Data Figure 45. GEV 20-25 tons (240-300) - front return/back supply 31 1/2" (800) 36 1/4" (921) 6 1/4" (159) 74 1/2" (1892) 4 3/4" (121) 81 5/8" (2073) TOP VIEW C 19 1/8" (486) A A 24 VOLT 1 1/8" (29) O.D. B 38 7/8" (987) W.O. 2" (51) NPTI 67 5/8" (1718) 6 7/8" (175) DRAIN 3/4" (19) NPTI D WCI mounting location 20 1/2" (521) HIGH VOLTAGE 7/8" (22) O.D. 27 1/8" (537) E 12 1/2" (318) 1" (25.4) SIDE VIEW CONTROL BOX ACCESS 2 3/8" (60) FRONT VIEW W.I.
Dimensional Data Figure 46. GEV 20-25 tons (240-300) - back return/front supply 81 5/8" (2073) 4 3/4" (121) 36 1/4" (921) 74 1/2" (1892) 31 1/2" (800) 6 1/4" (159) TOP VIEW C 19 1/8" (486) A A B 38 7/8" (987) W.O. 2" (51) NPTI 27 1/8" 537) (537) 1" (25.4) 24 VOLT 1 1/8" WCI mounting (29) O.D. location 6 7/8" (175) 6 5/8" 67 ( (1718) DRAIN 3/4" (19) NPTI D 20 1/2" (521) HIGH VOLTAGE 7/8" (22) O.D. CONTROL BOX ACCESS W.I.
Dimensional Data Figure 47. GEV 20-25 tons (240-300) - front return/top supply 36 1/4" (921) 6 1/4" (159) 1 1/4" (32) B 31 1/2" (800) 74 1/2" (1892) 4 3/4" (121) 81 5/8" (2073) TOP VIEW C 19 1/8" (486) A A 38 7/8" (987) (98 W.O. 2" (51) NPTI WCI mounting location 20 1/2" (521) 24 VOLT 1 1/8" (29) O.D. 6 7/8" (175) 68" (1727) DRAIN 3/4" (19) NPTI CONTROL BOX ACCESS 27 1 1/8" (53 (537) D 12 1/2" (318) HIGH VOLTAGE 7/8" (22) O.D. 1" (25.4) FRONT VIEW W.I.
Dimensional Data Figure 48. GEV 20-25 tons (240-300) - back return/top supply 81 5/8" (2073) 4 3/4" (121) 1 1/4 1/4" (32) 36 1/4" (921) 74 1/2" (1892) 31 1/2" (800) B 6 1/4" (159) TOP VIEW C 19 1/8" (486) A A 38 7/8" (987) W.O. 2" (51) NPTI 68" (172 (1727) 1" (25.4) 6 7/8" (175) 24 VOLT 1 1/8" (29) O.D. WCI mounting location CONTROL BOX ACCESS 20 1/2" (521) 27 1/8" (537) DRAIN 3/4" (19) NPTI HIGH VOLTAGE 7/8" (22) O.D. SIDE VIEW MIN.
Dimensional Data Figure 49. GEV 12½-25 tons (150-300) - waterside economizer(a) D 13" (330) TOP VIEW A = TO FIELD RETURN PIPING C SIDE VIEW 2 3/4" (70) FRONT VIEW (a) See Figure 50, p. 101 for waterside economizer coil piping diagram. 100 Unit GEV A (in.) B (in.) C (in.) D (in.
Dimensional Data Figure 50. Waterside economizer coil piping diagram Unit Water Outlet Unit Heat Exchanger WSE Coil Outlet Unit Water Inlet WSE Coil Inlet WSE Coil TEE Port A Port AB 3 Way Valve Please match the entering water port marking with the marking label on the valve prior to using this diagram.
Weights Weight Distribution Approximate weight distribution for the GEH model is indicated in the graphic below. Tolerance on the weights determined are ±15%. Total weights for each unit are available in “General Data,” p.
Controls Deluxe 24V Electronic Controls The deluxe 24V electronic unit control provides component protection devices to maximize system performance to extend the system life. Each device, is factory mounted, wired, and tested in the unit.
Controls indicating the operating mode of the controller. See the unit IOM for diagnostics or troubleshooting through the use of the LEDs. Generic Relay The generic relay is provided for field use. Night setback or pump restart are two options that may be wired to the available relay. An external Class II 24VAC signal will energize the relay coil on terminals R1 and R2.Terminals C (common), NO (normally open), and NC (normally closed) will be provided for the relay contacts.
Controls Stand-alone System The 24V controller may be applied as a standalone control system.The stand-alone design provides accurate temperature control directly through a wall-mounted mercury bulb or electronic thermostat.This system set-up may be utilized in a replacement design where a single unit retrofit is needed. It may be easily interfaced with a field provided control system by way of the factory installed 18-pole terminal strip.
Controls isolation valve(s) are driven open for three minutes and the entering water temperature reading is taken.The determination as to whether or not to utilize electric heat will be made and the controller will take appropriate action. If boilerless electric heat is enabled, then the isolation valve will be closed, shutting down the water flow to the unit.
Controls allows multiple units to share a common space temperature sensor in both stand-alone and building automation applications. Dehumidification Dehumidification for the single and dual circuited water-source heat pump is applicable with the UC400 and ZN524 controller.The controller is capable of directing one stage of DX cooling in conjunction with one stage of reheat (hot gas reheat). Dehumidification can only occur when the controller is in the cooling mode.
