User's Guide
Table Of Contents
- TK-RP08
- The TK-RP08 allows its user to upgrade firmware contents whenever is needed to enhance its functionality and/or performance. With the firmware upgrade feature, your investment on the unit is further ensured and its life-time value just maximized. You don’t have to buy a newer unit just to have better features, instead you can have them all added to your current unit with an easy flash upgrade! The correct Flash upgrade procedure is described below. Please follow the instructions to complete your firmware upgrade.
- The TK-RP08 can be used as a power control accessory for TK-IP101 Swtich, or any other KVM Switch that supports a standard serial power control.
- Before you connect the TK-RP08 to the TK-IP101, you might need to install them first into their own proper placements within a rack, that is , if you are going to use them within a rack. After you have installed the TK-RP08, TK-IP101 into the rack, or into their proper locations, you can now proceed with following steps for further connections.
14
ON – Power ON
[Description]Power on one/all AC outlet port(s) immediately
[Usage] ON [bank_number] [port_number]
[Examples]
ON 1 4 – Power on port 4 on bank 1 immediately
ON 1 0 – Power on all ports on bank 1 immediately
ON 0 0 – Power on all ports on all cascaded banks immediately
Notes:
1. A port number of 0 represents all ports; while a bank number of 0 represents all
cascaded banks.
2. The command: ON 0 x ………, x = 1~9, is not valid.
OF – Power OFF
[Description]Power off one/all AC outlet port(s) immediately
[Usage] OF [bank_number] [port_number]
[Examples]
OF 1 4 – Power off bank 1 port 4 immediately
OF 1 0 – Power off bank 1 all ports immediately
OF 0 0 – Power off all ports on all cascaded banks immediately
Notes:
1. A port number of 0 represents all ports; while a bank number of 0 represents all
cascaded banks.
2. The command: OF 0 x ………, x = 1~9, is not valid.
TA – Timer Activate at specific time point
[Description]Set the timer to turn on/off a specific port at specific time
[Usage] TA [bank_number] [port_number] [ON | OF] [Time_point]
[Examples]
TA 1 4 ON 01:22:50 – Set timer to power on port 4 on bank 1 exactly
at 01:22:50.
TA 1 0 ON 00:10:00 – Set timer to power on all ports on bank 1 exactly
at 00:10:00
TA 0 0 OF 01:00:00 – Set timer to power off all ports on all cascaded
banks at 01:00:00
Notes:
1. A port number of 0 represents all ports; while a bank number of 0 represents all
cascaded banks.
2. The command: TA 0 0x ………, x = 1~9, is not valid.
3. The system time should be calibrated before use for the first time.
TF – Timer Activate after specific time duration
[Description]Set the timer to turn on/off a specific port after specific time duration
[Usage] TF [bank_number] [port_number] [ON | OF] [Time_duration]
[Examples]
TF 1 4 ON 03:25:56 – Set timer to power on port 4 on bank 1 exactly
after 3 hour 25 minutes and 56 seconds.
TF 1 0 ON 00:10:00 – Set timer to power on all ports on bank 1 exactly
after 10 minutes
TF 0 0 OF 01:00:00 – Set timer to power off all ports on all cascaded
banks after 1 hour.
Notes:
1. A port number of 0 represents all ports; while a bank number of 0 represents all
cascaded banks.
2. The command: TF 0 0x ………, x = 1~9, is not valid.