Product Catalog Split System Condensing Units —RAUJ Remote Chiller Evaporators 20 - 120 Tons — 50/60 Hz — R-410A March 2012 SS-PRC030-EN
Introduction Trane 20 to 120-ton air-cooled condensing units are the leaders in the split system marketplace. Designed for efficiency, reliability and flexibility, the Trane units have the most advanced design in the industry. All 20 to 120-ton units feature the Trane 3-D™ Scroll compressor, solid-state controls and Trane’s exclusive Packed Stock Plus availability 20 to 60 tons for quick shipment.
Table of Contents Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Application Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Features and Benefits Trane 3-D Scroll Compressor Simple Design with 70% Fewer Parts Fewer parts than an equal capacity reciprocating compressor means significant reliability and efficiency benefits. The single orbiting scroll eliminates the need for pistons, connecting rods, wrist pins and valves. Fewer parts lead to increased reliability. Fewer moving parts, less rotating mass and less internal friction means greater efficiency than reciprocating compressors.
Features and Benefits Coil Frost Protection Trane offers Frostat™ with the VAV system control option on the 20 to 120-ton units. FROSTAT is the industry’s most reliable method of coil frost protection and assures that your system will provide energy efficient comfort at part load conditions. Remote Chiller Evaporator Option with Field Installation Kit Allows chilled water to be generated remotely from the condensing section.
Application Considerations Certain application constraints should be considered when sizing, selecting and installing Trane aircooled condensing units. Unit reliability is dependent upon these considerations. Where your application varies from the guidelines presented, it should be reviewed with the local Trane sales engineer. Unit Sizing Unit capacities are listed in the performance data section. Intentionally oversizing a unit to assure adequate capacity is not recommended.
Application Considerations Condenser coils and fan discharge must be kept free of snow and other obstructions to permit adequate air flow for satisfactory unit operation. Effect of Altitude on Capacity Condensing unit capacities given in the performance data tables are at sea level. At elevations substantially above sea level, the decreased air density will decrease condenser capacity and, therefore, unit capacity and efficiency. The adjustment factors in Table 4, p.
Application Considerations Water Temperature Limits RAUJ with remote EVP chiller performance data is based on a water temperature drop of 10°F. Full load chilled water temperature drops from 8 to 14°F may be used as long as minimum and maximum water temperature and minimum and maximum flow rates are not violated. Leaving water temperatures below 42°F require freeze protection down to 15°F. The maximum water temperature that can be circulated through the chiller when the unit is not operating is 125°F.
Selection Procedure Net capacity curves for the RAUJ condensing units are given in the performance data section. When matched with a coil curve, the resultant point of intersection will be the system design balance point. The design operating suction temperature and capacity can then be read directly from the graph. Note: It is usually necessary to account for suction and liquid line losses in the performance . The actual losses are determined by the interconnecting piping.
Model Number Descriptions 20 to 60-Ton Units1 Digit 17 Digit 13 — Number of Circuits G = Return Air Sensor 2 = Dual (All 80-120 Ton) Digit 1 — Unit Type Digit 18 Digit 14 R = Condensing Unit J = Corrosion Protected Condenser Coil B = Hot Gas Bypass Valve Digit 2 — Condenser Digit 19 Digit 15 A = Air Cooled C = Remote Chiller Evaporator & Install Kit T = Flow Switch (EVP Control Only) D = Suction Service Valves Digit 3 — Airflow U = Upflow Digit 4 — Development Sequence Digit 20 1 = Spring
General Data Table 1. General data - 20-120 ton condensing units Model Number RAUJ-C20 RAUJ-C25 RAUJ-C30 RAUJ-C40 RAUJ-C50 RAUJ-C60 RAUJ-C80 RAUJ-D10 RAUJ-D12 Compressor Data Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll 10T + 10T 10T +13.5T 15T + 15T 10T + 10T 11.5T + 13.5T 15T + 15T 15T + 15T + 15T + 15T + 20T + 20T + 15T 20T 20T 10T + 10T 11.5T + 13.
