Programming Guide

64 VAV-SVP01A-EN
VAV VV550 Controller Device Home Tabs: Instructions
Binary Output 5
This output can be configured for:
Parallel or series fan on/off control
Hot-water on/off control
Electric-heat staged or pulse width modulation
The output is automatically configured based on your answers in the Output Configuration Wizard.
Device Contacts Normally Open: Select this check box if the device contacts are normally open.
This check box is available only for hot-water on/off control.
Test Tab
Use the Test tab to exercise the binary outputs and verify that they are working correctly.
To perform a manual output test:
1. Click the Start button.
2. Click the Next Step button repeatedly to step through the test.
3. Click the Cancel button to stop the test.
Figure 47. Test tab