CHAPTER 11 - START-UP PROCEDURES
11.3.5
Measure Input - Natural Gas Only
1.
Ensure the boiler is firing at maximum firing rate. To
manually place the boiler into high fire, reference
Section 11.3.4 on page 65.
2.
Operate the unit for approximately 10 minutes.
3.
Turn off all gas appliances within the building, ex-
cept the INSTINCT.
4.
At the gas meter, record the time required to use
one
cubic
f
oot
of
gas
.
5.
Calculate Natural gas input using the following
equation:
3600 x 1000 / number of seconds recorded for one
cubic foot of gas = BTU/H.
6.
The BTU/H calculated should approximate the in-
put rating listed on the unit.
11.3.6
Test High Temperature Limit
The high temperature limit can be temporarily lowered
from 210ºF [99ºC] to 10 F [39ºC] for testing.
1.
Touch simultaneously on the
and
soft keys
for 3 seconds to access the functions for the install-
er. Reference
Fig. 26 on page 43.
2.
Enter the installer access
code “054”,
using
the
and
soft keys to select a digit and the
and
soft keys to change the digit. Touch the soft key
to enter the access code.
3.
Touch the
soft key while CH & DHW Settings
icon
is highlighted.
4.
Touch the
soft key to highlight the Boiler Settings
icon then touch the soft key.
5.
Touch the
soft key to highlight Lockout
Temperature then touch the
soft key.
6.
Touch the soft key to highlight 102ºF [39ºC] then
touch the soft key.
7.
Touch the
soft key to highlight the Home Screen
icon
then touch the
soft key.
8.
Initiate a CH or DHW call and confirm that a High
Boiler Temperature lockout occurs once the supply
temperature reaches 102ºF [39ºC].
9.
Touchany
ARROW
soft key to return to the Home Screen.
10.
Touch simultaneously on the
and
soft keys for
3 seconds to access the functions for the installer.
11.
Touch the
soft key while the CH & DHW Settings
icon
is highlighted.
12.
Touch the
soft key to highlight the Boiler Settings
icon
then touch the
soft key.
13.
Touch the
soft key to highlight Lockout
Temperature, then touch the
soft key.
14.
Touch the soft key to highlight 210ºF [99ºC] then
touch the
soft key.
15.
Touch the
soft key to highlight the Home Screen
icon
then touch the
soft key.
16.
Touch the
soft key to reset the lockout and
return the unit to service.
Table 6 - Acceptable Combustion Levels
Natural Gas 110, 155
Natural Gas 199
Propane 110, 155
Propane 199
HIGH
FIRE
CO2 Range
9.0 to 10.5%
8.5 to 10.5%
10.0 to 11.0%
CO2 Target
9.50%
10.80%
O2 Range
4.85 to 2.15 %
5.75 to 2.15 %
5.7 to 4.2 %
O2 Target
3.95%
4.50%
CO Max
<150 ppm @ 9.5% CO2
<200 ppm @ 10.8% CO2
LOW FIRE
CO2 Range
9.0 to 10.0 %
8.5 to 10.0 %
10.0 to 11.0 %
CO2 Target
9.5%
9%
10.8% 10.4%
Target values are equivalent to High Fire values, ensure
CO₂ values measured are less than or equal to High Fire
CO₂ measurements
Target values are equivalent to High Fire values, ensure
CO₂ values measured are less than or equal to High Fire
CO₂ measurements
O2 Range
4.85 to 3.0 %
5.75 to 3.0 %
5.7 to 4.2 %
O2 Target
3.95% 4.85% 4.5% 5.1%
Target values are equivalent to High Fire values, ensure
O₂ values measured are higher than or equal to High
Fire O₂ measurements
Target values are equivalent to High Fire values, ensure
O₂ values measured are higher than or equal to High
Fire O₂ measurements
CO Max
10 ppm
10 ppm
CHAPTER 11