prestige Control Application Supplement - ACVMax LI STED WARNING This document is intended to be used by a factory trained and qualified heating contractor or service technician only. Read all instructions within this document and within the PRESTIGE Boiler Installation and Maintenance Manual before proceeding. It is recommended to follow the procedures in the steps given. Skipping or missing procedural steps could result in severe personal injury, death or substantial property damage.
Table of Contents PRODUCT AND SAFETY INFORMATION Definitions ................................................................................................................1 1.0 - OPERATING INFORMATION 1.1 1.2 Entering Installer Access Code ......................................................................2 ACVMax Installer Menu Structure..................................................................3 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.10 2.11 2.12 2.13 2.14 2.15 2.16 2.17 2.18 Navigation .
Table of Contents - Continued 4.6 4.5.2 Preset Pump Configuration (Solo) .................................................16 4.5.3 Preset Pump Configuration (Excellence) .......................................16 4.5.4 Flexible Pump Configuration..........................................................16 4.5.5 Flex. Relay Configuration...............................................................17 4.5.6 Error Relay .....................................................................................
(Page left intentionally blank) iii
Product and Safety Information IMPORTANT INFORMATION - READ BEFORE PROCEEDING WARNING NOTICE This document is intended to be used by a factory trained and qualified heating contractor or service technician only. Read all instructions within this document and within the PRESTIGE Boiler Installation and Maintenance Manual before proceeding. It is recommended to follow the procedures in the steps given.
1.0 1.0 Operating Information OPERATING INFORMATION The ACVMax Boiler Management System is designed to be flexible yet easy to use. ACVMax monitors and controls the Prestige to operate as efficiently as possible. ACVMax monitors the boiler supply, return and flue gas temperatures and operates the igniter, gas valve and blower. ACVMax uses this information to modulate the boiler’s firing rate to maintain the required setpoint.
1.0 1.1 Operating Information Entering Installer Access Code The INSTALLER button (the small round button) provides the installing contractor with full access to all available features after entering an access code. Installer Button Fig. 1: ACVMax Navigation Buttons Entering installer access code procedure 1. Press the round INSTALLER button. 2. Enter the installer access code “054” by using the LEFT and RIGHT buttons to select a digit and the UP and DOWN buttons to change the digit.
1.0 1.2 Operating Information ACVMax Installer Menu Structure Home Screen Installer Access Code ENTER INSTALLER ACCESS CODE 05[4] Installer Menu CH & DHW Settings CH & DHW Settings Menu CH Settings Reset All Settings Cascade Menu Reset All Settings Cascade Info.
2.0 2.0 2.1 CH Settings CH SETTINGS Heating Settings Navigation: Home Screen > Installer Menu > CH & DHW Settings > CH Settings The CH Settings menu contains settings related to central heating operation. Each line contains a CH Setting followed by its current value. Six CH Settings are displayed on the screen at one time. Press the UP or DOWN buttons to scroll through additional CH Settings. 2.
2.0 2.4 CH Settings Absolute Max CH Setpoint Default: 188°F [87°C] Absolute Max CH Setpoint can be used to prevent a user from adjusting the central heating setpoint or outdoor reset curve above a safe operating temperature in the EZ Setup Menu. A warning screen will be displayed in EZ Setup if the user attempts to raise the setpoint above the Absolute Max CH Setpoint.
2.0 CH Settings 2.8 Outdoor Curve Warmest Day Default: 64°F [18°C] Outdoor Curve Warmest Day is the warmest outdoor design temperature of the heating system when an Outdoor Curve option is chosen in Demand Type. This setting is not applicable when a Setpoint option is chosen in Demand Type. Press the LEFT or RIGHT buttons to adjust the Outdoor Curve Warmest Day then press the OK button to store the setting.
2.0 2.13 CH Settings Circulation Pump Permanent Default: Disabled Circulation Pump Permanent allows the circulators configured for central heating calls in Pump Settings to be constantly enabled even without a central heating call. The Warm Weather Shutdown function will disable circulators enabled via this function. A domestic hot water call will cause the circulators to be disabled during the domestic call as long as DHW Priority is enabled.
2.0 CH Settings WARNING Freeze Protection should only be disabled when the system contains antifreeze to prevent the system from freezing. Serious damage could occur to the Prestige as well as the entire heating system if Freeze Protection is disabled without antifreeze in the system. WARNING The Prestige should NEVER be installed in a location where freezing could occur. Subjecting the Prestige to freezing conditions could lead to freezing of the condensate possibly causing serious injury or death. 2.
