Air-Cooled Series R Helical-Rotary Liquid Chiller ™ Model RTAC 120 to 200 (400 to 760kw - 50 Hz) Built for the Industrial and Commercial Markets RLC-PRC005-E4
Introduction The new Trane Model RTAC Air-Cooled Helical-Rotary Chiller is the result of a search for higher reliability, higher energy efficiency, and lower sound levels for today’s environment. In an effort to reduce energy consumed by HVAC equipment and to continually produce chilled water, Trane has developed the Model RTAC chiller with higher efficiencies and a more reliable design than any other air cooled chiller available on the market today.
Contents Introduction 2 Features and Benefits 4 5 6 7 8 9 Improved Acoustical Performance Simple Installation Superior Control with Tracer™ Chiller Controls Options Application Considerations Selection Procedure 12 General Data 13 Performance Data 19 Electrical Data 33 36 36 39 44 45 Dimensional Data 47 Mechanical Specifications 50 Performance Adjustment Factors Controls Generic Building Automation System Controls Typical Wiring Diagrams Job Site Data RLC-PRC005-E4 3
Features and Benefits Water Chiller Systems Business Unit The Series R™ Helical-Rotary Compressor • Unequaled reliability. The next generation Trane helical-rotary compressor is designed, built, and tested to the same demanding and rugged standards as the Trane scroll compressors, the centrifugal compressors, and the previous generation helical-rotary compressors used in both air- and water-cooled chillers for more than 13 years. • Years of research and testing.
Improved Acoustical Performance Figure 2 Cutaway of a compressor The sound levels of the Series R Model RTAA have been steadily improved since its introduction. With the advent of the Model RTAC, sound levels are reduced significantly by addressing two major sources: the compressor and the refrigerant piping. First, the compressor has been specifically designed to minimize sound generation.
Simple Installation Compact Physical Size The Trane Model RTAC chiller averages a 20 percent reduction in physical footprint, while the greatest change is actually 40 percent smaller when compared against the previous design. This improvement makes the RTAC the smallest air-cooled chiller in the industry and a prime candidate for installations that have space constraints.
Superior Control with Tracer Chiller Controls ™ The End of Nuisance Trip-Outs and Unnecessary Service Calls? The Adaptive Control™ microprocessor system enhances the air-cooled Series R chiller by providing the very latest chiller control technology. With the Adaptive Control microprocessor, unnecessary service calls and unhappy tenants are avoided. The unit does not nuisance-trip or unnecessarily shut down.
Options Premium Efficiency and Performance Option This option provides oversized heat exchangers with two purposes. One, it allows the unit to be more energy efficient. Two, the unit will have enhanced operation in high-ambient conditions. Low-Temperature Brine The hardware and software on the unit are factory set to handle lowtemperature brine applications, typically below 5°C [41°F]. Ice Making The unit controls are factory set to handle ice making for thermal storage applications.
Application Considerations Certain application constraints should be considered when sizing, selecting, and installing Trane air-cooled Series R chillers. Unit and system reliability is often dependent on properly and completely complying with these considerations. When the application varies from the guidelines presented, it should be reviewed with your local Trane sales engineer. Unit Sizing Unit capacities are listed in the performance data section.
Application Considerations Figure 5 — GPM Out of Range 29.4°C 7.6 Lps 15.6°C 2.2 Lps 15.6°C 7.6 Lps CV Pump Load 35°C 5.4 Lps 15°C 5.4 Lps 21°C 7.6 Lps CV Pump 35°C 2.2 Lps 35°C 7.6 Lps Leaving-Water Temperature Range Trane air-cooled Series R chillers have three distinct leaving-water categories: standard, low temperature, and ice making. The standard leaving-solution temperature range is 4.4 to 15.6°C [40 to 60°F]. Low-temperature machines produce leaving-liquid temperatures less than 4.
