CHAPTER 9 - CTRLMAX OPERATION
48
EZ Setup
Heating EZ Setup
Select CH Demand
Thermostat & Setpoint
Constant
& Setpoint
0 - 10 V Modulation Signal
Select CH Demand
prompts the installer to select how a CH De-
mand is generated.
Thermostat & Setpoint
- A central heating call from a thermostat or
zone panel will enable the INSTINCT and the setpoint will be fixed for
central heating calls. After Thermostat & Setpoint is selected, the
CH1
Setpoint
screen appears. (see below).
Select CH Demand
Thermostat & Setpoint
Constant & Setpoint
0 - 10 V Modulation Signal
CH1 Setpoint
140°F
68°F
188°F
CH2
Setpoint
140°F
68°F
188°F
EZ Setup Complete
Heating EZ setup is complete.
Additional
changes can be made in
the Installer Menu if required.
Press OK to return to EZ Setup Menu
Constant & Setpoint
- The INSTINCT will maintain setpoint without
an external CH call from a thermostat or zone panel. The setpoint will
be fixed for CH calls. After Constant & Setpoint is selected, the CH1
Setpoint
screen appears.
CH1 Setpoint
prompts to enter the fixed setpoint for a CH1 heating
call
when
a
S
etpoint
option
is
chosen
in
S
elec
t
CH
D
emand
.
Touch the
then touch
appears.
or
soft keys to adjust the temperature setpoint
to store the setting.
The
CH2 Setpoint
screen then
CH2 Setpoint
prompts to enter the fixed setpoint for a CH2 heating
call
when
a
S
etpoint
option
is
chosen
in
S
elec
t
CH
D
emand
.
Touch the
then touch
S
etup
.
or
soft keys to adjust the temperature setpoint
to store the setting and complete the Heating EZ
CH1 Default: 140°F [60°C]
CH2 Default: 140°F [60°C]
Select CH Demand
Thermostat & Setpoint
Constant & Setpoint
0 - 10 V Modulation Signal
EZ Setup Complete
Heating EZ setup is complete.
Additional changes can be made in
the Installer Menu if required.
Press OK to return to EZ Setup Menu
0 - 10V Modulation Signal
- This option allows the INSTINCT firing
rate to be controlled by an external control system.
Refer to
Chapter 13 on page 69
for more information.
9.7.
Heating EZ Setup
Heating EZ Setup allows the installer to quickly customize the central heating settings for the application.
9.7.1
Select CH Demand (No outdoor sensor connected)
CHAPTER 9