Instinct Installation Manual

Table Of Contents
CHAPTER 2 - COMBUSTION AIR & VENTING
11
2.8.3
Signage
A metal or plastic identification plate shall be
permanently mounted to the exterior of the building at
a minimum height of eight (8) feet above grade directly
in line with the exhaust vent terminal for the horizontally
vented gas fueled heating appliance or equipment.
The sign shall read, in print size no less than one half
(1/2) inch in size,
GAS VENT DIRECTLY BELOW. KEEP
CLEAR OF ALL OBSTRUCTIONS”.
2.8.4
Inspection.
The state or local gas inspector of the side wall
horizontally vented gas fueled equipment shall not
approve the installation unless, upon inspection, the
inspector observes carbon monoxide detectors and
signage installed in accordance with the provisions of
248 CMR 5.08(2)(a) 1 through 4.
Exemptions
The following equipment is exempt from 248 CMR
5.08(2)(a) 1 through 4:
1.
The equipment listed in Chapter 10 entitled
“Equipment Not Required To Be Vented” in the most
current edition of NFPA 54 as adopted by the Board;
and
2.
Product Approved side wall horizontally vented gas
fueled equipment installed in a room or structure
separate
fr
om
the
dw
elling
,
building
or
struc
tur
e
used in whole or in part for residential purposes.
2.8.5
Manufacturer Requirements - Gas Equip-
ment Venting System Provided.
When the manufacturer of Product Approved side wall
horizontally vented gas equipment provides a venting
system design or venting system components with the
equipment, the instructions provided by the manufac-
turer for installation of the equipment and the venting
system shall include:
1.
Detailed instructions for the installation of the venting
system design or the venting system components;
and
2.
A complete parts list for the venting system design
or venting system.
2.8.6
Manufacturer Requirements - Gas Equip-
ment Venting System Not Provided.
When the manufacturer of a Product Approved side
wall horizontally vented gas fueled equipment does
not provide the parts for venting the flue gases, but
identifies “special venting systems”, the following
requirements shall be satisfied by the manufacturer:
1.
The referenced “special venting system” instructions
shall be included with the appliance or equipment
installation instructions; and
2.
The “special venting systems” shall be Product
Appr
o
v
ed
b
y
the
B
oar
d
,
and
the
instruc
tions
f
or
that
system shall include a parts list and detailed installation
instructions.
A copy of all installation instructions for all Product
Approved side wall horizontally vented gas fueled
equipment, all venting instructions, all parts lists
for venting instructions, and/or all venting design
instructions shall remain with the appliance or
equipment at the completion of the installation.
CHAPTER 2