Catalogue

36 RLC-PRC006M-EN
Electrical Data
500
200/60/3 1 n/a
200/60/3 2 4 14/14 1.5 6.5 7.3 1.59
459-459/
459-459
2525-2525/
2525-2525
821-821/
821-821
1129/
1129
1200/
1200
230/60/3 1 n/a
230/60/3 2 4 14/14 1.5 6.5 7.3 1.59
399-399/
399-399
2126-2126/
2126-2126
691-691/
691-691
994/994
1200/
1200
380/60/3 1 n/a
380/60/3 2 4 14/14 1.5 3.5 3.7 1.59
242-242/
242-242
1306-1306/
1306-1306
424-424/424-424 596/596 800/800
460/60/3 1 4 28 1.5 3 3.7 1.59
200-200/
200-200
1065-1065/
1065-1065
346-346/346-346 941 1000
460/60/3 2 4 14/14 1.5 3 3.7 1.59
200-200/
200-200
1065-1065/
1065-1065
346-346/346-346 495/495 600/600
575/60/3 1 4 28 1.5 2.5 3.0 1.59 160-160/160-160 853-853/853-853 277-277/277-277 756 800
575/60/3 2 4 14/14 1.5 2.5 3.0 1.59 160-160/160-160 853-853/853-853 277-277/277-277 397/397 500/500
Notes:
1. Voltage Utilization Range: +/- 10% of rated voltage. Rated voltage (use range): 200/60/3 (180-220), 230/60/3 (208-254), 380/60/3 (342-418), 460/60/
3 (414-506), 575/60/3 (516-633)
2. As standard, 140-250 ton units have a single point power connection. Optional dual point power connections are available. As standard, 275-500 ton
unitshave dual point power connections. Optional single point power connections are available on 460V and 575V/60 Hz units.
3. Control VA includes operational controls only. It does not include evaporator heaters. A separate 115/60/1, 20 ampcustomer provided power connection is
required to power the evaporator heaters (1640 watts).
4. RLA - Rated Load Amps
5. XLRA - Locked Rotor Amps - based on full winding (x-line) start units). YLRA for wye-delta starters is ~1/3 of LRA of x-line units.
6. MCA - Minimum Circuit Ampacity - 125 percent of largest compressor RLA plus 100 percent of all other loads.
7. Max fuse or MOPD = 225 percent of the largest compressor RLA plus 100 percent of the second compressor RLA, plus the sum of the condenser fan FLA.
(Use FLA per circuit, NOT FLA for the entire unit).
8. Local codes may take precedence.
9. All ambient means standard, low, high and wide ambient options.
Table 14. Standard efficiency all ambient options (continued)
Unit
Size
Rated
Voltage
1
#
Power
Conn
2
#
Comp
# Fan
Ckt1/
Ckt2
Fan
kW
Fan
FLA
VFD
Input
Cntrl
kVA
3
RLA
4
Ckt1/Ckt2
XLRA
5
Ckt1/Ckt2
YLRA
5
Ckt1/Ckt2
MCA
6
Ckt1/
Ckt2
MOP
7
Ckt1/