Fan User Manual

57
RT-PRC005-EN
Electrical
Data
Table ED-8 Unit Wiring With Electric Heat (Single Point Connection) 460 Volts High Efficiency
Standard Indoor Motor Oversize Indoor Motor
To Use Heater Heater Control Max Fuse Size Or Max Fuse Size Or
Tons With Model No. kW Rating
1
Stages MCA Max Circuit Breaker
2
MCA Max Circuit Breaker
2
460 Volts Three Phase
BAYHTRR406A 6.0 1 10.4 15 11.9 15
3 THC036A4 BAYHTRR412A 12.0 2 19.4 20 20.9 25
BAYHTRR418A 17.4 2 27.5 30 29.9 30
BAYHTRR406A 6.0 1 11.1 15 13.1 15
4 THC048A4 BAYHTRR412A 12.0 2 20.1 25 22.1 25
BAYHTRR418A 17.4 2 28.3 30 30.3 35
BAYHTRR406A 6.0 1 14.7 20 15.0 20
5 THC060A4 BAYHTRR412A 12.0 2 21.6 25 22.0 25
BAYHTRR418A 17.4 2 29.8 30 30.1 35
BAYHTRR423A 23.0 2 38.3 40 38.6 40
BAYHTRS409A 9.0 1 17.5 25 18.1 25
6 THC072A4 BAYHTRS418A 18.0 1 30.3 35 31.0 35
BAYHTRS427A 27.0 2 43.8 45 44.5 45
BAYHTRS436A 36.0 2 57.3 60 58.0 60
BAYHTRT409A 9.0 1 19.4 25 20.9 25
THC092A4 BAYHTRT418A 18.0 1 31.0 35 32.9 35
BAYHTRT427A 27.0 2 44.5 45 46.4 50
BAYHTRT436A 36.0 2 58.0 60 59.9 60
BAYHTRT409A 9.0 1 21.4 25 22.9 30
THC102A4 BAYHTRT418A 18.0 1 31.0 35 32.9 35
BAYHTRT427A 27.0 2 44.5 45 46.4 50
BAYHTRT436A 36.0 2 58.0 60 59.9 60
BAYHTRT418A 18.0 1 32.9 35 35.4 40
10 THC120A4 BAYHTRT427A 27.0 2 46.4 50 48.9 50
BAYHTRT436A 36.0 2 59.9 60 62.4 70
BAYHTRT454A 54.0 2 70.8 80 73.3 80
NOTES:
1. Heater kW ratings are at 208/240 for 208/230V unit
2. HACR type circuit breaker per NEC.
(High Efficiency)