Fan User Manual

59
RT-PRC005-EN
Electrical
Data
(High Efficiency)
460 Volts Three Phase
BAYHTRR406A 6.0 1 12.1 15
3 THC036A4 BAYHTRR412A 12.0 2 21.1 25
BAYHTRR418A 17.4 2 29.3 30
BAYHTRR406A 6.0 1 12.1 15
4 THC048A4 BAYHTRR412A 12.0 2 21.1 25
BAYHTRR418A 17.4 2 29.3 30
BAYHTRR406A 6.0 1 14.3 20
5 THC060A4 BAYHTRR412A 12.0 2 21.1 25
BAYHTRR418A 17.4 2 29.3 30
BAYHTRR423A 23.0 2 37.8 40
575 Volts Three Phase
BAYHTRRW06A 6.0 1 9.3 15
3 THC036AW BAYHTRRW12A 12.0 2 16,6 20
BAYHTRRW18A 17.4 2 23.1 25
BAYHTRRW06A 6.0 1 9.3 15
4 THC048AW BAYHTRRW12A 12.0 2 16.6 20
BAYHTRRW18A 17.4 2 23.1 25
BAYHTRRW06A 6.0 1 11.4 15
BAYHTRRW12A 12.0 2 16.6 20
5 THC060AW
BAYHTRRW18A 17.4 2 23.1 25
BAYHTRRW23A 23.0 2 29.8 30
NOTES:
1. Heater kW ratings are at 208/240 for 208/230V unit
2. HACR type circuit breaker per NEC.
Table ED-10 Unit Wiring With Electric Heat (Single Point Connection) Optional Belt Drive High
Efficiency
Belt Drive Indoor Motor
To Use Heater Heater Control Max Fuse Size Or
Tons With Model No. kW Rating
1
Stages MCA Max Circuit Breaker
2
208/230 Volts Single Phase
BAYHTRR105A N/A N/A N/A N/A
3 THC036A1 BAYHTRR110A N/A N/A N/A N/A
BAYHTRR114A N/A N/A N/A N/A
BAYHTRR105A N/A N/A N/A N/A
BAYHTRR110A N/A N/A N/A N/A
4 THC048A1
BAYHTRR114A 1N/A N/A N/A N/A
BAYHTRR118A N/A N/A N/A N/A
BAYHTRR105A N/A N/A N/A N/A
BAYHTRR110A N/A N/A N/A N/A
5 THC060A1
BAYHTRR114A N/A N/A N/A N/A
BAYHTRR118A N/A N/A N/A N/A
208/230 Volts Three Phase
BAYHTRR306A 4.5/6.0 1 21.9/24.3 25/25
3 THC036A3 BAYHTRR312A 9.0/12.0 2 37.5/42.4 40/45
BAYHTRR318A 13.1/17.4 2 51.6/58.6 60/60
BAYHTRR306A 4.5/6.0 1 22.6/24.3 35/35
4 THC048A3 BAYHTRR312A 9.0/12.0 2 37.5/42.4 40/45
BAYHTRR318A 13.1/17.4 2 51.6/58.6 60/60
BAYHTRR306A 4.5/6.0 1 28.8/28.8 45/45
BAYHTRR312A 9.0/12.0 2 37.5/42.4 45/45
5 THC060A3
BAYHTRR318A 13.1/17.4 2 51.6/58.6 60/60
BAYHTRR323A 17.3/23.0 2 66.3/75.4 70/80