Application Considerations Variable Flow in the Evaporator An attractive chilled-water system option may be a variable primary flow (VPF) system. VPF systems present building owners with several costsaving benefits that are directly related to the pumps. The most obvious cost savings result from eliminating the secondary distribution pump, which in turn avoids the expense incurred with the associated piping connections (material, labor), electrical service, and variable-frequency drive.
Selection Procedure The chiller capacity tables cover the most frequently encountered leavingliquid temperatures. The tables reflect a 6°C [10.8°F] temperature drop through the evaporator. For other temperature drops, apply the appropriate performance data adjustment factors. For chilled brine selections, refer to Figures F-3 and F-4 for ethylene and propylene glycol adjustment factors.
General Data SI Units Table G-1 — RTAC Standard Size Compressor Quantity Nominal Size (1) tons Evaporator Evaporator Model Water Storage L Minimum Flow Lps Maximum Flow Lps Condenser Qty of Coils Coil Length mm Coil Height mm Fin series fins/ft Number of Rows Condenser Fans Quantity (1) Diameter mm Total Air Flow m3/s Nominal RPM Tip Speed m/s Motor kW kW Min Starting/Operating Ambient(2) Standard Unit °C Low-Ambient Unit °C General Unit Refrigerant Number of Independent Refrigerant Circuits % Minimum Load
General Data SI Units Table G-3 — RTAC Low Noise Standard Size Compressor Quantity Nominal Size (1) tons Evaporator Evaporator Model Water Storage L Minimum Flow Lps Maximum Flow Lps Condenser Qty of Coils Coil Length mm Coil Height mm Fin series fins/ft Number of Rows Condenser Fans Quantity (1) Diameter mm Total Air Flow m3/s Nominal RPM Tip Speed m/s Motor kW kW Min Starting/Operating Ambient(2) Standard Unit °C Low-Ambient Unit °C General Unit Refrigerant Number of Independent Refrigerant Circuits % Min
General Data SI Units Table G-4 — RTAC High Efficiency Low Noise Size Compressor Quantity Nominal Size (1) tons Evaporator Evaporator Model Water Storage L Minimum Flow Lps Maximum Flow Lps Condenser Qty of Coils Coil Length mm Coil Height mm Fin series fins/ft Number of Rows Condenser Fans Quantity (1) Diameter mm Total Air Flow m3/s Nominal RPM Tip Speed m/s Motor kW kW Min Starting/Operating Ambient(2) Standard Unit °C Low-Ambient Unit °C General Unit Refrigerant Number of Independent Refrigerant Circuit
General Data English Units Table G-5 — RTAC Standard Size Compressor 140 155 170 185 200 Quantity Nominal Size (1) tons 2 70/70 2 70/85 2 85/85 2 85/100 2 100/100 Evaporator Model Water Storage Minimum Flow Maximum Flow gal gpm gpm F140 35 171.2 524.7 F155 37.3 182.3 605.6 F170 39.8 198.2 683.2 F185 41.2 215.6 626.2 F200 43.2 215.6 767.2 4 13/13 3.5 192 3 4 15/13 3.5 192 3 4 15/15 3.5 192 3 4 18/15 3.5 192 3 4 18/18 3.5 192 3 ft/s kW 4/4 30 75867 915 120 1.
General Data English Units Table G-7 — RTAC Low Noise Standard Size Compressor Quantity Nominal Size (1) tons Evaporator Evaporator Model Water Storage gal Minimum Flow gpm Maximum Flow gpm Condenser Quantity of Coils Coil Length ft Coil Height ft Fin Series fins/ft Number of Rows Condenser Fans Quantity (1) Diameter in.
General Data English Units Table G-8 — RTAC High Efficiency Low Noise Size Compressor Quantity Nominal Size (1) tons Evaporator Evaporator Model Water Storage gal Minimum Flow gpm Maximum Flow gpm Condenser Quantity of Coils Coil Length ft Coil Height ft Fin Series fins/ft Number of Rows Condenser Fans Quantity (1) Diameter in.
