Product Catalog Water Source Heat Pump Axiom™ High Efficiency Vertical Stack — GET ¾–3Tons—60 Hz November 2013 WSHP-PRC020D-EN
Introduction Water-Source Vertical High-Rise The 3/4-ton through 3-ton vertical high-rise water-source heat pump is a floor mounted, “furredin” unit, designed to be hidden from view behind drywall to blend with the room’s natural decor. In multi-story buildings, the units may be stacked one on top of the other to minimize piping and electrical costs. Supply, return and condensate riser piping may be factory mounted to simplify job site installation of the equipment.
Table of Contents Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Water-Source Vertical High-Rise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Application Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Selection Procedures . . . . . . . . . .
Features and Benefits Unit Description The vertical high-rise water-source heat pump is a floor mounted configuration available in a ¾ ton, 1 ton, 1¼ ton, 1½ ton, 2 ton and 3 ton sizes. The unit cabinet may be ordered for early shipment to aid in early installation of drywall, plumbing and electrical. See “Model Number Descriptions,” p. 14.The cabinet design is available in either an 88-inch height (free discharge) or 80-inch height (ducted) configuration.
Features and Benefits Thermostat selections are provided in the “Thermostats and Zone Sensors,” p. 55 section of the catalog.They are available in manual or automatic changeover options. The deluxe controller includes relays for: anti-short cycle compressor protection, random start delay, brown-out protection low pressure time delay, compressor delay on start and night setback control.These extended control features offer greater system performance to extend the equipment’s life. Figure 2.
Features and Benefits is no cross leakage between the water tube and the refrigerant gas (steel tube) coil.The ½” (009/ 012/015/018) and ¾”(024/036) threaded water connections to the water-coil are available on the exterior chassis top. A flexible hose connection with shut-off is typically used between the riser and water-coil in/out connections on the chassis to reduce water vibration. The refrigerant flow metering is made through a thermal expansion valve (TXV).
Application Considerations Advantages of Geothermal The advantages of a geothermal heat pump system can literally decrease heating and cooling operating costs by 30%-40%.The units are durable, and typically last longer than conventional systems.They are protected from harsh outdoor weather conditions, because the unit is installed indoors and the loop underground. According to ASHRAE, the estimated service life for a commercial water-to-air heat pump is 19 years.
Application Considerations Figure 4. Installation illustration Equipment Installation The vertical high-rise unit is versatile in design to fit numerous applications. It is typically applied to dorm rooms, hotels and motels where multiple supply air configurations may be required for individual tenant heating and cooling.The equipment requires little space, and is tucked away from sight, and rough handling.The vertical stack design is economical to install, requiring no ductwork for air supply.
Application Considerations Equipment Risers The riser provides an easy way to facilitate the water flow through a multi-story building and the high-rise heat pump.The high-rise heat pump is best applied to a building with identical zones on each floor, and zones that are typically small. An example building might include a hotel, dorm, condominium or assisted living facility. With these types of buildings, the riser column (external to the unit cabinet) can be stacked one on top of the other.
Application Considerations Table 1. Riser characteristics (continued) Type M (standard) Riser Size (in.) I.D. (in.) O.D. (in.) Copper Wall Thickness (in.) 1½ 1.527 1.625 0.049 2 2.009 2.125 0.058 2½ 2.495 2.625 0.065 3 2.981 3.125 0.072 Note: Pressure ratings for risers are typically greater than the maximum pressure rating of the coaxial water-to-refrigerant heat exchangers.This is true with exception ofType M copper in a 3" diameter.
Application Considerations Riser Size Example Assume a six story building is served by a high-rise water-source heat pump. When referencing the catalog, determine each highrise heat pump uses 3 gallons per minute to meet the required capacity of the 1-ton unit. What is the minimum riser diameter that can be used on each floor? With this arrangement, determine the volume of water used at each floor is 3 GPM.The top floor riser therefore only needs to be sized for 3 GPM. Referring to Table 2, p.
