Horizontal Specifications
General
Furnish and install, where indicated
or scheduled on plans Model S
horizontal steam/hot water unit
heaters. Unit shall be equipped as
specified herein. All units shall be
installed in a neat and workmanlike
manner in accordance with this
specification and the manufacturer's
installation instruction.
Casing
Casings are fabricated from 20
gauge die-formed steel. Casing
substrates are prepared for finishing
with a hot wash, iron phosphatizing
clear rinse, chromic acid rinse and
oven drying. Paint finish is leadfree,
chromate free, alkyd melamine resin
base and applied with an
electrostatic two-pass system. Finish
is baked at 350°F.
Coil Models 18 – 360
Coil elements and headers are heavy
wall drawn seamless copper tubing.
Element tubes are brazed into
extruded header junctions. Pipe
connection saddles are cast bronze.
Aluminum fins have drawn collars to
assure permanent bond with
expanded element tubes and exact
spacing. All Element Assemblies are
submersion tested at factory at 250
P.S.I., and are rated at 150 pounds of
saturated steam pressure at 366°F,
under maximum load conditions. We
recommend operating pressure of 75
P.S.I. at 320°F for long life.
Motors
Motors are totally enclosed, resilient
mounted with class “B” windings.
All motors are designed for
horizontal mounting. Motors under
1/3 H.P. are totally enclosed, frame
mounted, 115/1/60 with thermal
overload protection and
permanently lubricated sleeve
bearings with optional solid state
speed controller available. 1/3 H.P.
(115/1/60) motors are open frame
construction, with thermal overload
protection and ball bearings. 1/3 H.P.
at (230V) and1/2 H.P. (230V) motors
are open frame construction, with
thermal overload protection and ball
bearings. 1/3 and 1/2 H.P. motors are
available in single and 3 phase in
open frame construction or
explosion-proof housings, all the
above are available as options.
Explosion Proof Motors
An enclosed motor whose enclosure
is designed and constructed to
withstand an explosion of a specific
gas or vapor which may occur within
the motor and to prevent the ignition
of this gas or vapor surrounding the
machine.
Motors comply with the National
Electrical Code classification as
follows:
Class I, Group D; all sizes
Class II, Group F; all sizes
Class II, Group G; all sizes
Division I & II Installations
T-code (T3B)
Explosion proof equipment is not
generally available for Class I,
Groups A and B and it is necessary
to isolate motors from the hazardous
area. All explosion proof motors are
shelf mounted.
Fans
Fans are aluminum blade, hub type
designed and balanced to assure
maximum air delivery, low motor
horsepower requirements and quiet
operation. Blades are spark proof.
Fan Guards
Fan guards are welded steel, zinc
plated or painted. To meet CSA and
OSHA requirements, units mounted
below 8 feet from floor must be
equipped with an OSHA fan guard.
OSHA fan guards are optional.
Air Deflection Louvers
Units are equipped with horizontal,
individually adjustable louvers. An
optional vertical louver is available
for four-way air control.
Serpentine Coil Specifications
General
Furnish and install, where indicated
or scheduled on plans Model S-A
horizontal hot water unit heaters.
Unit shall be equipped as specified
herein. All units shall be installed in
a neat and workmanlike manner in
accordance with this specification
and the manufacturer's installation
instruction.
Casing
Casings are fabricated from 20
gauge die-formed steel. Casing
substrates are prepared for finishing
with a hot wash, iron phosphatizing
clear rinse, chromic acid rinse and
oven drying. Paint finish is leadfree,
chromate free, alkyd melamine resin
base and applied with an
electrostatic two-pass system. Finish
is baked at 350°F.
Mechanical Specifications