3.0 3.0 3.1 DHW Settings DHW SETTINGS Navigation: Home Screen>Installer Menu>CH & DHW Settings>DHW Settings The DHW Settings menu contains settings related to domestic hot water operation. Each line contains a DHW Setting followed by its current value. Six DHW Settings are displayed on the screen at one time. Press the UP or DOWN buttons to scroll through additional DHW Settings. DHW Operation Default: Enabled DHW Operation allows the domestic hot water function to be enabled and disabled.
3.0 DHW Settings 3.4 DHW Boiler Setpoint Default: 168ºF [76ºC] DHW Boiler Setpoint is the fixed boiler setpoint temperature during a domestic hot water call when the Thermostat option is chosen in DHW Demand. Press the LEFT or RIGHT buttons to adjust the DHW Boiler Setpoint then press the OK button to store the setting. 3.5 DHW Setpoint Default: 140°F [60°C] DHW Setpoint is the domestic hot water storage setpoint temperature when the Sensor option is chosen in DHW Demand.
3.0 DHW Settings 3.7 DHW Storage Adder Default: 46°F [25°C] DHW Storage Adder is used to compute the boiler setpoint when the Sensor option is chosen in DHW Demand. The boiler setpoint will be DHW Setpoint + DHW Storage Adder for a domestic hot water call. Press the LEFT or RIGHT buttons to adjust the DHW Storage Adder then press the OK button to store the setting.
3.0 DHW Settings taneous domestic hot water and central heating calls are present. The DHW circulator will be enabled during a domestic hot water call. The heating circulators will be enabled during a central heating call. WARNING Simultaneous domestic hot water and central heating calls will result in the PRESTIGE operating at the highest target temperature when DHW Priority is set to Disabled.
3.0 DHW Settings 3.13 Antilegionella Function Default: Enabled The Antilegionella Function ensures that an Indirect Water Heater is heated at least once per week to prevent the growth of Legionella bacteria. Press the UP or DOWN buttons to select Enabled or Disabled then press the OK button to store the setting. • • Enabled- When the Thermostat option is chosen in DHW Demand, a domestic hot water call is generated for 15 minutes once per week to heat the Indirect Water Heater.
4.0 4.0 4.1 Boiler Settings BOILER SETTINGS Boiler Settings Navigation: Prestige Model Home Screen>Installer Menu>CH & DHW Settings>Boiler Settings The Boiler Settings menu contains settings related to general boiler operation. Each line contains a Boiler Setting followed by its current value. 4.2 • Lockout Temp. 210ºF [99ºC] Modbus Address Solo (2 pumps) - A CH Demand is satisfied using the circulators configured for central heating calls in Pump Settings.
4.0 4.4 Boiler Settings Modbus Address Default:0=BCST Modbus Address assigns the boiler with a unique address in the Modbus control system. Press the LEFT or RIGHT buttons to change the Modbus Address then press the OK button to store the setting. See Pages 57 & 58 for Modbus Interface information. 4.5 Pump Settings Pump Settings allows the selection or assigment of the appropriate pump configuration for the installation piping arrangement.
4.0 Boiler Settings 4.5.5 Flex. Relay Configuration Each relay function has several options that must be set for activation. Press the UP or DOWN buttons to scroll through the options then press the OK button to toggle between the On/Off status. At the end of the list is Save & Exit which will store the settings for the particular relay. • On - Activation of the relay will occur. • Off - Activation of the relay will not occur. • CH1/CV1 - Relay is activated at CH 1 Demand.
Boiler Settings ! " # $ " $%" & # " " '# (# 4.0 Fig.
Boiler Settings ( ) ' ) * + (( ) ', $* -* .* ! " ! # ! ! $ ! % & % 4.0 Fig.
Boiler Settings ( ) ' ) * + (( ) ', $* -* .* ! " ! # ! ! $ ! % & % 4.0 Fig.
Boiler Settings ! " # $ " $%" & # " " '# (# 4.0 Fig.
Boiler Settings ! " # $ " $%" & # " " '# (# 4.0 Fig.
Boiler Settings ! " # $ " $%" & # " " '# (# 4.0 Fig.
Boiler Settings $) 4.0 * " $+ , * $ +#$ $% $ +#$ * ! " # $ " $%" & # " " '# (# $) Note: This Configuration to be used where the Low Temp Circuit is a micro load as the High Temp Circuit will run for any call on the Low Temp Circuit to prevent boiler cycling. Fig.
Boiler Settings ! " # $ " $%" & # " " '# (# 4.0 Fig.