General Data Table 2. General data - 20 - 120 ton remote chillers RAUJC20 Model Number RAUJC25 RAUJC30 RAUJC40 RAUJC50 RAUJC60 RAUJC80 RAUJD10 RAUJD12 Shipping weight, lbs 44 84 113 90 135 157 208 292 320 Operating weight, lbs 56 104 142 131 206 244 330 473 520 No. of refrigerant circuits 1 1 1 2 2 2 2 2 2 Water volume, Gal 1.4 2.2 3.3 4.6 7.9 9.7 13.6 20.1 22.2 Chiller refrig charge @ AHRI condition, lbs 0.9 1.5 2.2 3.1 5.3 6.4 9.0 13.3 14.
Performance Data 60 Hz Data Figure 2. 20 Ton condensing unit performance — RAUJ-C20 (60 HZ) 325 300 Net Capacity MBH 275 250 225 200 175 150 30 32 34 36 38 40 42 44 46 48 50 46 48 50 Saturated Suction Temperature (F) Figure 3.
Performance Data Figure 4. 30 Ton condensing unit performance — RAUJ-C30 (60 HZ) 475 450 425 Net Capacity MBH 400 375 350 325 300 275 250 225 30 32 34 36 38 40 42 44 46 48 50 46 48 50 Saturated Suction Temperature (F) Figure 5.
Performance Data Figure 6. 50 Ton condensing unit performance — RAUJ-C50 (60 HZ) 850 800 750 Net Capacity MBH 700 650 600 550 500 450 400 30 32 34 36 38 40 42 44 46 48 50 46 48 50 Saturated Suction Temperature (F) Figure 7.
Performance Data Figure 8. 80 Ton condensing unit performance — RAUJ-C80 (60 HZ) 1300 1250 1200 1150 1100 Net Capacity MBH 1050 1000 950 900 850 800 750 700 650 30 32 34 36 38 40 42 44 46 48 50 46 48 50 Saturated Suction Temperature (F) Figure 9.
Performance Data Figure 10. 120 Ton condensing unit performance — RAUJ-D12 (60 HZ) 2000 1900 1800 Net Capacity MBH 1700 1600 1500 1400 1300 1200 1100 1000 30 32 34 36 38 40 42 44 46 48 50 46 48 50 Saturated Suction Temperature (F) 50 Hz Data Figure 11.
Performance Data Figure 12. 25 Ton condensing unit performance — RAUJ-C25 (50 HZ) 325 300 Net Capacity MBH 275 250 225 200 175 150 30 32 34 36 38 40 42 44 46 48 50 46 48 50 Saturated Suction Temperature (F) Figure 13.
Performance Data Figure 14. 40 Ton condensing unit performance — RAUJ-C40 (50 HZ) 525 500 475 450 Net Capacity MBH 425 400 375 350 325 300 275 250 30 32 34 36 38 40 42 44 46 48 50 46 48 50 Saturated Suction Temperature (F) Figure 15.
Performance Data Figure 16. 60 Ton condensing unit performance — RAUJ-C60 (50 HZ) 775 725 675 Net Capacity MBH 625 575 525 475 425 375 30 32 34 36 38 40 42 44 46 48 50 46 48 50 Saturated Suction Temperature (F) Figure 17.
Performance Data Figure 18. 100 Ton condensing unit performance — RAUJ-D10 (50 HZ) 1350 1250 1150 Net Capacity MBH 1050 950 850 750 650 30 32 34 36 38 40 42 44 46 48 50 46 48 50 Saturated Suction Temperature (F) Figure 19.
Performance Data Table 5. System performance data — 20-120 Ton RAUJ with remote EVP chiller Entering Condenser Air Temperature (F) 85 Model RAUJ C20 RAUJ C25 RAUJ C30 RAUJ C40 RAUJ C50 RAUJ C60 RAUJ C80 22 95 105 115 LWFT(F) Capacity Tons Compr kW Capacity Tons Compr kW Capacity Tons Compr kW Capacity Tons Compr kW 40 18.8 17.5 17.7 19.4 16.6 21.4 15.4 23.7 42 19.4 17.8 18.3 19.6 17.2 21.7 16.0 23.9 44 20.1 18.0 19.0 19.8 17.8 21.9 16.6 24.1 46 20.8 18.