Application Considerations Heat Rejection through a Closed Circuit Cooling Tower Cooling towers serve to reject heat from the condenser water loop to the atmosphere.Two types of cooling towers are used with water-source heat pump systems: open or closed-circuit.The towers themselves are different, but when an open tower is used in conjunction with a water-towater heat exchanger, the control of the two tower types is essentially the same.
Selection Procedures Model Number Two model number designators have been defined for the cabinet configuration, and the chassis configuration. Both model numbers require input for the order to be complete and built to specification. Typically the vertical stack equipment ships in two sections.
Model Number Descriptions Vertical High-Rise Cabinet WSHP Digits 1-3: Unit Configuration GET = High Efficiency Vertical High Rise Heat Pump Digit 4: Development Sequence E = R-410A Digits 5-7: Nominal Size (Tons) 009 = ¾Tons 012 = 1Tons 015 = 1¼Tons 018 = 1½Tons 024 = 2Tons 036 = 3Tons Digit 8: Voltage (Volts/Hz/Phase) 1 = 208/60/1 2 = 230/60/1 7 = 265/60/1 Digit 9: Heat Exchanger 1 = Copper Water Coil 2 = Cupro-Nickel Water Coil 3 = Copper Water Coil with Isolation Valve and Low Flow Control 4 = Cupr
Model Number Descriptions Digit 34, 35, 36: Riser Length Digit 11: Refrigeration Circuit Digit 20-22: Open Digits 000 = No Riser 096 = 96" Riser Length 097 = 97" Riser Length 098 = 98" Riser Length 099 = 99" Riser Length 100 = 100" Riser Length 101 = 101" Riser Length 102 = 102" Riser Length 103 = 103" Riser Length 104 = 104" Riser Length 105 = 105" Riser Length 106 = 106" Riser Length 107 = 107" Riser Length 108 = 108" Riser Length 109 = 109" Riser Length 110 = 110" Riser Length 111 = 111" Riser Length
General Data Table 3. General Data Model Number 009 012 015 018 024 036 Compressor Type Rotary Rotary Rotary Rotary Scroll Scroll Depth (in.) 16.0 16.0 18.0 18.0 24.0 24.0 Height (in.) 88.0 88.0 88.0 88.0 88.0 88.0 Width (in.) 16.0 16.0 20.0 20.0 24.0 24.0 Cabinet Size Depth (mm) 406.4 406.4 457.2 457.2 609.6 609.6 Height (mm) 2235.2 2235.2 2235.2 2235.2 2235.2 2235.2 Width (mm) 406.4 406.4 508.0 508.0 609.6 609.
Performance Data Table 4. AHRI-ISO performance Rated Rated Flow Air Cooling Rate Flow Capacity Unit Size (GPM) (CFM) (Mbtuh) Water Loop EER Ground Water Heating Cooling Capacity Capacity (Mbtuh) COP (Mbtuh) EER Ground Loop Heating Cooling Capacity Capacity (Mbtuh) COP (Mbtuh) EER Heating Capacity (Mbtuh) COP PSC Motor GET 009 2.1 340 8200 12.8 10800 4.6 9700 18.4 8700 3.8 8800 14.9 6600 3.2 GET 012 2.8 440 11900 13.5 14100 4.6 13100 18.9 11800 4.0 12300 15.1 9000 3.
Performance Data Table 5. 18 GET 009 cooling performance (continued) EWT GPM Total Gross (Mbtuh) Gross Sen (Mbtuh) SHR Heat of Rej (Mbtuh) Comp Pwr (kW) LWT WPD (feet head) 75 1.8 9.3 7.7 0.82 11.0 0.49 87.2 4.2 75 2.1 9.4 7.7 0.82 11.0 0.49 85.5 5.5 75 2.3 9.4 7.7 0.82 11.0 0.48 84.8 6.2 75 2.4 9.4 7.7 0.82 11.1 0.48 84.2 7.0 75 2.6 9.4 7.7 0.82 11.1 0.48 83.4 8.2 77 1.1 9.1 7.6 0.83 11.0 0.54 96.5 1.8 77 1.5 9.2 7.6 0.83 11.0 0.