Controls Random Start To prevent all of the units in a building from energizing major loads at the same time, the controller observes a random start from 0 to 25 seconds.This timer halts the controller until the random start time expires. Reversing Valve Operation For cooling, the reversing valve output is energized simultaneously with the compressor. It will remain energized until the controller turns on the compressor for heating. At this time, the reversing valve moves to a de-energized state.
Controls Quantity of Networks per Tracer™ Wireless Zone Sensors. The WCI also communicates withTrane wireless zone sensors, eliminating the need for analog receivers. Wired Zone Sensors. Systems using Wireless Comm can also use wired zone sensors. Dimensions 2.896 in (73.55 mm) 1.419 in (36.03 mm) 0.118 in (3.00 mm) 3.385 in (86.0 mm) 4.677 in (118.8 mm) 0.650 in (16.50 mm) R0.71 in (R1.80 mm) TYP 2.480 in (63.0 mm) 0.236 in (6.0 mm) 2.62 in (66.55 mm) 1.344 in (34.
Controls not the limiting factor for proper signal quality. Signal quality is affected by walls, barriers, and general clutter. Output power North America: 100 mW Radio frequency 2.4 GHz (IEEE Std 802.15.4-2003 compliant) (2405–2480 MHz, 5 MHz spacing) Radio channels 16 Address range Group 0–8, Network 1–9 Mounting Fits a standard 2 in. by 4 in. junction box (vertical mount only). Mounting holes are spaced 3.2 in. (83 mm) apart on vertical center line.
Controls Mounting Receiver: Suitable for mounting above or below ceiling grid. Requires 24V power. Factory installed receiver comes mounted to the unit with power provided by associated unit controller transformer. Field installed option provided with associated wire harness for similar power and communication connection. Sensor: Mounts to a 2x4 handi-box or directly to the wall by attaching the back plate and then snapping the sensor body into place.
Thermostats and Zone Sensors Table 81. Thermostat selection for use with the Deluxe Controller Thermostat Part Number X13511536010 Description 3 Heat/2 Cool, Non-programmable commercial thermostat for conventional (rooftop) air conditioners and heat pumps that are configured with or without auxiliary heat. • X13511537010 3 Heat/2 Cool, Programmable commercial thermostat for conventional (rooftop) air conditioners and heat pumps that are configured with or without auxiliary heat.
Thermostats and Zone Sensors Table 82.
Accessories Automatic and Manual Balancing Kits Superior circuit balancing of the HVAC equipment is an important aspect to the overall layout and design of the HVAC system. Proper balance of the system can protect the WSHP equipment while providing a longer equipment life. Trane provides three hose kit selections for equipment balancing.
Accessories Motorized water valve The motorized water valve is installed on the return line of the water loop system between the loop and the loop’s pump module.This isolation device is less expensive and a very effective alternative to the water regulating valve. When the compressor begins running, the valve will open, allowing water to flow through the unit. As the compressor shuts down, the valve slowly closes off.
Control Wiring Figure 52. Deluxe 24V - 208-230V-60 Hz - 3 ph(a) (a) Wiring diagrams provided in the catalog are generic. A unit specific As Built wiring diagram is located on the unit control panel.
Control Wiring Figure 53. Tracer™ ZN524 460V-60 Hz - 3 ph(a) (a) Wiring diagrams provided in the catalog are generic. A unit specific As Built wiring diagram is located on the unit control panel.
Control Wiring Figure 54. UC400(a) (a) Wiring diagrams provided in the catalog are generic. A unit specific As Built wiring diagram is located on the unit control panel.
Control Wiring Figure 55. UC400 with 2 speed motor(a) (a) Wiring diagrams provided in the catalog are generic. A unit specific As Built wiring diagram is located on the unit control panel.
Mechanical Specifications General Equipment is completely assembled, piped, internally wired, fully charged with R-410A and test operated at the factory. Filters, thermostat field interface terminal strip, and all safety controls are furnished and factory installed. The system water inlet and outlet connections are female NPT composed of copper. All units are ETL certified and under 10 tons are AHRI certified. Larger units are rated in accordance with ISO-ARI 13256-1.
Mechanical Specifications The refrigerant coil distributor assembly is of orifice style with round copper distributor tubes.The tubes are sized consistently with the capacity of the coil. Suction header is fabricated from rounded copper pipe. A thermostatic expansion valve is factory selected and installed for a wide range of control. Drain Pan The condensate pan is constructed of corrosion resistant material and insulated to prevent sweating.
Mechanical Specifications Deluxe Controls (option) The deluxe control package provides a 75 VA transformer with circuit breaker.The controller includes a lockout relay, anti-short cycle compressor protection, random start delay, brown-out protection, low pressure time delay, compressor delay on start and an open relay for night setback or pump request. Optional wiring from the factory for condensate overflow, hot gas reheat, electric heat, and compressor enable is also provided.
Mechanical Specifications Motorized Water Valve (option) When extreme fluid temperature conditions do not exist with an open loop system, a motorized water valve may be applied to each water-source heat pump.The motorized valve shall stop flow to the unit, causing pressures to rise.This rise in pressure will halt pump operation to provide greater energy savings of the entire system.
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com. Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.