Catalogue

26 WSHP-PRC020D-EN
Performance Data
55 2.8 14.8 11.8 0.90 46.6 9.0
55 3.5 15.1 12.1 0.90 48.1 13.3
55 3.8 15.2 12.2 0.90 48.6 15.3
55 4.1 15.3 12.2 0.90 49.0 17.5
55 4.4 15.4 12.3 0.90 49.4 19.6
68 1.9 16.3 13.2 0.91 54.0 4.2
68 2.3 16.7 13.6 0.90 56.2 6.1
68 2.8 17.1 14.0 0.91 58.0 8.6
68 3.5 17.4 14.4 0.91 59.8 12.7
68 3.8 17.6 14.5 0.91 60.4 14.6
68 4.1 17.7 14.6 0.91 60.9 16.7
68 4.4 17.8 14.7 0.91 61.3 18.7
75 1.9 17.4 14.3 0.91 59.7 4.1
75 2.3 17.9 14.8 0.91 62.1 5.9
75 2.8 18.3 15.2 0.91 64.1 8.4
75 3.5 18.7 15.6 0.91 66.1 12.4
75 3.8 18.9 15.8 0.91 66.7 14.3
75 4.1 19.0 15.9 0.91 67.3 16.3
75 4.4 19.1 16.0 0.91 67.7 18.3
77 1.9 17.7 14.6 0.91 61.4 4.1
77 2.3 18.3 15.2 0.91 63.8 5.9
77 2.8 18.7 15.6 0.91 65.9 8.3
77 3.5 19.1 16.0 0.91 67.9 12.3
77 3.8 19.2 16.1 0.91 68.5 14.2
77 4.1 19.4 16.3 0.91 69.1 16.2
77 4.4 19.5 16.4 0.91 69.5 18.1
86 1.9 19.3 16.2 0.91 68.8 4.0
86 2.3 19.8 16.7 0.91 71.4 5.7
86 2.8 20.3 17.2 0.91 73.7 8.1
86 3.5 20.8 17.7 0.90 75.9 11.9
86 3.8 20.9 17.9 0.90 76.6 13.8
86 4.1 21.1 18.1 0.90 77.2 15.7
86 4.4 21.2 18.1 0.90 77.7 17.6
Notes: Heating performance data is tabulated at 68°F DB entering air at AHRI/ISO 13256-1 rated cfm. See Performance correction tables to correct
performance at conditions other than those tabulated. Interpolation of data is permissible, extrapolation is not. Rated GPM 3.5; Minimum cfm
432; Rated cfm 540; Maximum cfm 648.
Table 11. GET 018 cooling performance
EWT GPM
Total Gross
(Mbtuh)
Gross Sen
(Mbtuh) SHR
Heat of Rej
(Mbtuh)
Comp Pwr
(kW) LWT
WPD
(feet head)
45 2.3 20.1 15.9 0.79 22.5 0.72 65.0 3.8
45 2.9 19.9 15.8 0.79 22.2 0.67 60.3 6.0
45 3.6 19.8 15.8 0.80 22.0 0.64 57.2 8.7
45 4.2 19.7 15.8 0.80 21.8 0.62 55.4 11.4
45 4.6 19.7 15.7 0.80 21.8 0.61 54.5 13.4
Table 10. GET 015 heating performance (continued)
EWT GPM
Total Gross
(Mbtuh)
Heat of Absorb
(Mbtuh)
Compr Power
(kW) LWT
WPD
(feet head)