Packaged Rooftop Air Conditioners Manual

27RT-PRC010-EN
Table GD-3 General Data 90-130 Tons Continued
90 Ton 105 Ton 115 Ton 130 Ton
Filters
Panel Filters
Number/Size (Inches) 25-24x24x2 25-24x24x2 25-24x24x2 25-24x24x2
Face Area (Ft
2
) 100.0 100.0 100.0 100.0
Bag Filters 3-12x24x19 3-12x24x19 3-12x24x19 3-12x24x19
Number/Size (Inches) 15-24x24x19 15-24x24x19 15-24x24x19 15-24x24x19
Cartridge Filters 3-12x24x12 3-12x24x12 3-12x24x12 3-12x24x12
15-24x24x12 15-24x24x12 15-24x24x12 15-24x24x12
Prefilters (For Bag & Cartridge) 3-20x24x2 3-20x24x2 3-20x24x2 3-20x24x2
15-24x24x2 15-24x24x2 15-24x24x2 15-24x24x2
Face Area (Ft
2
) 66.0 66.0 66.0 66.0
Standard Unit Min. Outside Air Temperature For Mechanical Cooling
Without Hot Gas Bypass 45 F 45 F 45 F 45 F
With Hot Gas Bypass 45 F 45 F 45 F 45 F
Notes:
1. For cfm values outside these ranges, refer to RT-EB-104.
2 Refer to Table PD-30 for availability of electric heat kw ranges by voltage.
3. 90-130 Ton models are dual circuit.
4. Max cfm for 105 Ton std is 44,000.
5 The firing rate of the unit can vary from 33% of the Heater Mbh up to the nameplate rating of the unit.
6. The firing rate of the unit can vary from pilot rate of 125,000 Btuh up to the nameplate rating of the unit.
Table GD-4 ARI Performance Data
1
ARI Performance Data
1
Capacity
Tons Model
3
(MBh) EER IPLV
2
SAHFC2040A**A**A***** 220 9.5 12.8
SXHFC2040A**A**A***** 220 9.5 12.8
20 SFHFC204LA**A**A***** 220 9.4 12.7
SEHFC204*A**A**A***** 220 9.4 12.7
SLHFC204LA**A**A***** 220 9.4 12.6
SSHFC204LA**A**A***** 220 9.4 12.7
Notes:
1. This information is rated and tested in accordance with ARI Standard 360-93
for large unitary equipment up to 25 tons. These Trane products can be
found in the current ARI Directory.
2. IPLV — Integrated Part Load Value
3. This information applies to units whose design sequence (Digit 10) is “A” or
later.
Table GD-5 ARI Correction Multipliers
Model Multipliers (%)
Option Description Digit Designator Capacity EER IPLV
2
High Heat — Gas 9 H,J,P 100 100 100
High Heat — Steam 9 H 100 99 98
High Heat — Hot Water 9 H 100 99 99
Wire Mesh Filter 13 B 100 101 101
95% Bag filter 13 D 99 95 91
95% Cartridge Filter 13 E 99 95 92
100% Economizer 16 D 100 99 98
High Capacity Coil 21 G 114 109 107
High Efficiency Motor 21 L 100 101 101
Inlet Guide Vanes 17 3 100 99 99
VFD (60 Hz) 17 6-9 99 98 98
Table GD-6 Economizer Outdoor Air Damper Leakage (Of Rated Airflow)
P Across Dampers (In. WC)
0.5 (In.) 1.0 (In.)
Standard “Low Leak” 1.5 % 2.5 %
Optional “Ultra Low Leak” 0.5 % 1.0 %
Note:
1. Above data based on tests completed in accordance with AMCA Standard 575 at AMCA
Laboratories.
General Data