Packaged Rooftop Air Conditioners Manual

63RT-PRC010-EN
Table PD-41 — Supply Fan Performance WITH INLET GUIDE VANES — 90 Ton (Cont.)
Cfm Total Static Pressure
Std. 6.250 6.500 6.750 7.000 7.250 7.500 7.750
Air RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
27000 1416 43.47 1440 45.34 1467 47.44 1492 49.40 1516 51.32 1540 53.35 1562 55.17
28000 1420 44.66 1444 46.52 1472 48.74 1497 50.83 1520 52.76 1544 54.79 1568 56.92
29000 1424 45.81 1450 47.90 1474 49.87 1499 51.95 1524 54.15 1547 56.17 1573 58.46
30000 1428 46.91 1453 49.00 1479 51.22 1503 53.30 1528 55.49 1552 57.66 1577 59.94
31000 1434 48.20 1459 50.30 1484 52.52 1508 54.60 1532 56.79 1557 59.10 1579 61.23
32000 1442 49.55 1464 51.55 1489 53.77 1512 55.85 1538 58.33 1559 60.35 1584 62.78
33000 1451 51.09 1473 53.11 1496 55.23 1518 57.33 1541 59.53 1565 61.85 1589 64.28
34000 1461 52.70 1482 54.63 1506 56.90 1527 59.03 1550 61.26 1570 63.29 1594 65.73
35000 1471 54.27 1491 56.22 1515 58.53 1536 60.68 1558 62.93 1578 64.99 1601 67.45
36000 1482 55.91 1503 58.03 1523 60.10 1544 62.28 1566 64.55 1589 66.93 1609 69.11
37000 1494 57.77 1514 59.79 1534 61.91 1555 64.11 1576 66.42 1597 68.68 1618 71.04
38000 1505 59.46 1527 61.78 1547 63.94 1568 66.19 1586 68.24 1608 70.69 1627 72.92
39000 1518 61.37 1540 63.74 1560 65.94 1579 68.09 1598 70.33 1617 72.50 1638 74.92
40000 1533 63.50 1552 65.66 1572 67.90 1592 70.24 1610 72.37 1629 74.58 1649 77.03
41000 1547 65.62 1566 67.82 1585 69.97 1603 72.20 1624 74.68 1642 76.94 1661 79.28
42000 1561 67.70 1580 69.96 1598 72.15 1617 74.44 1635 76.65 1654 79.10
43000 1576 69.89 1593 72.06 1613 74.46 1630 76.64 1650 79.22
44000 1591 72.20 1609 74.43 1628 76.89 1645 79.12
45000 1607 74.63 1625 76.92 1643 79.30
Notes:
1. Shaded areas indicate non-standard BHP or RPM selections. Contact your local Trane representive for more information.
2. Supply fan performance table includes internal resistance of rooftop. For total static pressure determination, system external static must be added to appropriate component
static pressure drops, (evaporator coil, filters, optional economizer, optional heating system, optional roof curb).
3. Maximum static pressure leaving the rooftop is 4.0’’ H20 positive. The static pressure drops from the supply fan to the space cannot exceed 4.0’’ H20.
4. Minimum motor horsepower is 30 hp.
5. See RT-EB-104 for further details.
Figure PD-10— Supply Fan Performance WITH INLET GUIDE VANES — 90 Ton
Note:
1. Important: Maximum static pressure leaving the rooftop is 4.0” H2O positive. The static pressure drops from the supply fan to the space cannot exceed 4.0” H2O.
(90 Ton)Performance
Data
0 10000 20000 30000 40000 50000 60000
0
1
2
3
4
5
6
7
8
9
4
0
%
W
O
C
F
M
5
0
%
W
O
C
F
M
6
0
%
W
O
C
F
M
9
0
%
W
O
C
F
M
8
0
%
W
O
C
F
M
7
0
%
W
O
C
F
M
1
0
0
H
P
7
5
H
P
60
H
P
5
0
H
P
4
0
H
P
3
0
H
P
2
5
H
P
2
0
H
P
1
6
0
0
R
P
M
1
5
0
0
R
P
M
1
4
0
0
R
P
M
1
3
0
0
R
P
M
1
2
0
0
R
P
M
1
1
0
0
R
P
M
1
0
0
0
R
P
M
9
0
0
R
P
M
CFM
Static Presure, Inches w.c.