Boiler Settings $) 4.0 * " $+ , * $ +#$ $% $ +#$ * ! " # $ " $%" & # " " '# (# $) Note: This Configuration requires that the Low Temp Pump and High Temp Pump be connected in parallel to the CH Pump Relay. An isolation relay is may be used to ensure the CH Pump Relay will not be overloaded during operation. Fig.
Boiler Settings $) 4.0 * " $+ , * $ +#$ * $% $ +#$ ! " # $ " $%" & # " " '# (# $) Note: This Configuration to be used where the Low Temp Circuit is a micro load as the High Temp Circuit will run for any call on the Low Temp Circuit to prevent boiler cycling. Fig.
Boiler Settings $) 4.0 * " + * $ ,#$ * $% $ ,#$ ! " # $ " $%" & # " " '# (# $) Fig.
Boiler Settings $) 4.0 * + * $ ,"$ $% $ ,"$ * !"# $ $% # & "! '" !(" $) # Fig.
Boiler Settings $) 4.0 * $% $ ,"$ * !"# $ $% # & "! '" + * $ ,"$ !(" $) # Fig.
Boiler Settings !"# $ $% # & "! '" !(" 4.0 Fig.
Boiler Settings !"# $ $% # & "! '" !(" 4.0 Fig.
Boiler Settings $, 4.0 * $% $ +"$ * !"# $ $% # & "! '" !(" ) * $ +"$ $, # Fig.
Boiler Settings $, 4.0 + $% $ )"$ + !"# $ $% # & "! '" !(" $) ! * + $ )"$ $, # Fig.
4.
5.0 Reset All Settings 5.1 Navigation: 5.0 RESET ALL SETTINGS Home Screen>Installer Menu>Reset All Settings Reset All Settings allows the installer to reset all CH, DHW, Boiler and Cascade settings back to the original PRESTIGE Solo factory defaults. Follow the onscreen instructions to reset all settings back to the original factory defaults. NOTICE PRESTIGE Excellence units require setting Prestige Model to Solo/Excel.
6.0 6.0 Section 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.10 2.11 2.12 2.13 2.14 2.15 2.16 2.17 2.18 Factory ACVMax Settings FACTORY ACVMAX SETTINGS Setting Heating Operation Enabled Demand Type Thermostat & Outd.
7.0 7.0 7.1 Cascade CASCADE Cascade Operating Information The ACVMax Boiler Management System includes a Cascade function which allows multiple Prestige boilers to operate together without the need for an external controller. One Prestige will be selected as the Master and will be wired to accept all the low voltage control signals. The other Prestige boilers will be designated as Slaves and will only have a communication cable connecting them to the other boilers in the Cascade System.
7.0 7.2 Cascade ACVMax Cascade Menu Structure Installer Menu Cascade Cascade Menu Cascade Cascade Information Menu Cascade Information Cascade Settings Menu Cascade Autodetection Cascade Settings Cascade Autodetection Stage Delay 60 sec Cascade Role Master System Temp. 86ºF Active Boilers 0 Max. Firing Rate Total Boilers 2 CH/DHW Boilers Cascade Firing Rate -- Auto Rotation Enabled CH Prop.
7.0 Cascade 7.3 Cascade Installation 7.3.1 System Piping Standard Cascade installations will utilize a balanced manifold system as the primary / secondary connection to the system piping as shown in Figure 21 on page 44 or a reverse return piping arrangement as shown in Figure 23 on page 46. Split Cascade installations will utilize a balanced manifold system as the primary / secondary connection to the central heating loop.
7.0 Cascade 1. Remove the white plastic cover from the sensor 2. Cut a small slit in the gasket seal on the end of the sensor. 3. Route 18 AWG 2-wire cable or similar cable through the seal gasket into the enclosure. 4. Push down on the orange wire terminal retainers to insert the wires into the sensor terminals. Release the orange wire terminal retainers and confirm that the wires are firmly attached to the sensor terminals. 5.
7.0 7.3.5 • Cascade Line Voltage Wiring Connections Circulator Wiring - Reference Figures 22, 24 and 26 on pages 45, 47 and 49 for circulator wiring required for each type of Cascade System. The circulator connections used will depend on the systems piping layout. NOTICE All circulators are powered from a common 5A fuse located on the control module. The total combined amp draw of the all circulators must not exceed 5 amps at any time.
7.0 Cascade 7.3.7 Lockouts If a lockout occurs to a boiler in a Cascade System, it will be removed from Cascade System operation. The remainder of the Cascade System continues to operate and the next available boiler will fire if necessary. The Lockout Screen will be displayed on the locked out boiler as well as the Master boiler. The Master boiler Lockout Screen will also indicate which boiler in the Cascade System is locked out.