Performance Data Table 5. GET 009 cooling performance (continued) EWT GPM Total Gross (Mbtuh) Gross Sen (Mbtuh) SHR Heat of Rej (Mbtuh) Comp Pwr (kW) LWT WPD (feet head) 120 2.3 8.0 7.2 0.91 10.9 0.86 129.7 5.3 120 2.4 7.9 7.2 0.91 10.9 0.86 129.0 6.0 120 2.6 7.9 7.2 0.91 10.8 0.85 128.3 7.0 Notes: Cooling performance data is tabulated at 80.6°F DB/66.2°F WB entering air at AHRI/ISO 13256-1 rated cfm.For AHRI/ISO 13256-1 certified ratings, see Table 4, p. 17.
Performance Data Table 6. GET 009 heating performance (continued) EWT GPM Total Gross (Mbtuh) Heat of Absorb (Mbtuh) Compr Power (kW) LWT WPD (feet head) 75 1.1 11.4 9.3 0.61 58.5 1.8 75 1.5 11.9 9.8 0.62 62.0 3.1 75 1.8 12.2 10.0 0.62 63.9 4.2 75 2.1 12.4 10.2 0.63 65.3 5.5 75 2.3 12.5 10.3 0.63 65.8 6.2 75 2.4 12.5 10.4 0.63 66.4 7.0 75 2.6 12.6 10.5 0.63 67.0 8.2 77 1.1 11.6 9.5 0.62 60.1 1.8 77 1.5 12.1 10.0 0.62 63.7 3.0 77 1.
Performance Data Table 7. GET 012 cooling performance (continued) EWT GPM Total Gross (Mbtuh) Gross Sen (Mbtuh) SHR Heat of Rej (Mbtuh) Comp Pwr (kW) LWT WPD (feet head) 68 2.8 12.8 10.1 0.79 14.7 0.56 78.5 13.4 68 3.0 12.8 10.1 0.79 14.7 0.56 77.8 15.1 68 3.2 12.8 10.1 0.79 14.7 0.55 77.2 16.9 68 3.5 12.8 10.1 0.79 14.7 0.55 76.4 19.8 75 1.5 12.5 10.0 0.80 14.8 0.68 94.8 4.4 75 2.0 12.6 10.0 0.80 14.8 0.64 89.8 7.3 75 2.4 12.6 10.0 0.
Performance Data Table 7. GET 012 cooling performance (continued) EWT GPM Total Gross (Mbtuh) Gross Sen (Mbtuh) SHR Heat of Rej (Mbtuh) Comp Pwr (kW) LWT WPD (feet head) 115 3.2 10.9 9.3 0.86 14.5 1.06 124.1 13.4 115 3.5 10.9 9.3 0.86 14.5 1.05 123.3 15.8 120 1.5 10.6 9.2 0.87 14.8 1.23 139.8 3.8 120 2.0 10.6 9.2 0.87 14.7 1.19 134.7 5.9 120 2.4 10.6 9.2 0.87 14.6 1.16 132.2 8.0 120 2.8 10.6 9.2 0.87 14.5 1.14 130.4 10.5 120 3.0 10.6 9.
Performance Data Table 8. GET 012 heating performance (continued) Total Gross (Mbtuh) Heat of Absorb (Mbtuh) Compr Power (kW) LWT WPD (feet head) EWT GPM 68 2.0 13.4 10.9 0.75 57.1 7.4 68 2.4 13.7 11.1 0.75 58.7 10.2 68 2.8 13.9 11.3 0.75 59.9 13.4 68 3.0 14.0 11.4 0.75 60.4 15.1 68 3.2 14.0 11.5 0.76 60.8 16.9 68 3.5 14.1 11.6 0.76 61.4 19.8 75 1.5 13.9 11.3 0.75 59.9 4.4 75 2.0 14.4 11.8 0.76 63.2 7.3 75 2.4 14.7 12.1 0.76 65.0 10.
