Catalogue

RLC-PRC006M-EN 21
Performance Data
46
140 154.1 148.8 11.5 143.4 161.3 9.9 132.3 175.4 8.5 121 191 7.2
155 169 161.5 11.6 157.4 175.2 10 145.6 190.5 8.6 133.4 207.6 7.2
170 184.5 174.4 11.7 172.2 189.3 10.1 159.5 206.1 8.7 146.6 224.7 7.3
185 201.9 194.1 11.5 188.5 210.1 10 174.6 228.3 8.6 160.4 248.5 7.3
200 220.7 214.7 11.4 206 231.9 9.9 190.8 251.3 8.5 175.1 273.1 7.2
225 242.1 236.8 11.3 226.3 255.8 9.9 209.8 277.5 8.5 192.8 301.7 7.2
250 265.8 260.2 11.3 248.5 281.2 9.9 230.5 304.9 8.5 211.6 331.6 7.2
275 295.4 284 11.5 275.8 307.3 10 255.6 333.6 8.6 234.9 362.9 7.3
300 331.5 325.7 11.3 309.5 351.2 9.8 286.7 380.2 8.5 263.3 412.6 7.2
350 376.6 373.3 11.2 352 402.4 9.8 326.3 435.4 8.4 297.3 467.6 7.2
400 444.4 437.6 11.2 415.2 471.8 9.8 384.9 510.5 8.5 353.7 553.8 7.2
450 488.8 484.8 11.2 457.1 522.7 9.8 424.1 565.7 8.4 384.5 602.6 7.2
500 535.2 533.4 11.2 500.7 574.8 9.7 464.5 621.9 8.4 416.8 652.5 7.2
48
140 159.6 152 11.7 148.5 164.6 10.1 137.1 178.7 8.6 124.5 192.8 7.3
155 175 164.9 11.7 163.1 178.7 10.2 150.8 194.2 8.7 137.3 209.6 7.4
170 190.9 178.1 11.8 178.3 193.1 10.3 165.3 210 8.8 152 228.6 7.5
185 208.9 198.3 11.6 195.1 214.5 10.1 180.8 232.7 8.7 166.2 253 7.4
200 228.2 219.4 11.5 213.1 236.7 10 197.4 256.3 8.6 181.3 278.1 7.4
225 250.4 242 11.5 234.1 261.3 10 217.1 283.1 8.6 199.5 307.5 7.3
250 275 266.2 11.5 257.1 287.3 10 238.4 311.3 8.6 216 331.7 7.4
275 305.7 290.2 11.7 285.4 313.6 10.1 264.7 340 8.7 243.3 369.5 7.4
300 342.8 333 11.4 320.1 358.7 10 296.7 387.7 8.6 272.5 420.3 7.3
350 389.6 381.8 11.3 364.1 411.2 9.9 337.5 444.5 8.5 301.2 462.7 7.3
400 459.4 447.4 11.4 429.2 481.7 9.9 398.1 520.6 8.6 363.2 558.7 7.3
450 505.3 495.8 11.3 472.6 533.9 9.9 438.5 577.3 8.5 389.9 597.2 7.4
500 553.4 545.7 11.3 517.7 587.5 9.9 480.3 635.2 8.5 421.5 644.1 7.4
1. Rated in accordance with AHRI Standard 550/590 based on TOPSS version 140: sea level altitude, evaporator fouling factor of 0.0001°F-ft²h/Btu,
evaporator temperature drop of 10°F, and 2 pass evaporator configuration. Consult a Trane representative for additional performance information.
2. kW input is for compressors only.
3. EER = Energy Efficiency Ratio (Btu/watt-hour). Power inputs include compressors, condenser fans and control power.
4. Interpolation between points is permissible. Extrapolation is not permitted.
Table 7. 60 Hz standard efficiency I-P units (continued)
Evap
Leaving
Water
Temp (°F)
Cond Entering Air Temp (°F)
85 95 105 115
Unit
Size Tons
kW
Input² EER³ Tons
kW
Input² EER³ Tons
kW
Input² EER³ Tons
kW
Input² EER³