User's Manual

65RT-PRC010-EN
Performance
Data
(105,115,130 Tons)
Table PD-42 Supply Fan Performance WITH VARIABLE FREQUENCY DRIVE or WITHOUT INLET GUIDE VANES 105, 115, 130 Tons (Cont.)
Cfm Total Static Pressure
Std. 6.250 6.500 6.750 7.000 7.250 7.500 7.750
Air RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
31000 1391 44.45 1413 46.37 1437 48.39 1458 50.25 1479 52.20 1501 54.25 1524 56.40
32000 1400 45.71 1422 47.64 1444 49.67 1465 51.55 1486 53.51 1508 55.58 1530 57.74
33000 1408 46.93 1430 48.87 1452 50.91 1473 52.93 1496 55.05 1517 57.14 1537 59.16
34000 1418 48.38 1440 50.32 1462 52.37 1481 54.27 1503 56.40 1524 58.50 1544 60.53
35000 1430 49.93 1449 51.76 1471 53.81 1490 55.72 1512 57.86 1532 59.96 1552 62.01
36000 1441 51.47 1461 53.44 1481 55.39 1502 57.43 1521 59.43 1542 61.55 1562 63.77
37000 1452 53.10 1473 55.10 1492 57.07 1513 59.13 1532 61.15 1552 63.26 1571 65.33
38000 1464 54.72 1484 56.74 1505 58.86 1523 60.81 1542 62.85 1562 64.98 1582 67.21
39000 1474 56.33 1494 58.37 1515 60.51 1535 62.61 1555 64.83 1573 66.83 1592 68.92
40000 1487 58.15 1507 60.24 1528 62.42 1546 64.40 1566 66.63 1584 68.66 1603 70.93
41000 1500 59.94 1519 62.08 1538 64.16 1558 66.32 1576 68.43 1595 70.62 1615 72.92
42000 1512 61.69 1531 63.88 1551 66.15 1569 68.21 1588 70.35 1607 72.58 1626 74.89
43000 1527 63.79 1545 65.91 1563 67.95 1582 70.21 1600 72.40 1619 74.67 1637 76.85
44000 1542 65.85 1559 67.89 1576 70.00 1594 72.18 1612 74.41 1631 76.72 1650 79.12
45000 1558 68.03 1575 70.14 1592 72.31 1610 74.56 1625 76.54 1643 78.91
46000 1573 70.18 1590 72.35 1607 74.59 1623 76.74 1640 78.95
Notes:
1. Shaded areas indicate non-standard BHP or RPM selections. Contact your local Trane representive for more information.
2. Supply fan performance table includes internal resistance of rooftop. For total static pressure determination, system external static must be added to appropriate
component static pressure drops, (evaporator coil, filters, optional economizer, optional heating system, optional roof curb).
3. Maximum static pressure leaving the rooftop is 4.0’’ H20 positive. The static pressure drops from the supply fan to the space cannot exceed 4.0’’ H20.
4. Maximum Cfm as follows: 105 Ton Std. — 44,000 Cfm, 105 Hi-Cap., 115, 130 Ton — 46,000 Cfm
5. Minimum motor horsepower is 30 hp.
6. See RT-EB-104 for further details.
Figure PD-11 Supply Fan Performance WITH VARIABLE FREQUENCY DRIVE or WITHOUT INLET GUIDE VANES 105, 115, 130 Tons
Note:
1. Important: Maximum static pressure leaving the rooftop is 4.0 H2O positive. The static pressure drops from the supply fan to the space cannot exceed 4.0 H2O.
0 10000 20000 30000 40000 50000 60000
0
1
2
3
4
5
6
7
8
9
4
0
%
WO
C
F
M
5
0
%
W
O
CF
M
6
0
%
W
O
C
F
M
9
0
%
W
O
C
F
M
80%
W
O
C
F
M
7
0
%
W
O
C
F
M
100
H
P
75
HP
60 HP
50
H
P
40
H
P
30
H
P
25 HP
20 HP
1
6
0
0
R
P
M
1
5
0
0
R
P
M
1
4
0
0
R
P
M
1
3
0
0
R
P
M
1
2
0
0
R
P
M
1
1
0
0
R
P
M
1
0
0
0
R
P
M
9
0
0
RP
M
CFM
Static Presure, Inches w.c.