Performance Data Standard Units (SI Units) Table P-1 — RTAC 140 LWT °C C.C. kW 5 536.3 7 571.1 9 606.9 11 643.4 13 680.6 25 P.I. kW/kW 131.3 136.4 141.7 147.2 152.8 COP kW 3.65 3.75 3.85 3.95 4.04 Table P-2 — RTAC 155 LWT °C C.C. kW 5 587.8 7 625.7 9 664.3 11 703.7 13 743.7 25 P.I. kW/kW 145.8 151.7 157.8 164.1 170.6 COP kW 3.60 3.70 3.79 3.87 3.95 Table P-3 — RTAC 170 LWT °C C.C. kW 5 640.2 7 681.1 9 722.7 11 765.0 13 807.9 25 P.I. kW/kW 160.5 167.2 174.2 181.4 188.8 COP kW 3.56 3.65 3.73 3.81 3.
Performance Data High Efficiency Units (SI Units) Table P-6 — RTAC 120 LWT °C C.C. kW 5 459.3 7 490.9 9 523.2 11 556.3 13 590.0 25 P.I. kW 104.9 108.9 113.0 117.2 121.6 COP kW/kW 3.81 3.94 4.07 4.18 4.29 Table P-7 — RTAC 130 LWT °C C.C. kW 5 506.6 7 541.5 9 577.2 11 613.9 13 651.4 25 P.I. kW 115.3 119.7 124.3 129.0 133.9 COP kW/kW 3.81 3.94 4.07 4.19 4.30 Table P-8 — RTAC 140 LWT °C C.C. kW 5 554.6 7 592.8 9 632.1 11 672.6 13 714.2 25 P.I. kW 125.8 130.7 135.7 140.9 146.3 COP kW/kW 3.82 3.95 4.07 4.
Performance Data High Efficiency Units (SI Units) Table P-12 — RTAC 200 LWT 25 °C C.C. P.I. kW kW 5 803.3 188.3 7 856.9 196.2 9 911.8 204.4 11 968.0 212.9 13 1025.5 221.6 COP kW/kW 3.73 3.84 3.94 4.04 4.12 Entering Condenser Air Temperature (°C) C.C. kW 761.2 812.3 864.8 918.6 973.7 30 P.I. kW 201.3 209.4 217.8 226.5 235.5 COP kW/kW 3.33 3.44 3.53 3.62 3.71 C.C. kW 717.3 766.0 816.0 867.3 919.9 35 P.I. kW 216.1 224.4 233.0 242.0 251.2 COP kW/kW 2.95 3.05 3.14 3.22 3.31 C.C. kW 671.8 717.9 765.4 814.
Performance Data Low Noise Standard Units (SI Units) Table P-13 — RTAC 140 LWT °C C.C. kW 5 510.3 7 541.1 9 572.3 11 603.8 13 635.6 25 P.I. kW 144.5 150.7 157.1 163.7 170.6 Table P-14 — RTAC 155 LWT °C C.C. kW 5 560.0 7 593.4 9 627.1 11 661.1 13 695.3 25 P.I. kW 159.7 166.7 173.9 181.4 189.1 Table P-15 — RTAC 170 LWT °C C.C. kW 5 610.3 7 646.3 9 682.6 11 719.1 13 755.8 25 P.I. kW 175.1 182.9 191.0 199.4 208.0 Table P-16 — RTAC 185 LWT °C C.C. kW 5 675.9 7 715.5 9 755.4 11 795.7 13 836.2 25 P.I.
