User's Manual

System synchronization: flood detector - controller
synchronization table
Note: adding detectors to the systems does not require resynchronization.
Subtraction or replacement of a detector required resynchronization of all the detectors
connected to the controller.
OPERATION Location Control indication
1 Press the valve "Open" and "Close"
buttons simultaneously.
CONTROL Red indicator - valve battery is continuously on.
Green indicator - voltage flashing.
2 Open the battery cover and insert
two AA batteries into the flood
detector.
Position the flood
detector where
measurements
indicate qualitative
and continuous
transmission from
the valve and the
controller.
I. The green detector indicator will flash every 5 seconds.
II. Wait 60 seconds, while looking at the detector indication light. When
the indicator light will light up for two consecutive seconds, the detector
will synchronize itself with the controller.
III. The green detector indicator will flash every minute.
IV. Now you can continue with this procedure to up to 10 detectors per
system.
3 Conclusion of the flood detector
synchronization will be achieved by
pressing the valve "Open" and
"Close" buttons simultaneously.
Flood detector. The controller will indicate voltage, communication and valve status (if
synchronized with the system.)
4 Synchronization test: expose the
detector to water (wetting the
electrodes would suffice.)
Flood detector.
Controller.
I. Detect a double flashing indication in the flood detector light.
II. Detect a flashing indication in the red valve battery light in the
controller.
III. Ensure that the valve was closed (if synchronized to the system.)
Pressing the "Open valve" button will return the system to routine state.