Performance Data Table 5. System performance data — 20-120 Ton RAUJ with remote EVP chiller (continued) Entering Condenser Air Temperature (F) 85 Model RAUJ D10 RAUJ D12 95 105 115 LWFT(F) Capacity Tons Compr kW Capacity Tons Compr kW Capacity Tons Compr kW Capacity Tons Compr kW 40 89.9 102.6 89.8 102.8 89.6 103.2 89.4 103.5 42 93.1 103.7 93.0 103.9 92.8 104.2 92.6 104.6 44 96.3 104.8 96.2 105.0 96.0 105.4 95.8 105.8 46 99.6 105.9 99.5 106.1 99.3 106.
Performance Data Figure 20. Remote EVP glycol freeze protection Solution Freeze Point Temperature, F 30 20 Ethylene 10 Propylene 0 10 15 20 25 30 35 40 45 50 -10 -20 -30 -40 % Glycol by Weight Figure 21. Remote EVP ethylene glycol GPM, capacity, and compressor power adjustment 1.20 GPM 1.18 Compressor power Capacity 1.16 1.14 Multiplier 1.12 1.10 1.08 1.06 1.04 1.02 1.00 0.98 0.96 10 15 20 25 30 35 40 45 50 % Ethylene Glycol by Weight Figure 22.
Controls Standard Options 20 to 120-Ton Condensing Units System Control Options Select one of the following control options to meet your application requirements. • No System Control provides the compressors wired to a terminal strip inside the control panel. The temperature controller must be field provided and installed. The 20, 25 and 30-ton have two capacity steps. The 40, 50 and 60-ton sizes have four steps available. The 80, 100, and 120-ton sizes have six steps available.
Electrical Data Table 7. Condensing units — 60 Hz Unit Characteristics Nominal Tons 20 25 30 40 50 60 80 100 120 Voltage/Start Characteristics Allowable Voltage Utilization Range RAUJ-C20E 200/60/3/XL 180-220 102 125 125 RAUJ-C20F 230/60/3/XL 207-253 89 110 100 2 RAUJ-C204 460/60/3/XL 414-506 46 60 60 2 Model Number Max.
Electrical Data Table 8. Nominal Tons 20 25 30 40 50 60 Nominal Tons 80 100 120 Compressor motor and condenser fan data — 60 Hz Compressor 1A(a) Model RAUJ-C20 RAUJ-C25 RAUJ-C30 RAUJ-C40 RAUJ-C50 RAUJ-C60 Model RAUJ-C80 RAUJ-D10 RAUJ-D12 Compressor 1B Compressor 2A Compressor 2B Condenser Fans Voltage RLA LRA RLA LRA RLA LRA RLA LRA Qty. FLA 200 XL 41.4 267.0 41.4 267.0 - - - - 2 4.1 230 XL 35.5 267.0 35.5 267.0 - - - - 2 4.1 460 XL 18.6 142.
Electrical Data Table 9. Condensing units — 50 Hz Unit Characteristics Allowable Minimum Max.
Dimensional Data Figure 23. 20-ton Air-cooled condensing unit NOTES: 1. SEE CONNECTION DRAWING FOR CONNECTION LOCATION AND SIZES. FAN GRILLE 2. LOW AMBIENT DAMPER ONLY COMES WITH SELECTED UNIT . 3. FRONT OF UNIT CLEARANCE 72" . BACK OF UNIT CLEARANCE 72" . LEFT AND RIGHT SIDE OF UNIT CLEARANCE 42". 3/4" X 4 MTG HOLES 4 3 1/2" X 4 KO (115V) 1/2" X 2 KO (115V) 5 3/8" 3 3/8" 2 5/8" 5 5/16" CONTROL PANEL 72 1/2" 4 1/2" FRONT (SEE NOTE 3 FOR ALL MIN.
Dimensional Data Figure 24. 20-ton Air-cooled condensing unit (connections) CONTROL PANEL SIDE NOTES: 1. VERIFY WEIGHT, CONNECTION, AND ALL DIMENSION WITH INSTALLER DOCUMENTS BEFORE INSTALLATION 1 3/8" O.D. DISCHARGE LINE SCALE 1,000 7/8" O.D.
