User's Manual

Page 30
E Series Ethernet Radio – User Manual
LAN Ethernet Port
The LAN port is a 10/100 Base-T compliant port using an RJ-45
connector. These ports support both TIA/EIA-568-A & B wiring as they
have Auto MDI/MDIX Auto Sensing. This means you can use both
straight-through and cross-over type CAT-5 or better patch cables.
All RJ45 connectors must utilize mating plugs that include an integral
locking tab.
If termination of a cable is required, then the following wiring
arrangement should be followed (Compliant with TIA/EIA-568-A).
Note: Maximum differential voltage : 5v, 50mA max through each differential pair.
Note: If 100-BaseT connection speed is required, CAT-6 Shielded
cable should be used for installation to comply with ETSI EMC
directives.
Performing a Factory Default
Please read the following notes carefully. Conguration errors
with Ethernet connections can be difcult to nd and resolve. It
is strongly recommended that you follow these guidelines.
IP Address and Factory Default Reset
The factory default IP address of an E Series Ethernet radio is
192.168.2.15. If you do not know the IP address of the E Series
Ethernet radio you can either read the unit using the TVIEW
programmer or perform a factory default.
A factory reset will cause all previous conguration settings to be
erased and returned to the factory default values. A factory default
can be initiated by applying DC power to the radio (wait 45 seconds),
depress the factory default switch using a paper clip or similar object
and keep the switch depressed for 5 seconds until all ve LEDs
illuminate solid GREEN indicating the radio will return to the factory
default settings. Please wait 45 seconds for the factory default reset
process to complete.