© Copyright 2004 Trio DataCom Pty. Ltd.
Part E – Getting Started - EB450
Digital Inputs and Outputs
The EB450 provides a facility for two channels of digital user inputs
and outputs (Digital User I/O). Information on how to control and
monitor this I/O using TVIEW+ Diagnostics can be found in the E
Series User Manual - Part J - TVIEW+ Management Suite - Remote
Diagnostics & Network Controller.
All user I/O is optocoupled for isolation between the EB450 and uses
equipment. When using the I/O facility the I/O electrical characteristics
and ratings must be observed. Failure to observe these ratings may
result in equipment damage.
Inputs
Two User Inputs are available. They have identical interface
characteristics. Each input has an internal resistance of 470 Ohms.
Some form of switching contact (ie: switch, relay) is normally used to
change the state of the input. Both an isolated and non-isolated input
configuration is possible.
Typical Radio Setup
Is
TVIEW+ Diagnostics will recognise an input as being ON when the
switch is closed. If the switch is open (or not connected) TVIEW+
diagnostics will recognise the inputs as being OFF.
Outputs
Two User Outputs (Open Collector) are available. They have identical
interface characteristics. The maximum current allowed through each
output is 20ma. External resistors must be used keep the current
below this value.
Each output has an internal resistance of 100 Ohms.Ohms law can be
used to calculate the resistance required for a specific voltage (keeping
the current below 20mA). Nominally 1k Ohm is used for a +13v8
supply and 330 Ohms for a +5v supply.
When the OUTPUT is OFF, V = Vs. No current will flow when output
is off.
When the OUTPUT is ON, V = nominally 2.3 volts . Current is set
by resistor.