Cfm Total Static Pressure
Std 4.250 4.500 4.750 5.000
Air RPM BHP RPM BHP RPM BHP RPM BHP
8000 1087 14.97 1114 16.01 1141 17.07 1166 18.13
9000 1102 16.10 1131 17.24 1158 18.39
10000 1114 17.13 1143 18.36
11000 1123 18.11 1153 19.40
12000 1129 19.08 1160 20.43
13000 1134 20.08 1165 21.48
14000 1137 21.08 1169 22.54
15000 1140 22.09
16000 1143 23.13
17000 1146 24.21
18000 1149 25.35
19000 1153 26.59
20000 1159 27.94
21000 1165 29.43
22000
22500
23000
24000
Table PD-37 — Supply Fan Performance WITH INLET VANES — 40, 50 and 55 Ton
Cfm Total Static Pressure
Std .250 .500 .750 1.000 1.250 1.500 1.750 2.000
Air RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
8000 318 .79 406 1.35 485 1.98 555 2.70 618 3.49 675 4.31 726 5.17 773 6.06
9000 339 1.01 416 1.56 491 2.24 558 2.97 621 3.79 678 4.67 730 5.58 778 6.52
10000 364 1.28 428 1.81 499 2.53 564 3.30 624 4.13 680 5.04 733 6.00 781 7.00
11000 391 1.63 444 2.13 509 2.85 571 3.68 629 4.53 684 5.45 735 6.44 784 7.48
12000 419 2.04 463 2.51 521 3.22 580 4.08 636 4.99 689 5.92 739 6.93 787 8.00
13000 448 2.53 486 2.97 536 3.66 591 4.52 645 5.49 696 6.47 744 7.49 791 8.57
14000 478 3.09 511 3.53 553 4.19 604 5.03 655 6.02 704 7.07 751 8.12 796 9.22
15000 507 3.74 537 4.18 574 4.80 619 5.63 667 6.60 714 7.69 760 8.82 803 9.95
16000 537 4.46 565 4.93 597 5.52 636 6.32 680 7.28 725 8.36 769 9.54 812 10.74
17000 567 5.28 593 5.78 622 6.35 656 7.11 695 8.05 738 9.12 780 10.30 821 11.56
18000 597 6.20 622 6.74 648 7.30 678 8.02 713 8.93 752 9.99 792 11.16 832 12.43
19000 627 7.22 652 7.80 675 8.37 702 9.05 733 9.92 768 10.97 806 12.12 844 13.38
20000 657 8.35 681 8.98 703 9.55 727 10.22 755 11.05 786 12.06 821 13.21 857 14.45
21000 687 9.60 711 10.27 732 10.87 754 11.53 779 12.32 807 13.28 838 14.41 871 15.64
22000 718 10.96 741 11.67 761 12.31 781 12.97 804 13.74 829 14.66 857 15.74 888 16.97
22500 733 11.69 756 12.42 776 13.08 795 13.74 817 14.50 841 15.40 868 16.46 897 17.68
23000 748 12.45 770 13.20 790 13.88 810 14.55 830 15.31 853 16.19 878 17.23 906 18.42
24000 779 14.08 800 14.86 820 15.59 838 16.28 857 17.03 878 17.88 901 18.87 926 20.02
Cfm Total Static Pressure
Std 2.250 2.500 2.750 3.000 3.250 3.500 3.750 4.000
Air RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
8000 817 6.98 858 7.92 896 8.89 932 9.88 966 10.88 998 11.89 1029 12.90 1058 13.93
9000 823 7.50 865 8.50 904 9.52 942 10.58 977 11.65 1010 12.74 1042 13.85 1073 14.97
10000 827 8.02 870 9.08 910 10.16 948 11.26 985 12.39 1019 13.55 1052 14.73 1084 15.92
11000 830 8.56 873 9.67 914 10.81 953 11.96 990 13.15 1026 14.35 1059 15.58 1092 16.83
12000 833 9.11 876 10.27 917 11.46 956 12.67 994 13.91 1030 15.17 1064 16.46 1098 17.76
13000 836 9.71 879 10.90 920 12.13 959 13.39 997 14.69 1033 16.00 1068 17.34 1102 18.70
14000 840 10.37 882 11.58 923 12.84 962 14.14 999 15.47 1036 16.84 1071 18.23 1105 19.65
15000 846 11.11 887 12.33 926 13.61 965 14.93 1002 16.30 1038 17.71 1073 19.14 1107 20.61
16000 853 11.95 893 13.18 931 14.47 969 15.81 1006 17.19 1042 18.62 1076 20.09 1110 21.60
17000 861 12.84 900 14.13 938 15.43 975 16.77 1010 18.17 1046 19.62 1080 21.11 1113 22.64
18000 871 13.77 909 15.12 945 16.48 981 17.85 1016 19.26 1051 20.71 1084 22.22 1117 23.76
19000 881 14.74 918 16.15 954 17.58 989 19.01 1023 20.46 1057 21.92 1090 23.43 1122 24.99
20000 893 15.80 929 17.23 964 18.72 998 20.22 1031 21.73 1064 23.24 1096 24.77 1128 26.34
21000 906 16.98 940 18.40 974 19.91 1008 21.46 1040 23.05 1072 24.63 1104 26.21 1135 27.81
22000 920 18.28 953 19.69 986 21.19 1018 22.77 1050 24.40 1082 26.05 1112 27.71 1143 29.37
22500 928 18.99 960 20.39 992 21.88 1024 23.46 1055 25.10 1086 26.78 1117 28.47 1147 30.17
23000 936 19.73 967 21.13 998 22.61 1030 24.18 1061 25.82 1092 27.52 1122 29.24 1151 30.98
24000 954 21.31 983 22.70 1012 24.17 1043 25.73 1073 27.36 1102 29.07 1132 30.83 1161 32.63
Notes:
1. Fan performance for 40, 50, and 55 ton rooftops is
identical. However, note maximum motor hp size for
each size. Contact your local Trane representative for
information on non-standard motors.
2. Shaded areas at table extremes note non-standard
Bhp or Rpm selection. Contact your local Trane
representative for more information.
3. Supply fan performance table includes internal
resistance of rooftop. For total static pressure
determination, system external static must be added
to appropriate component static pressure drops
(evaporator coil, filters, optional economizer,
optional exhaust fan, optional heating system,
optional cooling only extended casing, optional roof
curb).
4. Maximum Cfm (for UL approval) as follows: 40 Ton
— 18,000 Cfm, 50 Ton — 22,500 Cfm, 55 Ton —
24,000 Cfm
5. Minimum motor horsepower is 7.5 hp.
6. Maximum motor horsepower as follows: 40 Ton —
30 hp, 50 Ton — 30 hp, 55 Ton — 30 hp
7. Maximum 7.5 hp through 15 hp motor Rpm is 1,141
Rpm, maximum 20 hp through 30 hp motor Rpm is
1,170 Rpm.
8. See RT-EB-104 for further details.
(40, 50, 55 Tons)
Performance
Data