Performance Data Low Noise HE Units (SI Units) Table P-18 — RTAC 120 LWT °C 5 7 9 11 13.0 C.C. kW 443.2 471.8 500.8 530.2 560.0 25 P.I. kW 113.4 118.0 122.9 128.0 133.2 Entering Condenser Air Temperature (°C) COP kW/kW 3.67 3.76 3.84 3.91 3.98 Table P-19 — RTAC 130 LWT °C 5 7 9 11 13 C.C. kW 489.3 520.9 553.2 585.9 619.1 25 P.I. kW 124.6 129.8 135.2 140.7 146.5 5 7 9 11 13 C.C. kW 535.9 570.7 606.3 642.5 679.4 25 P.I. kW 136.0 141.7 147.5 153.6 159.9 COP kW/kW 3.68 3.77 3.85 3.93 4.
Performance Data Low Noise HE Units (SI Units) Table P-24 — RTAC 200 LWT °C 5 7 9 11 13 C.C. kW 776.4 824.9 874.3 924.4 975.2 25 P.I. kW 202.6 211.6 221.0 230.8 240.9 Entering Condenser Air Temperature (°C) COP kW/kW 3.61 3.68 3.74 3.80 3.85 C.C. kW 732.4 778.4 825.2 872.8 921.0 30 P.I. kW 217.3 226.6 236.4 246.5 257.1 COP kW/kW 3.19 3.25 3.31 3.37 3.42 C.C. kW 686.9 730.3 774.5 819.5 865.1 35 P.I. kW 233.7 243.4 253.6 264.1 275.1 COP kW/kW 2.79 2.85 2.91 2.96 3.01 C.C. kW 640.1 680.8 722.4 764.
Performance Data Standard Units (English Units) Table P-25 — RTAC 140 LWT °F 41 44 45 46 48 C.C. Ton 152.5 160.8 163.6 166.4 172.0 77 P.I. kW 131.3 135.5 137.0 138.5 141.4 EER 12.45 12.75 12.85 12.95 13.14 Table P-26 — RTAC 155 LWT °F 41 44 45 46 48 C.C. Ton 167.2 176.2 179.2 182.2 188.3 77 P.I. kW 145.8 150.7 152.4 154.1 157.5 EER 12.28 12.56 12.65 12.74 12.91 Table P-27 — RTAC 170 LWT °F 41 44 45 46 48 C.C. Ton 182.1 191.8 195.0 198.3 204.9 77 P.I. kW 160.5 166.1 168.0 170.0 173.8 EER 12.14 12.
Performance Data High Efficiency Units (English Units) Table P-30 — RTAC 120 LWT °F 41 44 45 46 48 C.C. Ton 130.6 138.1 140.6 143.2 148.3 77 P.I. kW 104.9 108.2 109.3 110.5 112.7 Entering Condenser Air Temperature (°F) EER EER 12.99 13.37 13.49 13.62 13.85 Table P-31 — RTAC 130 LWT °F 41 44 45 46 48 C.C. Ton 144.1 152.4 155.1 158.0 163.6 77 P.I. kW 115.3 119.0 120.2 121.5 124.0 41 44 45 46 48 C.C. Ton 157.7 166.8 169.8 172.9 179.2 77 P.I. kW 125.8 129.8 131.2 132.6 135.4 EER EER 13.01 13.38 13.
Performance Data Table P-36 — RTAC 200 LWT °F C.C. Ton 232.6 8.83 44 241.2 45 245.5 46 249.8 48 258.5 77 P.I. kW 174.7 194.9 197.1 199.4 204.0 Entering Condenser Air Temperature (°F) EER EER 255.4 13.04 13.14 13.24 13.43 C.C. Ton 7.42 228.6 232.7 236.8 245.1 86 P.I. kW 159.3 208.1 210.3 212.7 217.3 EER EER 278.4 11.67 11.76 11.86 12.04 C.C. Ton 6.26 215.5 219.4 223.4 231.3 95 P.I. kW EER EER C.C. Ton 104 P.I. kW EER EER C.C. Ton 115 P.I. kW EER EER C.C. Ton 122 P.I. kW EER EER 223.0 225.
