Catalogue
WSHP-PRC020D-EN 45
Dimensional Data
Water Flow Control
The factory installed water flow control option is hard piped to
the copper or cupro-nickel water coil.The selection is
available in a high or low flow option. An isolation valve and
strainer are standard when the factory flow device is selected.
Two foot hose and ball valves are recommended for these
units.The hoses and ball valves are optional and can be
selected with the chassis portion of the order, or can be field
provided.These items are shipped separate from the chassis.
Table 26. Factory hose kit flow options
Unit Size
Low Flow
Digit 9 = 3,4
High Flow
Digit 9 = 5,6
009 1.5 GPM 2.0 GPM
012 2.0 GPM 2.5 GPM
015 2.5 GPM 3.5 GPM
018 3.0 GPM 4.0 GPM
024 4.0 GPM 6.0 GPM
036 6.0 GPM 8.0 GPM
Water In
Strainer
Isolation Valve
Water Out
Flow
Control