The CO2 sensor is designed to
operate with a nominal 24 Vac
supply. The power supply should
maintain the voltage between 20 to
26 Vac.
Table 41 - CO
2
sensor wire size
Wire size
(mm²)
Maximum 
wire lengh
(m)
0,25 50
0,5 100
1200
Table 40 - Specifications
Wall-mounted Duct-mounted 
Measuring range CO
2 0-2000 ppm 
Accuracy at 25°C 
< +/- [40 ppm CO
2 + 3% of 
reading] 
(included repeatability and 
calibration uncertainty) 
< +/- [30 ppm CO2 + 2% of 
reading] 
(included repeatability and 
calibration uncertainty) 
Non-linearity  < 1.0% full scale 
Temperature dependence of output  0.3% full scale/°C 
Long-term stability  < 5.0% full scale/ 5 years
Recommended calibration interval  5 years 
Response time  1 minute (0-63%) 
Operating temperature  15-35°C  -5-45°C 
Storage temperature  -20-70°C 
Humidity range  0-85% relative humidity 
Airflow range  0-10 m/s) 
Output signals (jumper selectable)  0-10 Vdc 
Resolution of analog outputs  10 ppm CO
2
Recommended external load 
Current output: max 500 
Voltage output: min. 1000 
Power supply  Nominal 24 Vac 
Power consumption  < 5 VA 
Warm-up time  < 15 minutes
Dimensions (mm)  108 x 80 x 36  80 x 80 x 200 
CO2 sensors
Wall-mounted and duct-mounted
CO
2 sensors
Power supply requirements
CAUTION! Make sure that you
connect the power wire only to the
24V terminal. Connecting the power
wire to the output terminal may
result in equipment damage.