Performance Data Table 9. 24 GET 015 cooling performance (continued) EWT GPM Total Gross (Mbtuh) Gross Sen (Mbtuh) SHR Heat of Rej (Mbtuh) Comp Pwr (kW) LWT WPD (feet head) 55 3.8 16.8 14.0 0.83 18.5 0.50 64.8 15.3 55 4.1 16.8 14.0 0.83 18.5 0.50 64.0 17.5 55 4.4 16.8 14.0 0.83 18.5 0.49 63.5 19.6 68 1.9 16.3 13.8 0.85 18.9 0.76 88.2 4.2 68 2.3 16.4 13.8 0.85 18.8 0.72 84.4 6.1 68 2.8 16.4 13.8 0.84 18.8 0.69 81.4 8.6 68 3.5 16.4 13.9 0.
Performance Data Table 9. GET 015 cooling performance (continued) EWT GPM Total Gross (Mbtuh) Gross Sen (Mbtuh) SHR Heat of Rej (Mbtuh) Comp Pwr (kW) LWT WPD (feet head) 105 4.4 14.6 13.2 0.91 18.5 1.16 113.5 16.1 115 1.9 14.1 13.1 0.93 19.4 1.54 135.7 3.5 115 2.3 14.1 13.0 0.93 19.1 1.48 131.6 5.0 115 2.8 14.0 13.0 0.93 19.0 1.44 128.5 7.1 115 3.5 14.0 13.0 0.93 18.8 1.40 125.7 10.6 115 3.8 14.0 13.0 0.93 18.8 1.39 124.9 12.2 115 4.1 14.
Performance Data Table 10. GET 015 heating performance (continued) Total Gross (Mbtuh) Heat of Absorb (Mbtuh) Compr Power (kW) WPD (feet head) EWT GPM LWT 55 2.8 14.8 11.8 0.90 46.6 9.0 55 3.5 15.1 12.1 0.90 48.1 13.3 55 3.8 15.2 12.2 0.90 48.6 15.3 55 4.1 15.3 12.2 0.90 49.0 17.5 55 4.4 15.4 12.3 0.90 49.4 19.6 68 1.9 16.3 13.2 0.91 54.0 4.2 68 2.3 16.7 13.6 0.90 56.2 6.1 68 2.8 17.1 14.0 0.91 58.0 8.6 68 3.5 17.4 14.4 0.91 59.8 12.
Performance Data Table 11. GET 018 cooling performance (continued) EWT GPM Total Gross (Mbtuh) Gross Sen (Mbtuh) SHR Heat of Rej (Mbtuh) Comp Pwr (kW) LWT WPD (feet head) 45 5.0 19.6 15.6 0.80 21.6 0.60 53.6 15.5 45 5.3 19.6 15.7 0.80 21.6 0.60 53.2 16.9 55 2.3 20.0 15.9 0.79 22.9 0.84 75.3 3.7 55 2.9 20.0 15.8 0.79 22.7 0.79 70.6 5.7 55 3.6 19.9 15.8 0.79 22.5 0.76 67.5 8.4 55 4.2 19.9 15.8 0.79 22.4 0.74 65.7 11.0 55 4.6 19.9 15.8 0.
Performance Data Table 11. GET 018 cooling performance (continued) EWT GPM Total Gross (Mbtuh) Gross Sen (Mbtuh) SHR Heat of Rej (Mbtuh) Comp Pwr (kW) LWT WPD (feet head) 105 2.3 17.2 14.9 0.86 22.7 1.60 125.2 2.9 105 2.9 17.2 14.9 0.86 22.5 1.54 120.5 4.6 105 3.6 17.3 14.9 0.86 22.4 1.50 117.4 6.8 105 4.2 17.3 14.9 0.86 22.3 1.47 115.6 8.9 105 4.6 17.3 14.9 0.86 22.3 1.46 114.7 10.4 105 5.0 17.3 14.9 0.86 22.2 1.45 113.9 12.1 105 5.3 17.
Performance Data Table 12. GET 018 heating performance (continued) Total Gross (Mbtuh) Heat of Absorb (Mbtuh) Compr Power (kW) LWT WPD (feet head) EWT GPM 45 3.6 17.2 13.3 1.13 37.6 8.7 45 4.2 17.4 13.6 1.13 38.5 11.4 45 4.6 17.6 13.7 1.14 39.1 13.4 45 5.0 17.7 13.8 1.14 39.5 15.5 45 5.3 17.7 13.9 1.14 39.7 16.9 55 2.3 18.5 14.5 1.16 42.1 3.7 55 2.9 19.1 15.1 1.17 44.6 5.7 55 3.6 19.6 15.6 1.18 46.4 8.4 55 4.2 19.9 15.8 1.18 47.5 11.
