Supplementary User Guide

53
7.0 Cascade
0
6
0
CH/DHW Boilers
7.5.7 CH/DHW Boilers Default: 0
The CH/DHW Boilers setting specifies how many boilers in a Split
Cascade System will respond to a domestic hot water call. The CH/DHW
Boilers always begins with the Master boiler. The remaining boilers of
the Cascade System will only respond to central heating calls. This
allows the Cascade System to satisfy both central heating and domestic
hot water calls at the same time. At the completion of a domestic hot
water call, the CH/DHW Boilers will again be available to respond to
central heating calls. Press the LEFT or RIGHT buttons to adjust the
CH/DHW Boilers setting then press the OK button to store the setting.
Splitting the Cascade System into CH only and CH/DHW boilers
requires the boilers to be piped as shown in Figure 25 on page 48.
The CH/DHW boilers must be piped to both CH and DHW loads
directly for proper operation.
DHW Priority must be set to Enabled in DHW Settings of the
Cascade Master for proper operation.
All CH/DHW Boilers will respond to a domestic hot water call. It is
important that the domestic load is capable of transferring all of the
heat generated to prevent excessive boiler cycling.
7.5.8 Automatic Rotation Default: Enabled
Automatic Rotation allows the lead stage automatic rotation function to
be disabled. Press the UP or DOWN buttons to select Enabled or
Disabled then press the OK button to store the setting.
Enabled The lead boiler automatically rotates every time a call for
heat is received when a Switch option is chosen in CH Demand or
every 24 hours when a Constant option is chosen in CH Demand.
Disabled – The lead boiler is always the Master boiler followed by
each Slave boiler.
NOTICE
NOTICE
NOTICE
Automatic Rotation
Enabled
Disabled