Catalogue

RLC-PRC039B-EN 21
Performance Data
46
120 127.8 121.2 11.9 118.8 131.9 10.2 109.4 144 8.7 99.8 157.5 7.3
130 141.9 132.9 12 131.9 144.7 10.3 121.7 157.9 8.8 111.1 172.5 7.4
140 156.7 145 12.2 145.8 157.9 10.5 134.7 172.2 8.9 122.9 187.5 7.5
155 170.3 160.3 12 158.6 174 10.3 146.4 189.4 8.8 133.7 205.8 7.4
170 184.9 176.3 11.8 172 190.9 10.2 158.8 207.2 8.7 145.3 225.5 7.4
185 203.6 193.3 11.9 189.9 209.2 10.3 175.8 227.1 8.8 161.3 247 7.5
200 223.8 211.2 12 209 228.4 10.4 193.7 247.7 8.9 178 269.3 7.6
250 265.6 257.1 11.7 247.2 278.9 10.1 228.4 303.4 8.6 194 301 7.4
275 297.7 284.6 11.9 277.5 307.5 10.3 256.7 333.4 8.8 235.4 362.3 7.5
300 335.2 320.1 11.9 313.2 345.5 10.3 290.5 374.3 8.9 267.1 406.5 7.6
350 373 358.3 11.8 347.5 387.3 10.2 321.2 420.1 8.7 294.3 456.6 7.4
375 411.3 394.1 11.8 383.9 425.7 10.3 355.7 461.4 8.8 326.7 501.2 7.5
400 450.6 430.8 11.9 421.2 464.8 10.3 390.8 503.3 8.9 359.4 546.3 7.6
48
120 132.5 123.8 12.1 123.2 134.7 10.4 113.5 146.8 8.8 103.6 160.3 7.4
130 147 135.8 12.2 136.8 147.6 10.5 126.2 160.9 9 115 175 7.5
140 162.3 148.1 12.4 151.1 161 10.7 139.6 175.5 9.1 126.2 188.2 7.7
155 176.3 163.8 12.2 164.2 177.6 10.5 151.7 193.1 9 137.9 208.2 7.6
170 191.3 180.3 12 178.1 194.9 10.4 164.5 211.4 8.9 150.6 229.7 7.5
185 210.6 197.7 12.1 196.5 213.7 10.5 182 231.7 9 167 251.8 7.6
200 231.6 216.1 12.2 216.3 233.4 10.6 200.6 252.9 9.1 183.9 273.8 7.7
250 274.8 262.9 11.9 255.9 284.9 10.3 236.5 309.5 8.8 194.7 293.9 7.6
275 308 291.1 12 287.2 314.2 10.4 265.7 340.2 9 243.1 367.9 7.6
300 346.8 327.5 12 324.1 353.2 10.5 300.7 382.2 9 275.7 412.9 7.7
350 385.7 366.3 11.9 359.4 395.5 10.3 332.4 428.4 8.9 303.4 462.3 7.5
375 425.3 403 12 397.1 434.9 10.4 368 470.8 8.9 335.1 504.6 7.6
400 466 440.7 12 435.7 475 10.5 404.3 513.9 9 365.8 544.8 7.7
1. Rated in accordance with AHRI Standard 550/590 based on TOPSS version 140: sea level altitude, evaporator fouling factor of 0.0001°F-ft²h/Btu,
evaporator temperature drop of 10°F, and 2 pass evaporator configuration.Consult a Trane representative for additional performance information.
2. kW input is for compressors only.
3. EER = Energy Efficiency Ratio (Btu/watt-hour). Power inputs include compressors, condenser fans and control power.
4. Interpolation between points is permissible. Extrapolation is not permitted.
Table 6. 50 Hz high efficiency I-P units
Evap
Leaving
Water
Temp (°F)
Cond Entering Air Temp (°F)
85 95 105 115
Unit
Size Tons
kW
Input² EER³ Tons
kW
Input² EER³ Tons
kW
Input² EER³ Tons
kW
Input² EER³