Install Instructions
Installation
2
CODE COMPLIANCE
Maxi-Flo Heat Exchanger installation must conform with
the instructions in this manual and where applicable:
• Local,  state,  provincial,  and  national  codes,
laws, regulations and ordinances.
LOCATING THE MAXI-FLO HEAT EXCHANGER
• The Maxi-Flo
®
is not intended for outdoor installa-
tion. The unit must be sheltered from direct contact
of rain and moisture.
•  Keeping the distance between boiler and Maxi-Flo
®
to a minimum will:
- reduce piping heat loss
- provide minimal friction loss
•  The  Maxi-Flo
®
should  not  be  located  in  an  area
where possible water leakage will result in damage
to the appliance or to the surrounding structure.
It is recommend to install the Maxi-Flo
®
in an area at
or  above  the  pool  water  level.  Installing  the  Maxi-
Flo® in an area below the pool water level, such as a
basement, may result in extensive flooding of the area
and potential draining of the pool.
AUTOMATIC  CHLORINATORS  AND  CHEMI-
CAL FEEDERS
•  All  chemicals  must  be  introduced  and  completely
diluted into the pool or spa water before being cir-
culated through the heater.
•  Do not place chlorine tablets or bromine sticks in the
skimmer.  High chemical concentrations will result
when the pump is not running (i.e. overnight).
•  Chlorinators  must  feed  downstream  of  the  unit  and
have  an  anti-siphoning  device  to  prevent  chemical
back-up  into  the  heat  exchanger  when  the  pump  is
shut-off.
WARNING
High  chemical  concentrations  from  improperly
adjusted  feeders  and  chlorinators  can  cause  rapid
corrosion to the heat exchanger.  Bypassing the heat
exchanger, is recommended, prior to stabilization of
pH at 7.2 to 7.8 level and chlorine residual at 1.0 to
3.0 ppm. 
Equip the chlorinator with an anti-siphoning device
to  prevent  high  concentrations  of  chloride  from
siphoning back into the heat exchanger after the fil-
ter pump shuts off.
•  The chlorinator should not  operate unless the filter
pump is running.
•  If  the  chlorinator  is  controlled  by  an  independent
timer, ensure the timer is synchronized with the fil-
ter pump timer.
OPERATING RESTRICTIONS
• Maximum boiler water temperature is 230ºF.
• Maximum  working  pressure  for  Maxi-Flo
®
is  140
psig (primary and secondary) for stainless steel, and
425 psig primary  and  70  psig  secondary  for  titani-
um.
•  Recommended water chemistry levels:
Free Chlorine  . . . . . . . . . . . . . . . . . .1.0 - 3.0ppm
Bromine  . . . . . . . . . . . . . . . . . . . . . .2.0 - 4.0ppm
pH . . . . . . . . . . . . . . . . . . . . . . . . . . .7.2 - 7.8
Total Alkalinity  . . . . . . . . . . . . . . . . 60 - 120ppm
Calcium Hardness  . . . . . . . . . . . . . . . .200 - 1,000ppm
Langelier Saturation
Index (S.I)  . . . . . . . . . . . . . . . . . . . .(-)0.5 to (+)0.5
Cyanuric Acid  . . . . . . . . . . . . . . . . .30 - 150ppm
Total Dissolved
Solids (TDS)  . . . . . . . . . . . . . . . . . .< 1000 ppm
Copper  . . . . . . . . . . . . . . . . . . . . . . .0ppm
Chloride  . . . . . . . . . . . . . . . . . . . . . .140ppm
Salt Concentration  . . . . . . . . . . . . . .80 ppm
•  Water chemistry restrictions for Titanium Maxi-Flo:
Free Chlorine  . . . . . . . . . . . . . . . . . .0 - 15ppm
Salt concentration  . . . . . . . . . . . . . .0 - 10,000ppm
WARNING
NOTICE