Performance Data Table 13. GET 024 cooling performance 30 EWT GPM Total Gross (Mbtuh) Gross Sen (Mbtuh) SHR Heat of Rej (Mbtuh) Comp Pwr (kW) LWT WPD (feet head) 45 3.0 27.4 20.9 0.76 30.3 0.84 65.2 3.4 45 3.9 27.8 21.0 0.76 30.4 0.77 60.6 5.5 45 4.7 28.0 21.1 0.75 30.5 0.73 58.0 7.6 45 5.6 28.2 21.1 0.75 30.6 0.70 55.9 10.3 45 6.1 28.3 21.2 0.75 30.6 0.69 55.0 12.0 45 6.5 28.4 21.2 0.75 30.7 0.68 54.4 13.4 45 7.0 28.3 21.2 0.75 30.6 0.
Performance Data Table 13. GET 024 cooling performance (continued) EWT GPM Total Gross (Mbtuh) Gross Sen (Mbtuh) SHR Heat of Rej (Mbtuh) Comp Pwr (kW) LWT WPD (feet head) 95 3.9 23.3 19.3 0.83 29.1 1.70 109.9 4.3 95 4.7 23.4 19.3 0.82 29.1 1.66 107.4 6.0 95 5.6 23.5 19.3 0.82 29.1 1.63 105.4 8.2 95 6.1 23.6 19.3 0.82 29.1 1.61 104.5 9.5 95 6.5 23.6 19.4 0.82 29.1 1.60 103.9 10.6 95 7.0 23.6 19.4 0.82 29.1 1.59 103.3 12.1 105 3.0 21.9 18.
Performance Data Table 14. GET 024 heating performance (continued) 32 EWT GPM Total Gross (Mbtuh) Heat of Absorb (Mbtuh) Compr Power (kW) LWT WPD (feet head) 32 6.1 17.7 13.2 1.33 27.7 15.7 32 6.5 17.8 13.3 1.33 27.9 17.5 32 7.0 17.9 13.3 1.33 28.2 20.0 45 3.0 19.9 15.3 1.35 34.8 3.4 45 3.9 20.6 15.9 1.36 36.8 5.5 45 4.7 20.9 16.3 1.36 38.1 7.6 45 5.6 21.3 16.6 1.37 39.1 10.3 45 6.1 21.4 16.8 1.37 39.5 12.0 45 6.5 21.5 16.8 1.37 39.
Performance Data Table 14. GET 024 heating performance (continued) EWT GPM Total Gross (Mbtuh) Heat of Absorb (Mbtuh) Compr Power (kW) LWT WPD (feet head) 86 7.0 33.3 27.9 1.57 78.0 13.2 Notes: Heating performance data is tabulated at 68°F DB entering air at AHRI/ISO 13256-1 rated cfm. See Performance correction tables to correct performance at conditions other than those tabulated. Interpolation of data is permissible, extrapolation is not. Rated GPM 5.
Performance Data Table 15. GET 036 cooling performance (continued) EWT GPM Total Gross (Mbtuh) Gross Sen (Mbtuh) SHR Heat of Rej (Mbtuh) Comp Pwr (kW) LWT WPD (feet head) 86 7.1 36.5 29.4 0.80 43.5 2.05 98.3 10.8 86 8.4 36.6 29.5 0.80 43.5 2.01 96.4 14.5 86 9.1 36.7 29.5 0.80 43.5 1.99 95.5 16.7 86 9.8 36.7 29.6 0.81 43.5 1.98 94.9 19.0 86 10.5 36.7 29.5 0.80 43.5 1.97 94.3 21.4 95 4.5 34.7 28.8 0.83 43.1 2.46 114.2 4.5 95 5.8 34.9 28.9 0.
