Fan User Manual

37
RT-PRC005-EN
Performance
Data
(4 Ton)
High Efficiency
Table PD-40 Belt Drive Evaporator Fan Performance 4 Ton THC048A3,A4,AW Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1280 626 0.23 686 0.27 744 0.32 796 0.38 843 0.43 885 0.49 927 0.54 967 0.60 1005 0.66
1440 609 0.24 674 0.30 730 0.34 783 0.39 834 0.45 882 0.52 924 0.58 964 0.64 1002 0.70 1038 0.76
1600 661 0.32 724 0.38 776 0.44 825 0.49 872 0.54 919 0.61 962 0.68 1002 0.75 1039 0.82 1076 0.89
1760 716 0.42 775 0.48 825 0.54 870 0.60 915 0.66 958 0.72 999 0.79 1040 0.87 1078 0.95 1113 1.03
1920 771 0.53 825 0.59 875 0.66 918 0.73 959 0.79 1000 0.86 1039 0.92 1078 1.00 1116 1.09 1151 1.17
For Standard Evaporator Fan Speed (RPM), reference Table PD-50.
NOTES:NOTES:
NOTES:NOTES:
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-54 to determine additional static pressure drop due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK61 required. Field Supplied Belt may be necessary.
Trane’s factory supplied motors, in commercial
equipment, are definite purpose motors,
specifically designed and tested to operate
reliably and continuously at all cataloged
conditions. Using the full horsepower range of our
fan motors as shown in our tabular data will not
result in nuisance tripping or premature motor
failure. Our product’s warranty will not be
affected.
Table PD-40 Continued
External Static Pressure (Inches of Water)
1. 10 1. 20 1. 30 1. 40 1. 50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive
1280 1041 0.72 1076 0.78 1110 0.84 1143 0.91 1176 0.98
1440 1074 0.83 1108 0.89 1141 0.96 1174 1.03 1205 1.10
1600 1109 0.95 1142 1.02 1175 1.09 1207 1.17 1236 1.24
1760 1147 1.10 1179 1.17 1211 1.25 1241 1.32
1920 1186 1.26 1218 1.34 1249 1.42
Table PD-41 Belt Drive Evaporator Fan Performance 4 Ton THC048A3,A4,AW Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
1280 617 0.21 696 0.27 767 0.34 826 0.40 879 0.46 930 0.52 976 0.59 1020 0.66 1060 0.73 1098 0.80
1440 674 0.29 745 0.35 815 0.42 874 0.49 925 0.56 974 0.63 1020 0.70 1064 0.77 1104 0.85 1142 0.92
1600 733 0.38 799 0.45 862 0.53 922 0.60 975 0.68 1020 0.75 1065 0.83 1107 0.91 1147 0.99 1186 1.07
1760 793 0.49 854 0.56 911 0.65 969 0.73 1023 0.82 1069 0.90 1112 0.98 1152 1.07 1191 1.15 1230 1.24
1920 853 0.62 911 0.70 964 0.79 1018 0.88 1069 0.97 1118 1.06 1161 1.15 1201 1.25 1239 1.34 1275 1.43
For Standard Evaporator Fan Speed (RPM), reference Table PD-50.
NOTES:NOTES:
NOTES:NOTES:
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-54 to determine additional static pressure drop due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK61 required. Field Supplied Belt may be necessary.
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt may be necessary.
Trane’s factory supplied motors, in commercial
equipment, are definite purpose motors,
specifically designed and tested to operate
reliably and continuously at all cataloged
conditions. Using the full horsepower range of our
fan motors as shown in our tabular data will not
result in nuisance tripping or premature motor
failure. Our product’s warranty will not be
affected.
1-HP Standard Motor & Field
Supplied High Static Drive (2)
Table PD-41 Continued
External Static Pressure (Inches of Water)
1. 10 1. 20 1. 30 1. 40 1. 50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor
1280 1132 0.88 1167 0.95 1199 1.03 1231 1.10 1260 1.17
1440 1179 1.01 1213 1.09 1245 1.17 1277 1.26 1307 1.34
1600 1223 1.15 1258 1.24 1291 1.33 1322 1.42
176012671.3313011.42—— —— ——
1920 —— —— —— —— ——
1-HP Standard Motor &
Field Supplied High Static Drive(2)