3. Locate dimensions A and B for sheet rock opening size.
The position of the sheet rock opening must be
centered side-to-side with the return-air opening in the
cabinet. Ensure the bottom of the sheet rock opening is
2¼” below the return-air opening in the cabinet.This
allows the door recess to rest on the bottom of the
sheet rock opening for proper vertical placement of the
door.
4. Place the door frame into the sheet rock opening. A
positive seal is critical between the back of the door
frame and the front of the cabinet. Ensure that the
gasket material seals properly.
Note: When placing the sheet rock panel, make certain
the opening for the door is centered with the
return-air opening in the cabinet (±1/8").
8. Install Filter.
9. Vacuum all dust and construction debris from unit after
cutting out supply/return openings.
Supply Air Ductwork
A 2" (50.8 mm) duct flange may be required to help
eliminate supply air from recirculating back into the return
air, air-to-refrigerant coil prior to discharging into the
space.
Equipment containing a top discharge, ducted design:
install field ductwork to the unit providing a water tight
flexible connector at the unit.This helps prevent operating
sounds from transmitting through the ductwork. Elbows
with turning vanes or splitters are recommended to
minimize air noise due to turbulence and to help reduce
static pressure.
Figure 7. Drywall installation for hinged acoustic door
Table 4. Sheet rock opening size
Unit Size A B
09
012
19¼”
(489)
44 1/8”
(1121)
015
018
23¼”
(591)
45¼”
(1149)
024
036
27 1/8”
(689)
54 5/8”
(1387)
RETURN-AIR OPENING
FLANGE ON CABINET
RETURN-AIR OPENING
FLANGE ON CABINET
2 X 4 STUD
A
B
SHEET ROCK
OPENING
TOP VIEW
SIDE VIEW
CABINET
5“
B
4 5/8“
2 1/4“
3 1/2” ±3/8”
3 1/2” ±3/8”
1 1/2” X 2 3/8”
FLOOR
SHEETROCK
SHEETROCK
RETURN AIR
DOOR FRAME
RETURN AIR
DOOR FRAME
1“ X 1” CLOSED
CELL INSULATION
1“ X 1” CLOSED
CELL INSULATION
ROC
K
3 1/2” ±3/8”
1 1/4”
+1/2”/-0”
1 1/4”
+1/2”/-0”
A
1“ X 1” CLOSED
CELL INSULATION
1“ X 1” CLOSED
CELL INSULATION
2“ X 4”
STUD
2“ X 4” STUD
RETURN AIR OPENING
FLANGE ON CABINET
RETURN AIR OPENING
FLANGE ON CABINET
SHEETROCK
SHEETROCK
RETURN AIR
DOOR FLANGE
CABINET
CABINET
Note:
Finished wall and framing should not
touch the unit cabinetry.
Figure 8. Door opening
5. Secure the door frame to the side
studs using the holes located in
the door frame and field provided
screws.
Note: If the gap between the door
frame, and the side stud is
over 1/16-inch, place a shim in
between the door frame and
the stud to prevent the door
frame from bending/denting.
Figure 9. Air panel gasket
6. Place the air panel into the door
opening.The gasket on the back
side of the air panel should seal
around the coil perimeter.
Figure 10. Secure to door frame
7. After verifying that the air panel
gasket is sealed to the coil, secure
the air panel to the door frame
using the slots located on the sides
of the air panel.