Performance Data Table 16. GET 036 heating performance (continued) EWT GPM Total Gross (Mbtuh) Heat of Absorb (Mbtuh) Compr Power (kW) LWT WPD (feet head) 25 9.1 24.6 18.1 1.90 21.0 25.8 25 9.8 24.7 18.2 1.90 21.3 29.4 25 10.5 24.8 18.3 1.90 21.5 33.2 32 4.5 25.7 19.1 1.92 23.5 7.4 32 5.8 26.4 19.8 1.93 25.2 11.5 32 7.1 26.8 20.2 1.93 26.3 16.3 32 8.4 27.0 20.5 1.92 27.1 21.8 32 9.1 27.2 20.6 1.92 27.5 25.1 32 9.8 27.3 20.7 1.92 27.8 28.
Performance Data Table 16. GET 036 heating performance (continued) EWT GPM Total Gross (Mbtuh) Heat of Absorb (Mbtuh) Compr Power (kW) LWT WPD (feet head) 77 10.5 46.6 39.0 2.20 69.6 22.0 86 4.5 47.7 39.9 2.27 68.3 4.9 86 5.8 49.1 41.3 2.29 71.8 7.6 86 7.1 49.9 42.1 2.30 74.2 10.8 86 8.4 50.3 42.5 2.30 75.9 14.5 86 9.1 50.5 42.6 2.30 76.6 16.7 86 9.8 50.6 42.7 2.30 77.3 19.0 86 10.5 50.6 42.8 2.30 77.9 21.
Performance Data Table 18. Correction factors for variation in air flow (continued) Model Entering CFM Cooling Capacity Sensible Capacity Cooling Input Watts Heating Capacity Heating Input Watts GET 015 432 0.961 0.865 1.010 0.975 1.082 GET 015 459 0.972 0.899 1.007 0.982 1.057 GET 015 486 0.982 0.933 1.006 0.989 1.036 GET 015 513 0.990 0.968 1.003 0.995 1.017 GET 015 540 1.000 1.000 1.000 1.000 1.000 GET 015 567 1.008 1.034 0.997 1.005 0.
Unit Fan Performance Table 19. PSC blower motor external static pressure without return air door (RAD) with filter External Static Pressure (in. of wg) CFM 0.00 Model Speed Ducted (a) Unit No Tap Max Min CFM KW GET 009 GET 012 GET 015 GET 018 GET 024 GET 036 High Low High Low High Low High Low High Low High Low High Low High Low High Low High Low High Low High Low Yes Yes No No Yes Yes No No Yes Yes No No Yes Yes No No Yes Yes No No Yes Yes No No 408 304 421 355 357 307 453 401 418 345 0.108 0.
Unit Fan Performance Table 20. ECM Blower motor external static pressure without return air door (RAD) with filter External Static Pressure (in. of wg) Model Speed No. Profile CFM A GET 009 GET 012 GET 015 GET 018 GET 024 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.55 0.60 0.65 kW kW kW kW kW kW kW kW kW kW kW kW kW kW 0.70 kW 0.025 0.037 0.050 0.062 0.075 0.087 0.098 0.110 0.121 0.133 0.144 0.155 0.165 0.176 0.176 B 344 0.023 0.035 0.046 0.
Unit Fan Performance Table 21. Pressure drop due to return air door (RAD) Model No. CFM DP CFM DP CFM DP GET 009 272 0.04 340 0.05 408 0.08 GET 012 303 0.04 380 0.07 456 0.11 GET 015 432 0.06 540 0.09 648 0.12 GET 018 520 0.08 650 0.12 780 0.16 GET 024 656 0.06 820 0.08 984 0.12 GET 036 936 0.10 1170 0.16 1404 0.23 Note: The pressure drop across the RAD door should be included in the TOTAL ESP when determining airflow and fan motor power usage.
Unit Fan Performance Figure 6. Cooling capacity correction factor Figure 7. Heating capacity correction factor Figure 8. Water pressure drop correction factor Example 1 (Ethylene Glycol): The antifreeze solution is 20% by volume of Ethylene Glycol. Determine the corrected cooling capacity and waterside pressure drop for a GET009 when the EWT is 86°F and the GPM is 2.3. From the catalog data, the cooling capacity at these conditions with 100% water is 8.3 Mbtuh, and the waterside pressure drop is 9.