Cascade Note: Reference Fig. 22, page 45 for cascade wiring. 7.0 Fig.
7.
Note: Reference Fig. 24, page 47 for cascade wiring. 7.0 Cascade Fig.
7.
Note 2: DHW Priority must be set to Enabled in DHW Settings of the Cascade Master for proper operation. Note 1: Reference Fig. 26, page 49 for cascade wiring. 7.0 Cascade Fig.
7.
7.0 7.4 7.4.1 Cascade Cascade Information Navigation: Home Screen>Installer Menu>Cascade>Cascade Information Cascade Information provides real time operating information of the Cascade System. Each line contains an information item followed by its current value. See below for a list of all Cascade Information items. 7.4.2 System Temperature Logging System Temperature has a logging function which records one sample every 12 minutes to produce a graph of the last 24 hours.
7.0 Cascade 7.5 7.5.1 Cascade Settings Navigation: Cascade Setting Home Screen>Installer Menu>Cascade>Cascade Settings The Cascade Settings menu contains settings related to cascade operation. Each line contains a Cascade Setting followed by its current value. Six Cascade Settings are displayed on the screen at one time. Press the UP or DOWN buttons to scroll through additional Cascade Settings. NOTICE Stage Delay 60 sec Minimum Firing Rate Max.
7.0 Cascade 7.5.4 Boiler Enabling Algorithm The Master boiler uses the following algorithm to determine when the next boiler can be enabled: Number of Boilers Firing +1 x Minimum Firing Rate = Individual Boiler Firing Rate Number of Boilers Firing Once the currently fired boilers reach the calculated firing rate, the next boiler can be enabled without affecting the overall cascade firing rate.
7.0 Cascade 7.5.7 CH/DHW Boilers Default: 0 The CH/DHW Boilers setting specifies how many boilers in a Split Cascade System will respond to a domestic hot water call. The CH/DHW Boilers always begins with the Master boiler. The remaining boilers of the Cascade System will only respond to central heating calls. This allows the Cascade System to satisfy both central heating and domestic hot water calls at the same time.
7.0 Cascade 7.5.9 CH Proportional Gain Default: 7 CH Proportional Gain allows the cascade response to be adjusted for a central heating call. CH Proportional Gain has the greatest influence when the system temperature is far away from the setpoint. Press the LEFT or RIGHT buttons to adjust the CH Proportional Gain then press the OK button to store the setting.
7.0 - Cascade To reach the setpoint faster, decrease the CH Integral Gain value by 2. Perform Cascade Autodetection and initiate a central heating call. Observe the cascade response and make further adjustments if necessary. NOTICE Only make adjustments to this setting after consulting ACVTriangle Tube Technical Support. Improper adjustment of CH Integral Gain could lead to temperature fluctuations and erratic cascade operation. 7.5.
7.0 Cascade 7.5.12 DHW Integral Gain Default: 245 DHW Integral Gain allows the cascade response to be adjusted for a domestic hot water call. DHW Integral Gain has the greatest influence when the system temperature is close to the setpoint. Press the LEFT or RIGHT buttons to adjust the DHW Integral Gain then press the OK button to store the setting. • Increase DHW Integral Gain - • The Cascade System will take longer to reach the setpoint, but setpoint overshooting is minimized.
8.0 8.0 Modbus Interface MODBUS INTERFACE The Modbus Interface allows a Building Management System (BMS) to directly connect to the Prestige. A BMS can read information from the boiler to determine its operating state, lockout status, sensor readings, etc. A BMS can also operate the boiler by providing a setpoint.
8.
9.0 9.0 9.1 Manual Operation MANUAL OPERATION Navigation: Home Screen>Installer Menu>Manual Operation The Manual Operation Screen allows the burner and circulators to be manually enabled for testing. 9.2 Fan Press the OK button while the FAN icon is highlighted to manually fire the burner and power the CH (1) circulator. Press the LEFT and RIGHT buttons to adjust the firing rate from 1 % (Low Fire) to 100% (High Fire).
Additional quality water heating equipment available from ACV- Triangle Tube MAxI-FlO AND SPA HEAT ExCHANGERS - - - - Construction of high quality corrosion resistant stainless steel (AISI 316) or titanium Specially designed built-in flow restrictor to assure maximum heat exchange Compact and light weight Available in 8 sizes that can accommodate any size pool or spa SMART INDIRECT FIRED WATER HEATERS - - - - - - Exclusive tank-in-tank design Stainless steel construction Available in 7 size