Propeller Unit Heaters/Unitary 8.0 to 705.
Introduction The square, compact design of the Model P and rectangular Model S allow easy handling and installation. In most cases, only one person is needed to carry a unit. What’s more, the Model P can be stored standing on end. This means several units can be loaded on a single skid for moving from one point to another. Yet, the benefits of this compact design go beyond ease of installation. They continue with attractive styling.
Contents Model Number Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Features & Benefits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Application Consideration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Performance Data . . . . . . . . . . . . . . . . .
Model Number Description U H S B A 1 8 1 T A A 1 0 1 A 0 A 0 A 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 Service Model Number Description DIGIT 1,2,3 — PRODUCT TYPE UHP UHS 280 336 384 500 600 720 DIGIT 8—VOLTAGE DIGIT 4— DEVELOPMENT SEQUENCE 1 3 B 4 5 6 7 DIGIT 5, 6, 7—CAPACITY/COIL TYPE Hot Water Only "Serpentine Type Coil" Model S A08 A18 A25 A36 8,030 BTU/HR 18,400 BTU/HR 24,800 BTU/HR 35,900 BTU/HR Steam or Hot Water "Header Type Coil" Model S 018 02
Features & Benefits Features & Benefits: Overview Trane propeller unit heaters feature the largest selection of standard sizes from any line in the industry. In fact, vertical Model P and horizontal Model S unit heaters provide enough ‘off-the-shelf’ selections to fit almost any application. The versatile two-in-one Model P is available in 15 sizes with capacities from 41.3 MBh to 705.6 MBh. The companion standard and bypass Model S is available in 23 sizes with the capacities from 8.0 MBh up to 360 MBh.
Features & Benefits Steam Pressure Control SPST switch opens on a rise in pressure. Control is automatically reset, has a range of 0 to 15 PSIG (0 to 103 KPa) and has an adjustable differential. Other actions, ranges, circuits and manual reset models are available on request. Manual Starters Single and three-phase models are available. Standard models are single-speed, toggle-operated, NEMA Type 1 and are surfacemounted.
Application Consideration General Rules In locating or spotting Trane Propeller Unit Heaters – either the Model S Horizontal or Model P Projection Unit Heater – the following general rules should be considered. 1. Spot units at points of greatest heat loss. Blanket outside doorways effectively and provide ample coverage for exposed window areas. 2.
Application Consideration increase the downward projection of heat by as much as 45% over units without diffusers. Model P Units with the Louver Cone Diffusers can also be used to blanket doorways effectively, as shown in Figure 2 by simply adjusting half of the louvers vertically, and half closed. Model S horizontal-type units are ideal for mounting in plant areas where ceilings are low.
Application Consideration VE AL V TE GA "HIGH PRESSURE STEAM" PI TC H UP LY PP SU RN TU RE VE AL EV T GA PI TC K OC TC PE H UP D-6058 AP TR SS) ET PA CK BY BU AIR ITH (W ER IN RA ST Figure 5. Figure 6.
Application Consideration PET COCK (SYSTEM VENT) RE TU RN GATE VALVE SU PP LY "FORCED HOT WATER" (Serpentine Units) GATE VALVE DRAIN VALVE D-6057 Figure 7.
Selection Procedure Trane Propeller Unit Heaters Both Model S and Model P Propeller Unit Heaters are ideally suited to such a wide variety of installations that there can be no hard and fast rules regulating their selection. In determining the type and size of the units for any building, the following points are generally considered: BTU Requirements While the choice of units depends upon several important factors, the total Btu requirement is usually determined first.
Selection Procedure Formula The following formula is used to arrive at final air temperature volume when 70 F (Standard Air Basis) is known or vice versa: Table 1. Max. Mounting Heights and Distance of throw for Model S Units (based on 2 lbs Steam Pressure 60F entering Air) Cfm at final temp.
Selection Procedure obtained by equipping these units with Louver Cone Diffusers. The individually adjustable blades of the Louver Cone permit an infinite variety of adjustments to meet any on-the-job problems. By setting the blades vertically to straighten the airstream, as much as 45% increase in throw can be obtained. 4. Solution: Under 40 F and across from 30 lbs. in Table 2, find the factor 1.51. Hot Water Selection Example 1. Equivalent capacity of required unit at 2 lbs.
Selection Procedure Table 3. Factors For Determining Steam Capacity Of Model P Projection Unit Heaters At Various Pressures And Temperatures (Table based on 2 PSIG and 60 F Entering Air) Steam Pressure PSIG Temperature of Entering Air (F) -10 Draw-Through Unit 0 10 20 30 40 50 60 70 80 90 100 0 1.49 1.41 1.33 1.25 1.18 1.11 1.03 0.96 0.90 0.83 0.76 0.69 2 1.52 1.45 1.37 1.29 1.22 1.15 1.07 1.00 0.93 0.86 0.80 0.73 5 1.58 1.50 1.42 1.34 1.27 1.20 1.12 1.05 0.
