9.0 ACVMax Operation
9.6 EZ Setup
Navigation: Home Screen>Main Menu>EZ Setup
The EZ Setup menus provide a simple way to quickly customize the
TriMax for each installation. EZ Setup prompts the user to make selections
which allows the Prestige to be setup very quickly without searching
through long lists of settings and manually making adjustments.
9.7 Heating EZ Setup
Navigation: Home Screen>Main Menu>EZ Setup>Heating EZ Setup
Heating EZ Setup allows the installer to quickly customize the central heat-
ing settings for the application.
9.7.1 Select CH Demand Default: Switch & Outdoor Reset
Select CH Demand prompts the installer to select how a CH Demand is gen-
erated. Press the UP or DOWN buttons to select the CH Demand type then
press the OK button to store the setting. The Select CH Demand options are:
Thermostat & Outd. Curve – This option is only displayed when the
outdoor temperature sensor is connected. A central heating call from a
thermostat or zone panel will enable the Prestige and the setpoint will
vary with the outdoor temperature for central heating calls.
Thermostat & Setpoint - This option is only displayed when the out-
door temperature sensor is not connected. A central heating call from
a thermostat or zone panel will enable the Prestige and the setpoint will
be fixed for central heating calls
Constant & Outdoor Curve - This option is only displayed when the
outdoor temperature sensor is connected. The Prestige will maintain set-
point without an external call from a thermostat or zone panel. The set-
point will vary with the outdoor temperature for central heating calls.
Constant & Setpoint - The Prestige will maintain setpoint without an
external call from a thermostat or zone panel. The setpoint will be fixed
for central heating calls.
0-10V Modulation Signal – This option allows the Prestige firing rate
to be controlled by an external control system.
9.7.2 CH1 Setpoint Default: 180°F [82°C]
CH1 Setpoint prompts the installer to enter the fixed setpoint for a CH1
heating call when a Setpoint option is chosen in Select CH Demand. Press
the LEFT or RIGHT buttons to adjust the CH1 Setpoint then press the
OK button to store the setting.
9.7.3 CH2 Setpoint Default: 140°F [60°C]
CH2 Setpoint prompts the installer to enter the fixed setpoint for a CH2
heating call when a Setpoint option is chosen in Select CH Demand. Press
the LEFT or RIGHT buttons to adjust the CH2 Setpoint then press the
OK button to store the setting.
Select CH Demand
Thermostat & Setpoint
Constant & Setpoint
0
-10V Modulation Signal
Select CH Demand
Thermostat & Outd. Curve
Constant & Outdoor Curve
C
onstant & Setpoint
0-10V Modulation Signal
OR
60ºF
188ºF
180ºF
CH1 Setpoint