Catalogue

RLC-PRC006M-EN 45
Electrical Data
350
200/60/3 1 n/a
200/60/3 2 4 14/14 1.5 6.5 7.3 1.59
320-320/
320-320
2156-2156/
2156-2156
701-701/
701-701
817/817 1000/1000
230/60/3 1 n/a
230/60/3 2 4 14/14 1.5 6.5 7.3 1.59
278-278/
278-278
1756-1756/
1756-1756
571-571/
571-571
722/722 1000/1000
380/60/3 1 n/a
380/60/3 2 4 14/14 1.5 3.5 3.7 1.59
168-168/
168-168
1060-1060/
1060-1060
345-345/
345-345
430/430 500/500
460/60/3 1 4 28 1.5 3 3.7 1.59
139-139/
139-139
878-878/
878-878
285-285/
285-285
681 700
460/60/3 2 4 14/14 1.5 3 3.7 1.59
139-139/
139-139
878-878/
878-878
285-285/
285-285
358/358 450/450
575/60/3 1 4 28 1.5 2.5 3.0 1.59
111-111/
111-111
705-705/
705-705
229-229/
229-229
547 600
575/60/3 2 4 14/14 1.5 2.5 3.0 1.59
111-111/
111-111
705-705/
705-705
229-229/
229-229
287/287 350/350
Notes:
1. Voltage Utilization Range: +/- 10% of rated voltage. Rated voltage (use range): 200/60/3 (180-220), 230/60/3 (208-254), 380/60/3 (342-418), 460/60/
3 (414-506), 575/60/3 (516-633)
2. As standard, 140-250 ton units have a single point power connection. Optional dual point power connections are available. As standard, 275-500 ton units
have dual point power connections. Optional single point power connections are available on 460V and 575V/60 Hz units.
3. Control VA includes operational controls only. It does not include evaporator heaters. A separate 115/60/1, 20 amp customer provided power connection
is required to power the evaporator heaters (1640 watts).
4. RLA - Rated Load Amps
5. XLRA - Locked Rotor Amps - based on full winding (x-line) start units). YLRA for wye-delta starters is ~1/3 of LRA of x-line units.
6. MCA - Minimum Circuit Ampacity - 125 percent of largest compressor RLA plus 100 percent of all other loads.
7. Max fuse or MOPD = 225 percent of the largest compressor RLA plus 100 percent of the second compressor RLA, plus the sum of the condenser fan FLA.
(Use FLA per circuit, NOT FLA for the entire unit).
8. Local codes may take precedence.
9. All ambient means standard, low, high and wide ambient options.
Table 17. Extra efficiency high and wide ambient
Unit
Size
Rated
Voltage
1
#
Power
Conn
2
#
Comp
# Fan
Ckt1/
Ckt2
Fan
kW
Fan
FLA
VFD
Input
Cntrl
kVA
3
RLA
4
Ckt1/Ckt2
XLRA
5
Ckt1/Ckt2
YLRA
5
Ckt1/Ckt2
MCA
6
Ckt1/
Ckt2
MOP
7
Ckt1/
Ckt2