Selection Procedure Table 4. Maximum Mounting Heights in Feet for Model P Unit Heaters with and without Louver Cone Diffuser (continued) Unit Size Steam Pressure (PSI) 2 5 10 50 75 102-P-L LS 15.0 18.5 14.5 18.0 14.5 18.0 13.0 16.0 12.5 15.0 122-P 16.0 19.5 15.5 19.0 15.5 18.5 14.0 17.0 13.5 16.0 122-P-L 21.0 26.0 20.5 25.5 20.0 25.0 17.5 22.5 17.0 21.5 146-P 15.5 19.0 15.0 18.5 14.5 18.0 13.0 16.0 12.0 15.5 146-P-L 18.0 22.5 17.5 22.0 17.5 21.5 15.0 18.5 14.0 18.
Selection Procedure Table 5. Maximum Spread in Feet Unit Size: P 42 64 80 102 122 146 166 202 252 280 336 384 500 600 720 Spread ft 15 17 20 24 26 27 28 32 35 37 45 50 54 57 60 Additional Selection Data Motor and Fan Speeds Motor and fan speeds are selected to provide efficient performance. The solid-state speed control will provide an infinite number of speeds between the highest and the lowest cataloged fan speeds.
Performance Data Steam Performance Data Horizontal Unit Heaters Performance based on 2# steam pressure at heater with air entering @ 60° F (max working pressure 150 PSI,366° F) Table 7. Model No. S-18 S-24 S-36 S-48 S-60 S-72 S-84 S-96 S-108 Total MBh Cond. lbs./hr. E.D.R. Sq. Ft. LAT °F 18,000 18.0 75 102 16,200 16.2 68 105 24,000 24.5 100 109 21,600 22.0 90 112 36,000 37.0 150 119 32,400 33.0 135 120 48,000 49.0 200 119 43,200 44.0 180 123 60,000 61.
Performance Data Vertical Unit Heaters Performance based on 2# steam pressure at heater with air entering @ 60°F. Table 8.
Performance Data Table 9. Model No. P-42L P-64L Low Output Units: Standard Model Units w/All Air Ports Open Total MBh Cond. lbs./hr. E.D.R. Sq. ft. LAT °F. 34.8 36 145 108 26.0 27 108 111 57.2 59 238 104 45.8 48 191 109 Motor HP 1/40 1/20 Motor RPM Nominal CFM Outlet Velocity FPM 1550 668 950 1150 470 672 1550 1200 1190 1150 862 858 1550 1360 1350 1150 995 992 1070 1640 1050 850 1290 827 Sound Rating I I 68.0 71 283 106 55.0 57 229 111 85.
Performance Data Table 11. STEAM CORRECTION FACTORS BASED ON 2 LBS. STEAM 60° E.A.T. STEAM PRESSURE - LBS. PER SQ. IN. (SATURATED) ENTERING AIR TEMP 0 2 5 10 15 20 30 40 50 75 30° 1.18 1.22 1.27 1.34 1.40 1.45 1.53 1.61 1.67 1.79 40° 1.11 1.15 1.20 1.27 1.32 1.37 1.46 1.53 1.59 1.71 50° 1.03 1.07 1.12 1.19 1.25 1.30 1.39 1.46 1.52 1.64 60° 0.96 1.00 1.05 1.12 1.18 1.23 1.32 1.39 1.45 1.57 70° 0.90 0.93 0.98 1.05 1.11 1.16 1.25 1.32 1.38 1.
Performance Data Hot Water Performance Data Horizontal Unit Heaters Peformance based on 200° EWT, 60° E.A.T., 20° WTD (max working pressure 150 PSI, 366° F) Table 13. Model No. S-A08 S-A18 S-A25 S-A36 S-18 S-24 S-36 S-48 S-60 S-72 S-84 S-96 S-108 Total MBh 8.0 6.8 18.4 15.7 24.8 21.2 35.9 32.3 13.1 11.7 17.4 15.6 26.1 23.5 34.8 31.3 43.6 39.2 52.3 47.0 61.0 54.9 69.7 62.7 78.4 70.5 GPM 0.80 1.9 2.5 3.6 1.3 1.8 2.7 3.5 4.4 5.3 6.1 7.0 7.