Electrical Data Table 23. Electrical performance Model No. Motor Option PSC Motor GET 009 ECM Motor PSC Motor GET 012 ECM Motor PSC Motor GET 015 ECM Motor Free Discharge PSC Motor GET 018 ECM Motor Ducted PSC Motor PSC Motor GET 024 ECM Motor PSC Motor GET 036 ECM Motor 42 Maximum Overcurrent Protective Device Unit Volts Total FLA Comp RLA (ea) Comp LRA Blower Motor FLA Blower Motor HP Minimum Circuit Ampacity 208/60/1 4.3 3.7 16.0 0.60 1/20 5.23 15 230/60/1 4.1 3.5 17.0 0.
Dimensional Data Figure 9. Unit cabinet/riser 12 1/2" (318) 8" (203) S D 12 1/2" (318) 8" (203) 3 3/4" (95) 3 3/4" (95) R VARIES DEPENDENT ON RISER O.D. RETURN 1" (25.4) 1" (25.4) OPTIONAL DUCT OPENING 1" (12.7) DUCT COLLAR SUPPLY G 11" (279) FOR 80" (2032) CABINET HEIGHT 3" (76) FOR 88" (2235) CABINET HEIGHT H SUPPLY-AIR OPENINGS AND RISER LOCATIONS CANNOT BE ON THE SAME SIDE OF THE UNIT. DRAIN 1/2" (12.7) O.D. ELECTRIC CONDUIT 1" (25.
Dimensional Data Figure 10. Unit cabinet/riser 8" (203) 3 3/4" (95) A 12 1/2" (318) B N R TU PP SU LY AI DR N 1 1/2" (38) RE 1/2" (12.7) O.D. FACTORY ELECTRIC CONDUIT 7/8" (22 mm) O.D. FOR FIELD ELECTRIC CONDUIT 1" (24.4) WATER OUT 1/2" (13) NPTI = GET 009-018 3/4" (19) NPTI = GET 024-036 TOP DISCHARGE UNITS = 80" (2032) FRONT, SIDE, COMBINATION = 88" (2235) LOW VOLTAGE CONNECTION BOX FOR UNIT MTD THERMOSTAT C K 60" (1524) D J 4 3/4" (121) E H F G NOTE: REAR RISER LOCATION SHOWN.
Dimensional Data Water Flow Control The factory installed water flow control option is hard piped to the copper or cupro-nickel water coil.The selection is available in a high or low flow option. An isolation valve and strainer are standard when the factory flow device is selected. Two foot hose and ball valves are recommended for these units.The hoses and ball valves are optional and can be selected with the chassis portion of the order, or can be field provided.
Dimensional Data Figure 11. Riser to unit connection RISER ARRANGEMENTS SYSTEM SUPPLY IS FROM THE BOTTOM. - ALL RISERS ARE CAPPED AT THE CABINET RUN OUTS. SYSTEM SUPPLY IS FROM THE TOP OR BOTTOM. - DRAIN RISER IS CAPPED AT THE CABINET RUN OUT. - BOTTOM SUPPLY AND RETURN RISERS ARE PIPED WITH OPEN TOP FOR VENTING OR FLUSHING. 32" (813) 2 1/2" (64) - TOP SUPPLY AND RETURN RISERS. SYSTEM SUPPLY IS FROM THE TOP OR BOTTOM.
Dimensional Data Figure 12.
Dimensional Data Figure 13. Riser extensions 3" (76) SWAGE 3" (76) SWAGE 11" (279) 88" (2235) 80" (2032) 120" (3048) 120" (3048) 4" (102) 4" (102) 29" (330) 29" (737) 24" (610) 3" (76) SWAGE 2" (51) OVERLAP 11" (279) 3" (76) SWAGE 2" (51) OVERLAP 24" (610) 136" (3454) 136" (3454) 88" (2235) 80" (2032) 120" (3048) 120" (3048) 29" (737) 80" UNIT HEIGHT FOR TOP SUPPLY-AIR 29" (737) 88" UNIT HEIGHT FOR FRONT, BACK, SIDE SUPPLY-AIR Riser Extensions are field provided and installed.
