TB/TI Thermistor Insertion Temperature Sensor Installation Instructions TG200727 Issue 1/E 11/07/07
5
Installation Instructions TB/TI
Installation (continued)
Remove Lid
5
Insert Cable
6
either use M20 flexible conduit
or use M16 cable gland
Wire to Controller
7
Replace Lid
8
Sensor
IQ1xx/2xx
COM (0V)
IN
polarity
independent
Analogue input
channel linked for
thermistor (T)
terminate screen at
IQ end only
T
terminal size 0.5 to 2.5 mm
2
(14 to 20 AWG)
TP/1/1/22/HP/200 (Belden 8761) cable recommended
Note that IP67 (NEMA6) rating is only
achieved if the sensor is correctly installed
with cable or conduit connection fully
tightened.
Sensor
IQ3
0 (0V)
N (in)
+ (24 V)