Performance Data Vertical Unit Heaters Table 14. Standard Output Units** Water Temp. Model No. Drop P-42 P-42* P-64 P-64* P-80 P-80* P-102 P-102* P-122 P-146 P-166 P-202 P-252 P-280 22 Total MBh GPM WPD LAT °F 10° 28.8 5.93 .37 104.6° 20° 22.7 2.34 .06 95.2° 30° 16.7 1.15 .02 85.9° 10° 22.9 4.71 .24 108.3° 20° 18.1 1.87 .04 98.3° 30° 13.4 .92 .01 88.4° 10° 48.1 9.92 1.05 104.8° 20° 39.6 4.08 .19 96.9° 30° 31.1 2.14 .06 89.0° 10° 38.1 7.
Performance Data Table 14. Standard Output Units** (continued) Water Temp. Model No. Drop 15° P-336 P-384 P-500 P-600 P-720 Total MBh GPM WPD LAT °F 254.9 35.03 6.88 105.1° 20° 242.9 25.03 3.67 103.0° 30° 218.9 15.04 1.42 98.7° 15° 294.7 40.49 6.60 104.2° 20° 280.8 28.94 3.52 102.2° 30° 253.1 17.39 1.36 98.0° 15° ----- ----- ----- ----- 20° 368.1 37.93 5.81 102.3° 30° 333.6 22.92 2.29 98.3° 15° 451.2 62.00 8.78 104.0° 20° 431.1 44.43 4.72 102.
Performance Data Table 15. Low Output Units Standard Model P Units with All Air Ports Open** (continued) Water Temp. Model No. Drop 10° P-122 P-146L P-166L P-202L P-252L P-280L P-336L P-384L P-500L P-600L P-720L Total MBh GPM WPD LAT °F 83.7 17.24 2.40 95.4° 20° 73.9 7.62 .51 91.3 30° 64.2 4.41 .18 87.1° 10° 95.4 19.66 2.92 97.3° 20° 85.5 8.81 .65 93.4° 30° 75.6 5.20 .24 89.5° 10° 112.3 23.15 2.70 95.4° 20° 100.7 10.38 .60 91.8° 30° 89.2 6.13 .
Performance Data Table 16. HOT WATER CALCULATIONS AND CORRECTION FACTORS EXAMPLE: UNIT:__________________P-42 Entering Water Temp. _____160°F Entering Air Temp. ________ 40°F Water Temperature Drop ____ 10°F I. CAPACITY @ 20° TD: A. For 200° EWT, 60° EAT Read output directly from Table 14 & Table 15, 22,700 BTU/HR (Ref., Std. P-42, p. 22). B. For EWT and/or EAT above or below Standard Multiply output from Table 14 & Table 15 by factor from Table 17. 22,700 x .878 = 19,931 BTU/HR. II.
Performance Data Technical & Mounting Data Horizontal Unit Heaters Technical Data The performance data listed in Table 13, Table 14, and Table 15 include sound ratings. The ratings provide a guide in determining the acceptable degree of loudness in particular occupancy situations. Certain general rules apply to specific selection of unit heaters with regard to degree of quietness (or loudness); • The greater the fan diameter, the higher the sound level.
Performance Data Motor Characteristics Data Horizontal Unit Heaters Table 23. Totally Enclosed Motor Type S Unit Model No. AMP MCA MOP HP RPM 115/1/60 18, 24, A08, A18 0.8 1 1.8 16W* 1550 A36 1.4 1.8 3.2 1/20* 1000 1550 36, A25 1.2 1.5 2.7 25W* 48, 60, 72 1.4 1.8 3.2 1/20* 1000 84, 96, 108 2.2 2.8 5.0 1/12* 1000 120, 132, 144, 156, 180, 204, 240 4.5 5.6 10.1 1/3 1140 280, 300, 360 5.4 6.8 12.2 1/2 1100 230/1/60 18, 24, A08, A18 0.4 0.5 0.
Performance Data Table 24. Explosion Proof with Thermal Overload Motor Type S Unit Model No. AMP MCA MOP HP RPM 115/1/60 48, 60, 72, 84, 96, 108, 120, 132 3.7 4.6 8.3 1/6 1140 144, 156, 180, 204 5.4 6.8 12.2 1/4 1140 240, 280, 300 7.4 9.3 16.7 1/3*** 1140 360 7.4 9.3 16.7 1/2*** 1140 48, 60, 72, 84, 96, 108, 120, 132 3.7 4.6 8.3 1/6† 1140 230/1/60 144, 156, 180, 204 5.4 6.8 12.2 1/4† 1140 240, 280, 300 3.7 4.7 8.3 1/3*** 1140 360 3.7 4.7 8.
