Install Instructions

28
External Wiring
SECTION VIII- External Wiring
Installation Compliance
All field wiring made during installation must
comply with:
- National Electrical Code NFPA 70 and
any other national, state, provincial or
local codes or requirements.
- In Canada, CSA C22.1 Canadian
Electrical Code Part 1, and any other
local codes.
ELECTRICAL SHOCK HAZARD.
Before making any electrical connec-
tions to the CHALLENGER, disconnect
electrical power supply at the service
panel. Failure to comply can cause
severe personal injury or death.
Line Voltage Connections
1. Connect a 120 VAC/15A service to the
120V terminals L, N and G inside the
CHALLENGER as shown in Fig. 16,
page 27.
2. Route the incoming 120 VAC power wire
through the provided openings in the bot-
tom right side jacket panel.
3. The appliance must be provided with an
external service switch, check local code
requirements for compliance.
The installer must provide and install a
fused disconnect or 15 amp (minimum)
service switch. Check local electrical
code requirements for compliance.
The ON/OFF switch of the CHAL-
LENGER only disables the function of the
appliance. Electrical power remains at the
control module. To avoid a shock hazard,
disconnect power at the external service
switch when servicing the appliance.
Control Module Circulator AMP Ratings
- AMP draw of the CH circulator must not
exceed 2.3 amps.
WARNING
NOTICE
WARNING