Dimensional Data Figure 14. Hinged acoustical door 3 1/2” ±3/8” 2“ X 4” STUD 1 1/4” +1/2”/-0” SHEETROCK A CABINET 1“ X 1” CLOSED CELL INSULATION RETURN AIR OPENING FLANGE ON CABINET SHEET ROCK OPENING SHEETROCK A 2“ X 4” STUD Note: Finished wall and framing should not touch the unit cabinetry.
Dimensional Data Table 27. Return air hinged acoustical door Unit Size A B 009 012 19¼” (489) 44 1/8” (1121) 015 018 23¼” (591) 45¼” (1149) 024 036 27 1/8” (689) 54 5/8” (1387) Return Air (hinged) Acoustical Door The hinged acoustical door is recessed into the wall so that the door is flush with the surface of the wall. The opening through the wall for the door assembly must be centered with the return-air opening of the unit cabinet.
Controls Deluxe 24V Electronic Controls The 24V deluxe design is a microprocessor-based control board conveniently located in the control box.The board is unique toTrane water-source products and is designed to control the unit as well as provide outputs for unit status and fault detection. The board is factory wired to a terminal strip to provide all necessary terminals for field connections.
Controls In a high pressure situation, the compressor contactor is de-energized, which suspends compressor operation.The control will go into soft lockout mode initializing a three minute time delay and a random start of 3 to 10 second time delays. Once these delays have expired, the unit will be allowed to run. If a high pressure situation occurs within one hour of the first situation, the control will be placed into a manual lockout mode, halting compressor operation, and initiating the general alarm.
Controls and filter status, reversing valve coil, two-speed fan motor and water isolation valve support (for variable speed pumping). Note: Optional: condensate overflow Tracer ZN510 functions include: Building Control Advantages TheTracer ZN510 controller has the ability to share information with one or several units on the same communication link.This sharing of information is made possible via a twisted pair of wire and a building automation system or throughTrane's Rover™ service tool.
Controls High and Low Pressure Safety Controls TheTracer ZN510 controller detects the state of the high pressure or low pressure switches. When a fault is sensed by one of these switches, the corresponding message is sent to the controller to be logged into the fault log. When the circuit returns to normal, the high pressure control and low pressure control automatically reset. If a second fault is detected within a thirty-minute time span, the unit must be manually reset.
Thermostats and Zone Sensors Table 29.
Accessories System balancing hose kit For automatic system balancing of a water source heat pump, the Mesurflo® self-balancing hose kit provides a constant flow rate over the pressure differential rage of 2 to 80 psid. As system pressure changes (through further addition of heat pumps, for example) each individual flow control valve will automatically adjust to the new system conditions.
Mechanical Specifications General Equipment is factory assembled, piped, internally wired, fully charged with R-410A refrigerant and oil. Units are tested at the factory. Products are certified in accordance with AHRIWater to Air and Brine to Air Heat Pump Certification Program which is based ISO Standard 13256-1: 1998. All units have an ETL label that meets USA (UL std) and Canadian (CSA std). Casing The cabinet assembly is constructed of heavy-gauge galvanized steel.
Mechanical Specifications Drain Pan The condensate pan is constructed of corrosive resistant material.The bottom of the drain pan is sloped in two planes to pitch the condensate towards the drain connection. Condensate is piped to a lower base pan through condensate hose for ease of chassis removal. A clear drain hose is factory clamped onto the drain connection for field hook-up.
Mechanical Specifications Deluxe Controls (option) The deluxe control package provides a 75VA transformer with circuit breaker.The Micro-processor based controller is designed to include a lockout relay, anti-short cycle compressor protection, random start delay, brown-out protection, low pressure time delay, compressor delay on start and an open relay for night setback or pump request. Optional wiring from the factory for condensate overflow and compressor enable are also supplied.
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com. Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.