Dimensional Data Figure 25. 25- and 30-ton Air-cooled condensing unit NOTES: 1. SEE CONNECTION DRAWING FOR CONNECTION LOCATION AND SIZES. 2. LOW AMBIENT DAMPER ONLY COMES WITH SELECTED UNIT . 3. FRONT OF 20 AND 30 UNIT CLEARANCE 72" . BACK OF UNIT CLEARANCE 72”. LEFT AND RIGHT SIDE OF 20 AND 30 UNIT CLEARANCE 42”. FAN GRILLE 3/4" X 4 MTG HOLES 1/2" X 4 KO (115V) 4 3 1/2" X 2 KO (115V) 2 5/8" 5 5/16" 5 3/8" 3 3/8" CONTROL PANEL 4 1/2" 72 1/2" 3 3/8" 88 1/2" 1 3/4" KO LOW VOLTAGE (30V MAX.
Dimensional Data Figure 26. 25- and 30-ton Air-cooled condensing unit (connections) 1. VERIFY WEIGHT, CONNECTION, AND ALL DIMENSION WITH INSTALLER DOCUMENTS BEFORE INSTALLATION CONTROL PANEL SIDE 7/8" O.D. HOT GAS BYPASS (OPTIONAL) COMPRESSORS B A A CONTROL PANEL 7/8" O.D. LIQUID LINE SCA LE 1.000 1 5/8" O.D. SUCTION LINE 1 5/8" O.D.
Dimensional Data Figure 27. 40-ton Air-cooled condensing unit FAN GRILLE NOTES: 3/4" X 6 MTG HOLES 6 1. SEE CONNECTION DRAWING FOR CONNECTION LOCATION AND SIZES. 2. LOW AMBIENT DAMPER ONLY COMES WITH SELECTED UNIT . 3. FRONT AND BACK OF UNIT CLEARANCE 72" . LEFT AND RIGHT SIDE OF UNIT CLEARANCE 42". 5 1/2" X 4 KO (115V) 36 1/8" 1/2" X 2 KO (115V) 5 3/8" 3 3/8" 2 5/8" 5 5/16" 4 88 9/16" 3 36 1/8" FRONT (SEE NOTE 3 FOR ALL MIN.
Dimensional Data Figure 28. 40-ton Air-cooled condensing unit (connections) NOTES: 1. VERIFY WEIGHT, CONNECTION, AND ALL DIMENSION WITH INSTALLER DOCUMENTS BEFORE INSTALLATION 12" 7/8" O.D. HOT GAS BYPASS (OPTIONAL) 7/8" O.D. LIQUID LINE 7 11/16" 2 7/8" 7 1/4" 16 1/4" SERVICE VALVE (OPTIONAL) 1 5/8" O.D. SUCTION LINE COMPRESSORS 13 3/4" 10 1/4" CONTROL PANEL 4 3/4" VOLTAGE ACCESS CONTROL PANEL SIDE 7/8" O.D.
Dimensional Data Figure 29. 50-ton Air-cooled condensing unit NOTES: 1. SEE CONNECTION DRAWING FOR CONNECTION LOCATION AND SIZES. 2. LOW AMBIENT DAMPER ONLY COMES WITH SELECTED UNIT . 3. FRONT AND BACK OF UNIT CLEARANCE 72" . LEFT AND RIGHT SIDE OF UNIT CLEARANCE 42". FAN GRILLE 1/2" X 4 KO (115V) 6 3/4" X 6 MTG HOLES 5 1/2" X 2 KO (115V) 2 5/8" 5 5/16" 5 3/8" 3 3/8" CONTROL PANEL 48 7/8" 4 1/2" 3 3/8" 4 3 48 7/8" FRONT (SEE NOTE 3 FOR ALL MIN.
Dimensional Data Figure 30. 50-ton Air-cooled condensing unit (connections) NOTES: 1. VERIFY WEIGHT, CONNECTION, AND ALL DIMENSION WITH INSTALLER DOCUMENTS BEFORE INSTALLATION 7/8" O.D. LIQUID LINE 12" 7 11/16" 7/8" O.D, HOT GAS BYPASS (OPTIONAL) 10 13/16" 32 3/4" 41 3/4" SERVICE VALVE (OPTIONAL) 1 5/8" O.D. SUCTION LINE COMPRESSORS 38 3/4" 29 3/4" 10 13/16" VOLTAGE ACCESS CONTROL PANEL SIDE 7 11/16" 7/8" O.D.
