Installation and Maintenance Manual

VAV-SVX07A-EN 15
VAV Start Up/Check Out Procedure
Communication Wiring
WARNING
Electrocution and Fire Hazards with Improperly Installed and Grounded
Field Wiring!
Improperly installed and grounded field wiring poses FIRE & ELECTROCUTION hazards. To avoid
these hazards, you MUST follow requirements for field wiring installation and grounding as
described in NEC and your local/state electrical codes. All field wiring MUST be performed by
qualified personnel. Failure to follow these requirements could result in death or serious injury.
Communication Link Wiring Requirements
Use 18 AWG Trane purple-shielded communication wire for BACnet installations.
Link limit of 4,000 ft and 60 devices maximum (without a repeater).
Use a Trane BACnet termination on each end of the link.
Use daisy chain topology. See Figure 2, p. 15.
Maintain polarity.
Recommended Wiring Practices
To ensure proper network communication, follow these recommended wiring and planning
guidelines when installing communication wire:
All wiring must comply with the National Electrical Code (NEC) and local codes.
Make sure that 24 VAC power supplies are consistent in how they are grounded. Avoid sharing
24 VAC between controllers.
Avoid over tightening cable ties and other forms of cable wraps. This can damage the wires
inside the cable.
Do not run communication cable alongside or in the same conduit as 24 VAC power. This
includes the conductors running from TRIAC-type inputs.
In open plenums, avoid running wire near lighting ballasts, especially those using 277 VAC.
Use same communication wire type, without terminators, for the zone sensor communication
stubs from the Tracer UC400 controller IMC terminals to the zone sensor communication
module.
Note: For more information see wiring guide BAS-SVN03*-EN, Unit Controller Wiring for Tracer
SC™ System Controller.
Figure 2. BACnet link wiring in daisy chain configuration with Trane BACnet terminators and zone senor
communication stubs