Performance Data Vertical Unit Heaters Table 25. Totally Enclosed Motor Type P Unit Model No. AMP MCA MOP HP RPM 115/1/60 42 1.23** 1.6 2.8 1/40* 1550 64, 80 2.1** 2.6 4.7 1/20* 1550 102 1.2** 1.5 2.7 1/8* 1070 2.3** 2.9 5.2 1/6 1100 202 3.6** 4.5 8.1 1/4 1100 252 3.6** 4.5 8.1 1/4 1100 280 5.4** 6.8 12.2 1/2 1100 122 146 166 208-230/460/3/60 42 0.98-1.1/0.55 1.2-1.4/0.7 2.2-2.5/1.2 1/6 1140 64, 80 0.98-1.1/0.55 1.2-1.4/0.7 2.2-2.5/1.
Performance Data Table 26. Explosion Proof with Thermal Overload Motor Type P Unit Model No. AMP MCA MOP HP RPM 115/1/60 42 3.8 4.8 8.6 1/6 1140 64, 80 3.8 4.8 8.6 1/6 1140 102 3.8 4.8 8.6 1/6 1140 3.8 4.8 8.6 1/6 1140 202 4.4 5.5 9.9 1/4 1140 252 4.4 5.5 9.9 1/4 1140 280 7.8 9.8 17.6 1/2 1140 122 146 166 208-230/460/3/60 42 1.0-1.0/0.5 1.3-1.3/0.6 2.3-2.3/1.1 1/6 1140 64, 80 1.0-1.0/0.5 1.3-1.3/0.6 2.3-2.3/1.1 1/6 1140 102 1.0-1.0/0.5 1.3-1.
Wiring Diagrams Wiring Diagrams WARNING 1 PHASE LINE 1 PHASE LINE Hazardous Voltage Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury. MOTOR SPEED CONTROLLERS Hazardous Voltage 1. 2. For internal wiring and overload protection on all starters, consult the control manufacturer for details.
Dimensional Data Dimensional Data: P Model H H K K V G A R R G R A (4) MOUNTING HOLES 3 /8 - 16 FOR 42P-80P THREAD TAPS CEILING P L F T STEAM SUPPLY OR HOT WATER RETURN B S STEAM RETURN OR HOT WATER SUPPLY C T E P D Figure 15. Table 27. Models 42-80 Roughing in Dimensional Data - Model Size 42-80 Unit Capacity (MBH) Fan Dia.
Dimensional Data K H H V A K U V R G R A (4) MOUNTING HOLES 3/8 - 16 FOR 102P-384P THREAD TAPS 1/2 - 13 FOR 500P-720P CEILING P STEAM SUPPLY OR HOT WATER RETURN L F T B S C STEAM RETURN OR HOT WATER SUPPLY T E P D Figure 16. Table 28. Models 102-720 Roughing in Dimensional Data - Model Size 102-720 Unit Capacity (MBH) Fan Dia. 102 16 3/4 25 1/4 6 1/8 2 122 16 3/4 25 1/4 6 1/8 2 146 L (Min.
Dimensional Data Table 29. Louver Cone Diffuser Roughing in Dimensions Unit Size A B C D No. of Louvers 42 64 & 80 16 1/2 20 14 1/4 17 6 1/2 8 2 5/8 3 1/8 8 8 102 & 122 146, 166 & 202 24 1/4 28 3/8 21 24 3/4 9 3/4 11 1/2 3 15/16 4 5/8 8 8 252, 280, 336, & 384 35 1/2 500, 600 & 720 41 1/2 31 1/2 37 1/4 13 3/4 17 4 4 3/4 12 12 Dimensional Data: S Model Figure 17.
Dimensional Data Figure 18. Table 31.
Mechanical Specifications Horizontal Specifications General Furnish and install, where indicated or scheduled on plans Model S horizontal steam/hot water unit heaters. Unit shall be equipped as specified herein. All units shall be installed in a neat and workmanlike manner in accordance with this specification and the manufacturer's installation instruction. saturated steam pressure at 366°F, under maximum load conditions. We recommend operating pressure of 75 P.S.I. at 320°F for long life.
Mechanical Specifications Coil Models S-A08– S-A36 Coil is a serpentine design with seamless copper tubing. Aluminum fins have drawn collars to assure permanent bond with expanded tubes. Tubing connection are 3/8" copper tubing, type “M” (.500 O.D.). Coils are factory tested at 250 P.S.I. Motors Motors are totally enclosed, resilient mounted with class “B” windings. All motors are designed for horizontal mounting.
Literature Order Number Trane A business of American Standard Companies www.trane.com For more information, contact your local Trane office or e-mail us at comfort@trane.com UH-PRC001-EN Date August 2007 Supersedes UH-PRC001-EN October 1999 Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.