Performance Data Low Noise Standard Units (English Units) Table P-37 — RTAC 140 Entering Condenser Air Temperature (°F) LWT °F 41 44 45 46 48 EER 11.46 11.64 11.70 11.75 11.86 C.C.Ton 145.1 152.4 154.9 157.3 162.3 77 P.I. kW 144.5 149.7 151.4 153.2 156.7 C.C.Ton 136.1 143.1 145.4 147.7 152.4 86 P.I. kW 156.3 161.7 163.5 165.3 169.0 EER 9.97 10.15 10.20 10.26 10.36 Table P-38 — RTAC 155 Entering Condenser Air Temperature (°F) LWT °F 41 44 45 46 48 EER 11.37 11.54 11.59 11.64 11.73 C.C.Ton 159.
Performance Data Low Noise HE Units (English Units) Table P-42 — RTAC 120 LWT °F C.C.Ton 41 126.0 44 132.8 45 135.1 46 137.4 48 142.0 77 P.I. kW 113.4 117.3 118.6 119.9 122.6 Entering Condenser Air Temperature (°F) EER 12.51 12.78 12.86 12.94 13.09 Table P-43 — RTAC 130 LWT °F C.C.Ton 41 139.2 44 146.7 45 149.2 46 151.7 48 156.8 77 P.I. kW 124.6 128.9 130.4 131.9 134.9 77 P.I. kW 136.0 140.7 142.3 143.9 147.2 EER 12.56 12.82 12.90 12.98 13.14 77 P.I. kW 150.5 155.8 157.6 159.4 163.1 EER 12.60 12.
Performance Data Table P-48 — RTAC 200 Entering Condenser Air Temperature (°F) LWT °F C.C.Ton 41 220.8 44 232.3 45 236.2 46 240.1 48 247.9 77 P.I. kW 202.6 210.1 212.6 215.3 220.5 EER 12.32 12.52 12.58 12.64 12.76 C.C.Ton 208.3 219.2 222.9 226.6 234.0 86 P.I. kW 217.3 225.1 227.7 230.4 235.8 EER 10.87 11.07 11.13 11.19 11.30 C.C.Ton 195.4 205.7 209.1 212.6 219.6 95 P.I. kW 233.7 241.8 244.6 247.4 253.0 EER 9.52 9.70 9.76 9.81 9.92 C.C.Ton 182.0 191.7 195.0 198.2 204.8 104 P.I. kW 251.9 260.3 263.
Performance Data SI Units English Units Table P-49 — ARI Part-Load Values RTAC Standard (along with ARI 550/590-98) Table P-51 — ARI Part-Load Values RTAC Standard (along with ARI 550/590-98) Unit 140 Unit 140 155 170 185 200 % Load 100 75 50 25 100 75 50 25 100 75 50 25 100 75 50 25 100 75 50 25 kW cooling 505.9 372.0 247.9 124.1 554.3 407.6 271.9 135.7 603.4 443.8 295.8 148.1 669.7 491.7 328.1 164.2 737.6 542.3 361.5 180.8 P.I. kW 159.0 85.8 47.3 21.0 175.6 94.7 52.2 24.8 192.4 103.7 58.4 26.
Performance Data SI Units English Units Table P-53 — ARI Part-Load Values RTAC Low-Noise Standard (along with ARI 550/590-98) Table P-55 — ARI Part-Load Values RTAC Low-Noise Standard (along with ARI 550/590-98) Unit 140 Unit 140 155 170 185 200 % Load 100 75 50 25 100 75 50 25 100 75 50 25 100 75 50 25 100 75 50 25 kW cooling 473.9 353.4 232.5 116.1 519.8 382.6 254.6 127.3 566.1 417.1 277.5 138.9 628.8 463.5 308.1 154.0 692.7 508.9 339.4 169.9 P.I. kW 175.9 90.2 49.6 21.9 193.6 99.5 53.5 25.
