Installation, Operation, and Maintenance VariTrane™ Round Inlet/Round Outlet (VRRF) Models VRRF 04-16 SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and airconditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury.
Warnings, Cautions and Notices Warnings, Cautions and Notices. Note that warnings, cautions and notices appear at appropriate intervals throughout this manual. Warnings are provide to alert installing contractors to potential hazards that could result in death or personal injury. Cautions are designed to alert personnel to hazardous situations that could result in personal injury, while notices indicate a situation that could result in equipment or property-damage-only accidents.
Table of Contents Warnings, Cautions and Notices . . . . . . . . . . 2 Single Duct Hot Water . . . . . . . . . . . . . . . .23 Revision Summary . . . . . . . . . . . . . . . . . . . 2 Analog and DDC Fan Powered: Fan control . . . . . . . . . . . . . . . . . . . . . . . . .23 Trademarks . . . . . . . . . . . . . . . . . . . . . . . . . 2 Model Number Descriptions . . . . . . . . . . . . . . 4 General Information . . . . . . . . . . . . . . . . . . . . . Receiving and Handling . . . . . . . . . . . . . .
Model Number Descriptions V R R F 0 8 A 0 D D 0 4 5 W W H 1 D W 0 F W C 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Digits 1-4— Unit Type VRRF= VariTrane™ Round Inlet and Outlet (Retrofit) Digit 5, 6—Primary Air Valve 04 05 06 08 10 12 14 16 = = = = = = = = 4" inlet (225 cfm) 5" inlet (350 cfm) 6" inlet (500 cfm) 8" inlet (900 cfm) 10" inlet (1400 cfm) 12" inlet (2000 cfm) 14" inlet (3000 cfm 16" inlet (4000 cfm) Digits 7, 8—Design Seq
General Information This manual describes the installation of the Round In Round out (VRRF) VAV units with mounting and recommended wiring of the VRRF units. • For controls setup and operation parameters, reference the following literature: Upon receiving the equipment, please inspect each unit and components for external or internal damage. Refer to the bill of lading to insure all equipment and accessories have been received.
Installation Due to their weight and size, VRRF units should be suspended from the uppermost ceiling, independent of the false ceiling grid. Suspension devices are to be supplied by the installer. Units must be installed level in the vertical or horizontal position.To check if the unit is a vertical or horizontal unit, look at the model number of the unit as compared to the Service Model Number Description in this installation guide. Figure 1.
Installation Figure 2.
Installation Table 1. recommended that 6" of top and bottom clearance be provided. C, D, or E style units(a) Controls Air Valve Type Outlet Connection Type Pneumatic Normally Closed Single Duct Elec. Heat Retrofit not possible(b) Pneumatic Normally Closed Parallel Fan Elec. Heat Retrofit not possible(b) Pneumatic Normally Closed All Others 1 Pneumatic Normally Open Single Duct Elec. Heat 2 Pneumatic Normally Open Parallel Fan Elec.
Installation When installing the VRRF to a pre- existing unit, remove power from pre-existing unit and lock and tag out unit. Remove or pull back insulation and remove the amount of inlet ductwork necessary to install the RIRO damper. (See Figure 2, p. 7 for VRRF lengths.) 6. Remove air valve from existing VAV unit by breaking the seal around air inlet and the VAV unit. Once it is loose, remove air valve. (See Figure 5) Figure 5.
Installation removing the old tubing from the airflow switch and using the black tubing provided in the adaptor kit. Connect the airflow switch to the high pressure port of the VRRF unit.There is a tee located in the VRRF unit control box for this. Installation Option Original Ductwork 1. Make sure the existing VAV unit has its air valve set to the open position allowing airflow.With a DDC unit this can be done with Summit (BMTW-SVN01*-EN), Rover™ (EMTX-SVX01*-EN).
Installation New Facility VRRF Installation (Non-Retrofit) Table 3. Note: When installing VRRF, make sure the controller is level so the transducer can read airflow accurately. Important: Make sure inlet and outlet ductwork are adequately supported before installing VRRF. 1. Before hanging VRRF, ensure that the VRRF will have a minimum of 1.5 duct diameters of strait duct prior to the inlet of the VRRF. Insulation for RIRO A B C 12" 41.5 28 16.5 8 17 19.5 14" 47.5 32.75 18.25 9.
Installation Binary input occupancy or generic (dry contact) Binary outputs Air valve open Maximum output rating forTriac: 12VA Air valve close Maximum output rating forTriac: 12VA Heat stage 1: Maximum output rating forTriac: 12VA Heat stage 2: Maximum output rating forTriac: 12VA Heat stage 3 or Fan output: Maximum output rating forTriac: 12VA UC400 Table 4.