Dimensional Data Figure 31. 60-ton Air-cooled condensing unit NOTES: 1. SEE CONNECTION DRAWING FOR CONNECTION LOCATION AND SIZES. FAN GRILLE 3/4" X 6 MTG HOLES 2. LOW AMBIENT DAMPER ONLY COMES WITH SELECTED UNIT . 3. FRONT AND BACK OF UNIT CLEARANCE 72" . LEFT AND RIGHT SIDE OF UNIT CLEARANCE 42". 1/2" X 4 KO (115V) 5 6 1/2" X 2 KO (115V) 5 3/8" 3 3/8" 2 5/8" 5 5/16" CONTROL PANEL 48 7/8" 4 1/2" 3 3/8" 4 3 1 3/4" KO LOW VOLTAGE (30V MAX.) 114" 29 1/4" 31 1/4" FRONT (SEE NOTE 3 FOR ALL MIN.
Dimensional Data Figure 32. 60-ton Air-cooled condensing unit (connections) NOTES: 1. VERIFY WEIGHT, CONNECTION, AND ALL DIMENSION WITH INSTALLER DOCUMENTS BEFORE INSTALLATION 7/8" O.D. LIQUID LINE 12" 7 11/16" 7/8" O.D, HOT GAS BYPASS (OPTIONAL) 10 13/16" 32 3/4" 41 3/4" SERVICE VALVE (OPTIONAL) 1 5/8" O.D. SUCTION LINE COMPRESSORS 38 3/4" 29 3/4" 10 13/16" VOLTAGE ACCESS CONTROL PANEL SIDE 7 11/16" 7/8" O.D.
Dimensional Data Figure 33. 80-ton Air-cooled condensing unit NOTES: FAN GRILLE 8 1. SEE CONNECTION DRAWING FOR CONNECTION LOCATION AND SIZES. 3/4" X 8 MTG HOLES 2. LOW AMBIENT DAMPER ONLY COMES WITH SELECTED UNIT . 3. FRONT AND BACK OF UNIT CLEARANCE 96" . LEFT AND RIGHT SIDE OF UNIT CLEARANCE 48". 7 1/2" X 4 KO (115V) 72 1/8" 1/2" X 2 KO (115V) 5 3/8" 3 3/8" 2 5/8" 5 5/16" 6 5 4 3 176 11/16" 16" CONTROL PANEL 4 1/2" FRONT (SEE NOTE 3 FOR ALL MIN.
Dimensional Data Figure 34. 80-ton Air-cooled condensing unit (connections) 2 5/8" O.D. SUCTION LINE 1 1/8" O.D. LIQUID LINE DETAIL A SERVICE VALUE (OPTIONAL SEE DETAIL A) 46 3/16" NOTES: 1. VERIFY WEIGHT, CONNECTION, AND ALL DIMENSION WITH INSTALLER DOCUMENTS BEFORE INSTALLATION 42 9/16" 14 13/16" 25 1/8" CONTROL ANEL SIDE 2 5/8" O.D .SUCTION LINE SERVICE VALUE (OPTIONAL SEE DETAIL A) COMPRESSOR (6) 1 3/8" HOT GAS BYPASS (OPTIONAL) 3/8" O.D.
Dimensional Data Figure 35. 100- and 120-ton Air-cooled condensing unit NOTES: 1. SEE CONNECTION DRAWING FOR CONNECTION LOCATION AND SIZES. FAN GRILLE 2. LOW AMBIENT DAMPER ONLY COMES WITH SELECTED UNIT . 3. FRONT AND BACK OF UNIT CLEARANCE 96" . LEFT AND RIGHT SIDE OF UNIT CLEARANCE 48". 3/4" X 8 MTG HOLES 1/2" X 4 KO (115V) 1/2" X 2 KO (115V) 5 3/8" 3 3/8" 2 5/8" 97 5/8" 5 5/16" CONTROL PANEL 4 1/2" 3 3/8" 4" CONDUIT MAIN POWER 29 1/4" 31 1/4" 1 3/4" KO LOW VOLTAGE (30V MAX.
