Prestige Solo Features
• Light weight construction for wall mounting
• Approved for zero clearance to combustibles
• 3” PVC, CPVC, PP, or AL29-4C venting up to 100
equivalent feet
• Limited 5 year warranty on parts, except igniter
• Limited 10 year warranty on heat exchanger
Approvals
• 95% AFUE Efficiency
• ENERGY STAR Qualified
• ANSI Z21.13 and CSA 4.9 Boiler Standards
Compliance
• ASME Boiler Certification – ASME “H” Stamp
• Low NOx operation exceeding SCAQMD 2012 regu-
lations
Stainless Steel Fire Tube Heat Exchanger
• 439 Stainless Steel heat exchanger construction for
corrosion resistance
• Low pressure drop minimizes circulator size
• High water content provides stable temperature
control
• Self cleaning flue ways reduce maintenance
• Suitable for use with propylene glycol up to 50%
concentration
ACVMax Control System
• Graphical display with 6 navigation buttons
• EZ Setup allows quick and easy boiler settings adjust-
ment
• Presets allow quick configuration of 4 circulator out-
puts
• Each circulator output is fully configurable for cus-
tom applications
• Outdoor temperature reset to maximize efficiency
• Accepts two space heating call inputs with indepen-
dent outdoor reset curves
• Simultaneously heat dual temperature heating sys-
tems with built-in mixing valve control
• Domestic hot water priority with optional time-out
• Integrated cascade control for up to 6 Prestige boil-
ers
• 0-10 VDC Modulation input
• Modbus building management system (BMS) inter-
face, LonWorks® and BACnet® interface optional
• Adjustable warm weather shutdown
• Adjustable boiler freeze protection
• Logging function records sensor readings for sys-
tem optimization and troubleshooting
• Describes lockouts in plain english and suggests
solutions while storing last 8 errors
Standard Equipment
• Stainless steel premix burner
• Direct spark ignition with variable speed blower
• Full modulation with turndown ratio of 5.5:1
• Automatic air vent
• ASME 30 PSI pressure relief valve
• Integrated pressure and temperature gauge
• Outdoor temperature sensor
• Automatic low water cutoff feature with early warn-
ing
• High temperature manual reset limit safety control
• Terminal block for circulator output
• Low voltage terminal strip with removable jumpers
for manual or automatic reset limits
• Swing out control for easy access and servicing
• Alarm and flame status contacts
• Polypropylene condensate pan and internal flue
pipe
• Polypropylene vent/air connections with test ports
Engineering Submittal
Prestige Solo 155
1
2016-9 Prestige ACVMax Solo 155 SubmittalDate: 12/11/2017
Project / Location:_________________________________________________________________ Date: _______________
Consulting Engineer / Architect: _________________________________________________________________________
Mechanical Contractor: _________________________________________________________________________________