TB/TI Thermistor Insertion Temperature Sensor Installation Instructions TG200727 Issue 1/E 11/07/07
6
Installation (continued)
Configure IQ
9
I Q
IQ Configuration
Manual 90-1533
I Q
or
Set up IQ Sensor Type
10
Thermistor (-30 °C to +110 °C, -22 °F to +230 °F)
It is recommended to use SET (software tool) for the setting of the sensor type module. For all
IQ2 series controllers with firmware version 2.1 or greater, or IQ3 series controllers, the following
SET Unique Sensor References should be used:
Thermistor: Thermistor TBTI (-30 °C to +110 °C)
Thermistor TBTI F (-22 °F to +230 °F)
Alternatively set scaling mode to 5 (characterise) and enter scaling manually as defined in the
table below. Note that for IQ3, scaling mode and exponent do not need to be set up.
For all other IQ controllers see Sensor Scaling Reference Card TB100521A.