Instinct Installation Manual

Table Of Contents
CHAPTER 17 - MAINTENANCE PROCEDURES
79
17.13. Check Ignition Cable and Ground Wiring
Inspect the ignition cable from the spark generator
t
o
the
ig
nit
or
.
Inspect the ground wire from the spark generator
t
o
the
ig
nit
or
.
Ensure wiring is in good condition and securely connected.
Check ground continuity using a continuity meter.
Replace ground wire if ground continuity is not
satisfactory.
17.14. Check Control Wiring
I
nspec
t
all
control
wir
ing
.
Ensur
e
wir
ing
is
in
good
con
-
dition and properly connected.
17.15.
Check Control Settings
Review all boiler settings in the Heating & DHW
EZ
S
etup
menus
.
A
djust
settings
as
necessary
,
see
Section 9.7 onpage 48 and Section 9.8 onpage 50.
Check any external limit control settings (if used).
Adjust settings as necessary.
17.16.
Perform Start-up and Checkout Proce-
dures
Start the unit and perform the start-up procedures
as listed in
Chapter 11 on page 63
.
Verify the cold water fill pressure is correct and the
operating pressure of the boiler is within normal
operating range.
Complete the checkout procedures as outlined in
Chapter 14 on page 71.
17.17. Check Burner Flame
Inspect the flame pattern through the observation
port of the heat exchanger.
If flame pattern is not fully blue and covers the entire
burner surface during high fire, shut the unit down
and allow it to cool thoroughly before disassembly.
Close the external manual gas valve on the gas
supply line and disconnect the gas piping and gas
valve wire harness connector.
Disconnect the wiring harness connectors from the
blo
w
er
and
r
emo
v
e
the
blo
w
er
.
R
emo
v
e
the
blo
w
er
from the unit.
Remove the mounting nuts securing the burner
plate to the heat exchanger and set aside. Also re-
move the two screws* securing the burner plate to
the
back
panel
at
the
r
ear
and
discar
d
.
* These two screws are for transportation purposes
only and can be discarded.
Carefully remove the burner plate assembly from
the heat exchanger by lifting the front of the
burner plate initially then disengage the plate from
rear studs. Ensure that the combustion chamber
2-in-1 insulation is not damaged during removal of
burner mounting plate assembly.
Remove the burner head mounting screws and re-
move the burner head. Inspect the burner head for
deterioration. Use compressed air or a vacuum to
clean the burner head.
Remove the venturi and gas valve assembly from
the
blo
w
er
.
Use a vacuum cleaner or compressed air to clean
the interior of the blower assembly. Inspect the
blower blades to ensure they are clean and not
damaged
.
Re-assemble the venturi and gas valve onto the
blo
w
er
.
Ensur
e
the
v
entur
i
gask
et
or
o
-r
ing
is
in
good condition and positioned correctly. Replace
gasket or o-ring if necessary.
Re-assemble the burner head onto the burner
mounting plate. Ensure the burner head gasket is
in good condition and positioned correctly. Replace
gasket if necessary.
Re-assemble the burner plate assembly onto the
heat exchanger. Ensure the combustion chamber
2-in-1 insulation is in place and positioned correctly.
Replace if necessary.
Remove the blower gasket from the burner plate
assembly and clean with fresh water. Reinstall
blower gasket onto burner plate assembly with the
check
valve
hinge
at
the
t
op
.
Re-assemble the blower onto the burner plate and
reconnect the wiring harness connectors.
Re-assemble the gas supply connection and wire
harness to the gas valve. Open the external manual
gas valve. Check gas piping for any leaks as outlined
in
Section 10.5 on page 62
and repair if necessary.
T
or
que
all
scre
ws
,
bolts
,
and
nuts
in
accor
dance
with specifications in
Section 17.24 on page 80
.
Place the unit back into service.
17.18.
Check Flame Signal
The flame signal can be read from the Boiler Infor-
mation screen. It should be a min. 2-3 μΑ at low fire.
Check
the
ig
nit
or
condition
if
flame
sig
nal
is
lo
w
.
Check ground wire for continuity if flame signal is
lo
w
.
Replace
ig
nit
or
if
conditions
ar
e
satisfac
t
ory
.
CHAPTER 17