Performance Adjustment Factors Table F1 — Performance Data Adjustment Factors Fouling Factor (SI) 0.0176 m² K/kW 0.044 m² K/kW Fouling Factor (US) 0.0001 0.00025 Chilled Water Temperature Drop °C 4 5 6 7 8 9 10 4 5 6 7 8 9 10 Chilled Water Temperature Drop °F 8 10 12 14 16 8 10 12 14 16 RLC-PRC005-E4 Altitude Cooling Capacity 0.998 1.000 1.000 1.002 1.003 1.004 1.005 0.982 0.984 0.986 0.987 0.99 0.993 0.995 Sea level Evaporator Flow Rate 1.500 1.200 1.000 0.857 0.750 0.667 0.600 1.479 1.183 0.
Performance Adjustment Factors Figure F1 — Evaporator Water Pressure Drops, RTAC 120 to 200 (SI) 100 90 80 70 60 50 40 30 20 10 20 10 30 40 50 60 70 80 90 100 Flow Lps Evp. F140 (RTAC 120/140) Evp. F155 (RTAC 130/155) Evp. F170 (RTAC 140/170) Evp. F185 RTAC (155/185) Evp. F200 (RTAC 170/200) Evp. F240 (RTAC 200HE) Evp. F220 (RTAC 185HE) Legend (RTAC HE/STD) Figure F2 — Evaporator Water Pressure Drops, RTAC 120 to 200 (US Units) WPD ft of WG 100.0 10.0 1.0 100.
Performance Adjustment Factors Figure F-3 — Ethylene Glycol Performance Factors Figure F-4 — Propylene Glycol Performance Factors Figure F-5 — Ethylene Glycol and Propylene Glycol Freeze Point RLC-PRC005-E4 35
Generic Building Automation System Controls Simple Interface with Other Control Systems Microcomputer controls afford a simple interface with other control systems, such as time clocks, building automation systems, and ice storage systems. This means you can have the flexibility to meet job requirements while not having to learn a complicated control system. This setup has the same standard features as a stand-alone water chiller, with the possibility of having the following optional features.
Generic Building Automation System Controls Tracer Summit™ Controls — Interface with theTrane Integrated Comfort System (ICS) Trane Chiller Plant Manager with ICS The Tracer Chiller Plant Manager building management system provides building automation and energy management functions through standalone control. The Chiller Plant Manager is capable of monitoring and controlling your entire chiller plant system.
Controls Tracer™ Chiller Control human interfaces The Trane air-cooled Series R Model RTAC chiller offers two easy-to-use operator interface panels, the EasyView, and the DynaView. Standard Features External Auto/Stop A job-site-provided contact closure will turn the unit on and off. Figure 7 — Easy View Chilled Waterflow Interlock A job-site-provided contact closure from a chilled-water pump contactor, or a flow switch, is required and will allow unit operation if a load exists.