Installation Analog Inputs Binary Outputs • Binary Outputs Type Output Rating BO1 Fan 10A up to 277 Vac 10A at 30 Vac/VDC, 2A at 120 Vac, 8 A at 250 Vac BO2 Spare Relay 10A up to 277 Vac 10A at 30 Vac/VDC, 2A at 120 Vac, 8 A at 250 Vac BO3 Spare Relay 10A up to 277 Vac • Range: from 50°F to 90°F (10°C to 32.2°C), */** (thumbwheel) functionality supported 10A at 30 Vac/VDC, 2A at 120 Vac, 8 A at 250 Vac BO4 Fan ON/Off 24-27 Vac, 0.
Installation Table 5. UC400 specifications (continued) Environmental NEMA 1 rating (enclosure): Table 6. UC210 inputs and outputs (continued) • AO1: ECM • AO2: SCR Heat Installation: UL 840: Category 3 Pollution: UL 840: Degree 2 Agency Listing/Compliance • • • • • • • • UL916 PAZX, Open Energy Management Equipment UL94-5V, Flammability CE Marked FCC Part 15, Subpart B, Class B Limit AS/NZS CISPR 22:2006 VCCI V-3/2008.
Installation • Figure 44 and Figure 45 for the UCM 4.2 auxiliary sensor is not installed the UCM will retain the last control action in effect. • Figure 46 and Figure 47 for the VV550 Stand Alone VV550 • Figure 48 and Figure 49 for the UC400 • Figure 50 and Figure 51 for the UC210 When there is no communication to theVV550 control and the unit is in the stand alone mode the control action is determined by the auxiliary temperature sensor located onTB3-5 andTB3-6 terminals on the VV550 board.
Installation air temperature. In order for the auxiliary sensor to function as a supply air temperature sensor on VAV units with reheat and to properly determine the control action (heat, cool) it must be located upstream of the VAV unit. The auxiliary temperature is then compared to the zone temperature. If the supply air temperature is 10 degrees above the zone temperature, then the control action will be heat.
Installation Table 8. DIP switch settings (continued) Table 8.
Installation All binary outputs from control board are 24 VAC. Connection points for unit UCM controller are shown in Control Diagrams: • All wiring must comply with the National Electrical Code™ (NEC) and local codes. • Ensure that 24 Vac power supplies are consistent in regards to grounding. Avoid sharing 24 Vac between controllers. • Avoid over tightening cable ties and other forms of cable wraps.This can damage the wires inside the cable.
Installation Figure 10.
Installation Figure 11.
Installation Figure 12.
Installation Pneumatic Units: Single Duct Hot Water 1. Isolate pneumatic hot water valve and remove valve from system. 2. Install Proportional orTwo-Position hot water valve. Ensure that piping is correct to the new style of valve. 3. Field wire actuator 24VAC control voltage toVRRF DDC controller. See Control Diagrams: 2. Disconnect PE switch and optional duct pressure switch for fan control in fan control enclosure and replace PE switch with relay from kit. 3.
Installation 3. Field wire actuator 24VAC control voltage toVRRF DDC controller. See Control Diagrams: a. Figure 44 and Figure 45 for the UCM 4.2 b. Figure 46 and Figure 47 for the VV550 c. Figure 48 and Figure 49 for the UC400 d. Figure 50 and Figure 51 for the UC210 Analog and DDC Units: Single Duct Electric Heat 1. Remove Power and Lock andTag out unit if it hasn't been done already. WARNING Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing.
Installation Figure 13.
Installation Analog and DDC Fan-Powered: Fan-Powered Electric Heat 1. Remove Power and Lock andTag out unit if it hasn't been done already. WARNING Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury. 2.
Installation Figure 14.
Installation Figure 15.
Installation Figure 16.
Installation UCM Programming (UCM 4.2) The UCM 4.2 can be programed usingTracer Summit™, CCP computer software, andTrane’s service tool, Rover™. When using Summit or CCP software, refer to programming guides. When using Rover see, EMTXSVX01*-EN for overall use. When setting up VRRF UCM, see below for basic menu's using Rover. Figure 17. When using Rover, connect into UCM using proper cable. Initiate Rover software and search for unit using VRRF address. UCM 4.
Installation Figure 18. UCM 4.2 configuration: reheat setup To Set the Reheat Setup 1. Click the ’Configure’ button. 2. Click the ’Setup’ tab. 3. Click the ’HeatType’ drop-down button and select the desired type. 4. Click the ’Download’ button.
Installation Figure 19. UCM 4.2 configuration: fan-powered setup To Set the Fan-Powered Setup 1. Click the ’Configure’ button. 2. Click the ’Setup’ tab. 3. Click the ’FanType’ drop-down button and select the desired type. 4. Click the ’Download’ button.
Installation Figure 20. UCM 4.2 configuration: setpoints To Set the Set Points 1. Click the ’Configure’ button. 2. Click the ’Setpoints’ tab. 3. Enter the desired settings in the ’Heating Setpoints’ and ’Flow’ portions of the screen. 4. Click the ’Download’ button.
Installation UCM VV550 SVX01*-EN for overall use. When setting up RIRO UCM, see next page for basic menu's using Rover. The UCMVV550 can be programed usingTracer Summit™ computer software, andTrane’s service tool, Rover™. When using Summit software, use Summits programming guide. When using Rover see EMTX- When using Rover, connect into UCM using proper cable. Initiate Rover software and search for unit using RIRO Neuron ID. (Sample Neuron ID Number: 01-00-3A-52-3B00). Figure 21.
