Prestige Venting Supplement

9
CHAPTER 1
CHAPTER 1 - PRE-INSTALLATION REQUIREMENTS
1.3. Vent/Combustion Air Equivalent
Lengths
For all venting applications, PVC/CPVC, AL29-4C®,
SS or Polypropylene, the length must not exceed
the lengths listed in Table 8 below.
For PVC/CPVC or AL29-4C® vent systems, reduce
the maximum allowable length for each elbow as
follows:
3 feet for every 45º elbow
5 feet for every 90º elbow
For polypropylene vent systems, reduce the maxi-
mum allowable length for each elbow as follows:
5 feet for every 45º elbow
10 feet for every 90º elbow
1.4. Vent Restrictions
1.4.1 2 Inch (60 mm) Vent System Restrictions
Derate the maximum boiler input by 3% when us-
ing the maximum equivalent length of 2 inch (60
mm) vent piping on Solo 110 & Excellence.
The 2 inch vent system requires a 1 inch clearance
to combustibles.
Use long sweep elbows to limit pressure drop and
to avoid excessive vent temperatures.
In 2 inch PVC vent applications, the rst 7 equivalent
feet of the vent system must utilize CPVC material.
To avoid vent failure, the installer must use
CPVC vent material for the first 7 equivalent
feet of a 2 inch PVC vent system. The installer
must also utilize primer and glue that is cer-
tified for both PVC/CPVC materials. Failure to
comply with this requirement can cause the
venting system to fail, resulting in substantial
property damage, serious injury, or death.
1.4.2 3 Inch (80 mm) Vent System Restrictions
Derate the maximum boiler input of the PRESTIGE Solo
250 by 3% when using the maximum equivalent length
of 3 inch (80 mm) vent piping.
WARNING
Table 8
Prestige
Model
Maximum Allowable Vent or Combustion Air Piping Length
2 Inch [60 mm] Piping
OR
3 Inch [80 mm] Piping
OR
4 Inch [100 mm] Piping
Feet Elbows Feet Elbows Feet Elbows
Solo 60 55 0 100 0 100 0
Solo 80 55 0 100 0 100 0
Solo 110 45 0 100 0 100 0
Solo 155
Not Applicable
100 0 100 0
Solo 175 100 0 100 0
Solo 250 60 0 80 0
Solo 299
Not Applicable
100 0
Solo 399 100 0
Excellence 110 45 0 100 0 100 0