Dimensional Data Figure 36. 100- and 120-ton Air-cooled condensing unit (connections) SERVICE VALUE (OPTIONAL SEE DETAIL A) 45 7/8" 67 7/16" 2 5/8" O.D. SUCTION LINE 39 5/8" 2 5/8" O.D. SUCTION LINE 13 1/16" 18 1/16" 25 1/8" 1 1/8" O.D. LIQUID LINE SERVICE VALUE (OPTIONAL SEE DETAIL A) CONTROL PANEL SIDE COMPRESSOR (6) 1 3/8"HOT GAS BYPASS (OPTIONAL) 1 3/8"HOT GAS BYPASS (OPTIONAL) PLAN VIEW OF UNIT CONNECTION DRAWING 2 5/8" O.D. SUCTION LINE 74" 46 1/4" 25 1/8" 1 1/8" O.D.
SS-PRC030-EN REQUIRES FIELD PROVIDED 1/2”X14NPTE STAINLESS STEEL OR PVC PLUG REFRIGERANT CONNECTIONS ARE STAINLESS STEEL AND REQUIRE SPECIAL BRAZE MATERIALS. SEE IOM BRAZE PROCEDURES.
REQUIRES FIELD PROVIDED 1/2”X14NPTE STAINLESS STEEL OR PVC PLUG REFRIGERANT CONNECTIONS ARE STAINLESS STEEL AND REQUIRE SPECIAL BRAZE MATERIALS. SEE IOM BRAZE PROCEDURE.
SS-PRC030-EN REQUIRES FIELD PROVIDED 1/2”X14NPTE STAINLESS STEEL OR PVC PLUG REFRIGERANT CONNECTIONS ARE STAINLESS STEEL AND REQUIRE SPECIAL BRAZE MATERIALS. SEE IOM BRAZE PROCEDURE.
REQUIRES FIELD PROVIDED 1/2”X14NPTE STAINLESS STEEL OR PVC PLUG REFRIGERANT CONNECTIONS ARE STAINLESS STEEL AND REQUIRE SPECIAL BRAZE MATERIALS. SEE IOM BRAZE PROCEDURES.
SS-PRC030-EN REQUIRES FIELD PROVIDED 1/2”X14NPTE STAINLESS STEEL OR PVC PLUG REFRIGERANT CONNECTIONS ARE STAINLESS STEEL AND REQUIRE SPECIAL BRAZE MATERIALS. SEE IOM BRAZE PROCEDURES.
Weights Table 11. 20- to 120- Ton air-cooled condensing units Weight on isolator mounting location (lbs.) Tons Model Operating Weight Loc. 1 Loc. 2 Loc 3. Loc 4. Loc. 5 Loc. 6 Loc. 7 Loc. 8 20 RAUJC20 1573 475.5 383.3 403.2 311.0 --- --- --- --- 25 RAUJC25 1623 491.2 399.3 412.2 320.3 --- --- --- --- 30 RAUJC30 1623 491.2 399.3 412.2 320.3 --- --- --- --- 40 RAUJC40 2532 452.3 415.7 440.3 403.7 428.3 391.8 --- --- 50 RAUJC50 2868 365.5 331.0 427.
Weights Figure 42. Air-cooled condensing units Y X 2 Y 4 X 2 Control Panel 6 3 5 Control Panel 1 3 1 20-30 Ton Y 4 40-60 Ton X 2 4 6 8 3 5 7 Control Panel 1 80-120 Ton Table 13.
Mechanical Specifications 20 to 120-ton Condensing Units General All air-cooled condensing units have scroll compressors and are factory assembled and wired. Each unit is shipped from the factory with a nitrogen holding charge. Units are constructed of 14-gauge welded galvanized steel frame with 14 and 16-gauge galvanized steel panels and access doors. Unit surface is phosphatized and finished with an air-dry paint.
Mechanical Specifications Remote Evaporator Chillers The remote chiller control option includes an interface panel in the main unit control box and a remote mounted control box that is customer installed. The remote mounted box contains the Honeywell W7100G controller. The chiller controller has an adjustable 0-10°F control band with integrating logic, built in fixed-off timers and field installed discharge water temperature sensors for control and chiller freeze protection.
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com. Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.