Typical Wiring Diagram RTAC 120-200 Figure 9 — Compressor wiring diagram and control supply Figure 10 — Control diagram RLC-PRC005-E4 39
Typical Wiring Diagram RTAC 120-200 40 Figure 11 — Compressor control diagram RLC-PRC005-E4
Typical Wiring Diagram RTAC 120-200 Figure 12 — Control wiring diagram Figure 13 — Option control diagram RLC-PRC005-E4 41
Typical Wiring Diagram RTAC 120-200 5B53 Legend 5B56 5E51 5R3 5R51 Item Designation A2 Dual Analog Input/Output Module A3 Fans Inverter Interface Module A4 4 Relays Output Module A5 2 Relays Output Module A6 Dual Low Voltage Binary Input Module A7 Dual High Voltage Binary Input Module A8 Dual Triac Output Module A9 Communication Module A10 Power Supply Module A14 Starter Module A53 Local Human Interface A54 Remote Human Interface A55 IPC Buffer K43 6S43 Relay Q2 Circuit Breaker 1B52 Evaporator Heater
Typical Wiring Diagram RTAC 120-200 Figure 14 — Condenser fan wiring diagram Figure 15 — Condenser fan control diagram RLC-PRC005-E4 43
Job Site Data Job Site Connections Table J-1 — Customer Wire Selection Voltage 400/3/50 Unit Size Standard 140 155 170 185 200 Standard Low Noise 140 155 170 185 200 High Efficiency 120 130 140 155 170 185 200 High Efficiency Low Noise 120 130 140 155 170 185 200 44 Unit without Disconnect Switch Wire Selection Size to Main Terminal Block Minimum cable Maximum cable size mm² size mm² Unit with Disconnect Switch Wire Selection Size to Disconnect Switch Disconnect Switch Minimum cable Maximum cable Size (a
Electrical Data Table E-1 — Electrical Data 400/3/50 Unit Wiring Unit Number of Power Size Connections Standard 140 1 155 1 170 1 185 1 200 1 Standard Low Noise 140 1 155 1 170 1 185 1 200 1 High Efficiency 120 1 130 1 140 1 155 1 170 1 185 1 200 1 High Efficiency Low Noise 120 1 130 1 140 1 155 1 170 1 185 1 200 1 Maximum Amps (1) Starting Amps (2) Power Factor Disconnect Switch Size Compressor Fuse Size (A) 398 437 475 525 574 469 494 532 596 645 6x250 + 3x125 6x400 + 3x125 6x400 + 3x125 6x400 + 3
Electrical Data Table E-1 — Electrical Data 400/3/50 Motor Data Compressor (Each) Max Amps (1) Starting Amps (2) Circuit 1 Circuit 2 Circuit 1 Circuit 2 Quantity Standard 2 180 2 214 2 214 2 259 2 259 Standard Low Noise 2 180 2 214 2 214 2 259 2 259 High Efficiency 2 146 2 180 2 180 2 214 2 214 2 259 2 259 High Efficiency Low Noise 2 146 2 180 2 180 2 214 2 214 2 259 2 259 Quantity kW FLA Fans Fuse Size (A) VA A Option Evaporator Heater kW Fans (Each) Control 180 180 214 214 259 251 271 271 330
Dimensional Data 140-155-170 STD 120-130-140 HE RLC-PRC005-E4 Figure 16 47
Dimensional Data 185-200 STD 185-200 HE 48 Figure 17 RLC-PRC005-E4
Dimensional Data Liquid Chillers 1 Evaporator Water Inlet Connection 2 Evaporator Water Outlet Connection 3 Electrical Panel 4 Power Supply Inlet (155 X 400) 5 Rigging Eyes 045 6 Operating Weight (Kg) 7 Refrigerant Charge (Kg) R134a 8 Oil Charge (Litres) 9 Minimum Clearance (For Maintenance) 10 Minimum Clearance (Evaporator Tubes Removal) 11 Minimum Clearance (Air Entering) 12 Frame Post 13 Recommended Chilled Water Pipework Layout Options 14 Power Disconnect Switch 15 Isolators 16 Chilled Water Pump Start
Mechanical Specifications General Units are leak- and pressure-tested at 24.5 bars [350 psi] high side and 14 bars [200 psi] low side, and then evacuated and charged. Packaged units ship with a full operating charge of oil and refrigerant. Unit panels, structural elements, and control boxes are constructed of 1.5 to 3 mm [11 to 16 gauge] galvanized sheet metal and mounted on a welded structural-steel base.
Literature Order Number RLC-PRC005-E4 File Number PL-RF-RLC-PRC-0005-E4-0800 Supersedes New Stocking Location La Crosse The Trane Company An American Standard Company www.trane.com Since The Trane Company has a policy of continuous product improvement, it reserves the right to change design and specifications without notice. For more information contact your local sales office or e-mail us at comfort@trane.