Installation and Maintenance Manual

14 VAV-SVX07A-EN
VAV Start Up/Check Out Procedure
LED Description and Behavior
There are 15 LEDs on the front of the Tracer UC400 controller. Figure 1, p. 14 shows the locations
of each LED and describes the behavior of each.
Tracer UC400 Controller Module
LED Description and Operation
There are 15 LEDs on the front of the Tracer UC400 controller. Figure 1, p. 14 shows the locations
of each LED and a description of its behavior in specific instances.
Marquee LED
Shows solid green when the Tracer UC400 controller is powered and operating normally.
Shows solid red when the Tracer UC400 controller is powered, but represents low power or
a malfunction.
Blinks red when an alarm exists.
LINK
•The TX LED blinks green at the data transfer rate when the Tracer UC400 controller transfers
data to other devices on the link.
•The RX LED blinks yellow at the data transfer rate when the Tracer UC400 controller receives
data from other devices on the link.
IMC
•The TX LED blinks green at the data transfer rate when the Tracer UC400 controller transfer data
to other devices on the IMC bus.
•The RX LED blinks yellow at the data transfer rate when the Tracer UC400 controller receives
data from other devices on the IMC bus.
Service
Shows solid green when pressed.
BO1 to BO9
Shows solid green when corresponding binary output is on.
Figure 1. LED locations
SERVI
C
E
IM
C
LINK
RX
TX
BO2 9OB1OBBO8BO7BO6BO5BO3 BO4
Marquee LED