Installation Figure 22. VV550 configuration: reheat setup To Set the Reheat Setup 1. Click the ’Configure’ button. 2. Click the ’Outputs’ tab. 3. Click the ’Start’ button. 4. Choose the desired settings in the VV550 Output Wizard. 5. Once the wizard is complete, click the ’Download’ button.
Installation Figure 23. VV550 configuration: fan-powered setup Figure 24. VV550 configuration: temp setpoints To Set the Fan-Powered Setup 1. Click the ’Configure’ button. 3. Choose the desired settings from the ’Fan Configuration’ portion of the screen. 2. Click the ’Unit’ tab. 4. Click the ’Download’ button.
Installation To Set theTemp Setpoints 1. Click the ’Configure’ button. 3. Choose the desired settings from the ’Setpoints’ portion of the screen. 2. Click the ’Unit’ tab. 4. Click the ’Download’ button. Figure 25. VV550 configuration: flow setpoints To Set the Flow Setpoints 1. Click the ’Configure’ button. 2. Click the ’Setup’ tab. 3. Choose the desired settings from the ’Flow Setpoints Setup’ portion of the screen. 4. Click the ’Download’ button.
Installation UC400 and UC210 Figure 26. UC400 and UC210 configuration: navigation to configuration Navigate to the Configurations Page 2. Select Equipment. 1. Select Utilities in the tool bar. 3. Select Configuration. Figure 27. UC400 and UC210 configuration: equipment selection 1. Click the ‘Equipment’ drop down box in the ‘Equipment Selection’ group and select the desired setting.
Installation Figure 28. UC400 and UC210 configuration: application selection Select VAV control. 1. Click the ‘Profile’ drop down box in the ‘Application Selection’ group and select the desired setting. Figure 29. UC400 and UC210 configuration: inlet size selection To set the inlet size 1.
Installation Figure 30. UC400 and UC210 configuration: fan control settings To set the Fan-Powered Setup Figure 31. 1. Click the ‘Fan Control’ drop down box in the ‘Equipment Selection’ group and select the desired setting UC400 and UC210 configuration: reheat type selection To select ReheatType VAV-SVN09B-EN 1.
Installation Figure 32. UC400 and UC210 configuration: reheat setup 1 2 To set the Reheat Setup 2. Click the ‘Save’ button 1. Use the drop down menus in the ‘Reheat Settings’ group to choose the desired reheat settings Figure 33. UC400 and UC210 configuration: navigate to setpoints To setpoints 3. Select Setpoints 1. Select Utilities in the tool bar 2.
Installation Figure 34. UC400 and UC210 configuration: navigate to setpoints using tabs 1 To setpoints from configuration 1. Click the ‘Setpoints’ tab on the toolbar Figure 35. UC400 and UC210 configuration: temperature setpoints To Set theTemp Setpoints 2. Click the ‘Save’ button 1.
Installation Figure 36. UC400 and UC210 configuration: setup parameters To setup parameters 1. Select Utilities in the tool bar 2. Select Equipment 3. Select Setup Parameters Figure 37. UC400 and UC210 configuration: navigate to setpoints using tabs 1 To setup parameters from setpoints or configuration 1.
Installation Figure 38. UC400 and UC210 configuration: setup parameters Figure 39. UC400 and UC210 configuration: flow setpoints To Set the Flow Setpoints 3. Click the ‘Save’ button 1. Expand the ‘Flow Setpoints Setup’ group 2.
Installation Figure 40. UC400 and UC210 configuration: set measure value for airflow To Set the Measured Value for Airflow 1. Expand the ‘VAV Setup’ group 4. Open up VAV damper to Max Flow and measure the airflow across the magnahelic. 2. Choose the desired settings from the ‘VAV Setup’ group 5. Take the reading and compare it to chart on side of VRRF unit to get CFM value. 3. Click the ‘Save’ button 6.
Installation Figure 42. UCM 4.2 configuration: flow setup To Set the Measured Value for AirFlow 1. Click the ’Configure’ button. 2. Click the ’Setup’ tab. 3. Choose the measured value and adjust as desired. 4. Click the ’Download’ button.
Installation Figure 43. VV550 configuration: flow setup To Set the Measured Value for AirFlow 1. Click the ’Configure’ button. 2. Click the ’Setup’ tab. 3. Choose the flow offset and adjust as desired. 4. Click the ’Download’ button. UC400 Flow Setup. See VAV-SVX07*-EN for UC400 flow setup information. UC210 Flow Setup. See BAS-SVX62*-EN for UC210 flow setup information.
Wiring Figure 44. UCM 4.
Wiring Figure 45. UCM 4.
Wiring Figure 46.
Wiring Figure 47.
Wiring Figure 48.
Wiring Figure 49.
Wiring Figure 50.
Wiring Figure 51.
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com. Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.