y : a te y nt ion y for p Li rrant a r t a ip ar tra tod E Tr m/wa W is ine RE co g nl F e. Re r o a lit e in ipp st r gi to w w.t e R ce ww an — ch uct od pr Owner’s Manual Programmable MODBUS Card Model: MODBUSCARD Introduction 2 Installation 2 Features 2 Configuration 3 Operation 5 Warranty & Warranty Registration 18 1111 W. 35th Street, Chicago, IL 60609 USA www.tripplite.com/support Copyright © 2010 Tripp Lite. All rights reserved.
Introduction The MODBUSCARD provides UPS systems with the functionality of communication with PCs through MODBUS protocol: • Implements MODBUS RTU protocol • Provides MODBUS functions including Read Coils, Discrete Inputs, Holding Registers, Input Registers, Write Single Coil and Single Register • Provides RS-422/485 and RS-232 interfaces (PC communicates with UPS via RS-422/485 or RS-232 or both at the same time) Installation The MODBUSCARD should be installed in the accessory slot intended for Tripp Lite
Configuration Configuration of RS-232 Port Use SW2 to configure the RS-232 interface.
Configuration continued Configuration of RS-422/485 Port Use SW3 to configure the RS-422/485 interface.
Operation Discrete Inputs (Range 0x0100 - 0x012F, Read Function 0x02) The Read Discrete Inputs function code is used to read 1-2000 contiguous status of Discrete Inputs in a remote device. The starting address and number of inputs is specified by the request Protocol Data Unit. Addresses start at 0 and Discrete Inputs numbered 1-16 would address as 0-15.
Operation continued Coils (Range 0x0200 - 0x020F, Read Function 0x01, Write Function 0x05) The Read Coils function reads 1-2000 contiguous status of coils in a remote device. The starting address and number of coils is specified by the request Protocol Data Unit. Addresses start at 0 and Coils numbered 1-16 would address as 0-15. The Write Coils function writes a single output to ON/OFF in a remote device. A specified constant in the data field requests the ON/OFF state.
Operation continued Holding Register (Range 0x0300 - 0x0321, Read Function 0x03, Write Function 0x06) continued Description Address UPS Periodic Auto-Test 0x030D Buzzer Test UPS Boot Delay Bypass Freq.
Operation continued Input Register (Range 0x0400 - 0x051C, Read Function 0x04) Rating Value continued Description Address Unit 0x040F 0x0410 0x0411 0x0412 0x0413 0x0414 0x0415 Value 0: On-Line 1: Off-Line 2: Line-Interactive 3: 3-Phase 4: Split Phase 5: Others 0-999 0-999 0-999 0-999 5-50 5-50 0-999 UPS Type 0x040E Rating Battery Voltage Low Tx Frequency Point High Tx Frequency Point Bypass Rating Frequency Bypass Freq Max Tolerance Bypass Freq Set Tolerance Bypass Low Tx Voltage Point/Bypass Rating
Operation continued Input Status Description Input Number Lines Input Frequency 1 Input Voltage 1 Input Current 1 Input Power 1 Input Frequency 2 Input Voltage 2 Input Current 2 Input Power 2 Input Frequency 3 Address 0x0430 0x0431 0x0432 0x0433 0x0434 0x0435 0x0436 0x0437 0x0438 0x0439 Value 0-9 0-999 0-9999 0-9999 0-65534 0-999 0-9999 0-9999 0-65534 0-999 Unit Input Voltage 3 Input Current 3 Input Power 3 Input Voltage 12 Input Voltage 23 Input Voltage 31 Reserved Reserved 0x043A 0x043B 0x043C 0x043D
Operation continued Bypass Status Description Bypass Frequency Bypass Number Lines Bypass Voltage 1 Bypass Current 1 Bypass Power 1 Bypass Voltage 2 Bypass Current 2 Bypass Power 2 Bypass Voltage 3 Bypass Current 3 Bypass Power 3 Bypass Voltage 12 Bypass Voltage 23 Bypass Voltage 31 Bypass STS Temperature Reserved Reserved Address 0x0456 0x0457 0x0458 0x0459 0x045A 0x045B 0x045C 0x045D 0x045E 0x045F 0x0460 0x0461 0x0462 0x0463 0x0464 0x0465 0x0466 Value 0-999 0-9 0-9999 0-9999 0-65534 0-9999 0-9999 0-6553
Operation continued Select Voltage Description Selected Output Voltage Select Output Voltage 1 Select Output Voltage 2 Select Output Voltage 3 Address 0x0471 0x0472 0x0473 0x0474 Value 0-999 0-999 0-999 0-999 Unit Voltage Voltage Voltage Voltage Address 0x0475 Value 0: Doesn’t Exist 1: Exists Unit Address 0x0476 0x0477 0x0478 0x0479 0x047A 0x047B 0x047C 0x047D 0x047E 0x047F 0x0480 0x0481 Value Low: Byte 1, Hi: Byte 2 Low: Byte 3, Hi: Byte 4 Low: Byte 5, Hi: Byte 6 Low: Byte 7, Hi: Byte 8 Low: Byte 9
Operation continued TempStatus continued Temp Byte 16 (Hi): B0: Converter Board Power Abnormal B1: EPO Happened B2: Manual Bypass On B3: Converter Board Communication Error B4: Battery Cabinet Over Temperature Warning (>=75C) B5: Battery Ground Fault B6: Battery Test in Progress B7: Battery Test Fail Temp Byte 17: Reserved Temp Byte 18: Reserved Temp Byte 19: Reserved Temp Byte 20 (Hi): B5: Ambiance Over Temperature B7: Auxiliary Power Fail Temp Byte 13 (Lo): Battery Te
Operation continued Power Module General Status Description Power Module ID / General Status Power Module ID / General Status Power Module ID / General Status Power Module ID / General Status Reserved Reserved Address 0x048C 0x048D 0x048E 0x048F 0x0490 0x0491 Value Lo: ID (1-4), Hi: Status Unit Value 1-4 Lo: Status 0, Hi: Status 1 Unit Power Module General Status: B0: The power module exists or the power module is powered B1: B2: B3: B4: B5: B6: B7: Fault shutdown Power Module PFC Status Description
Operation continued Power Module Inverter Status Description Power Module ID / Status 0 Inverter Status 1,2 Power Module ID / Status 0 Inverter Status 1,2 Power Module ID / Status 0 Inverter Status 1,2 Power Module ID / Status 0 Inverter Status 1,2 Reserved Reserved Reserved Reserved Address 0x049E 0x049F 0x04A0 0x04A1 0x04A2 0x04A3 0x04A4 0x04A5 0x04A6 0x04A7 0x04A8 0x04A9 Value Lo: ID (1-4), Hi: Status 0 Lo: Status 1, Hi: Status 2 Unit Inverter Status: B0: Inverter Fuse Open B1: Inverter Over Temperat
Operation continued Power Module Temperature Status Description Power Module ID Temperature PFC Temperature TBD Temperature INV Temperature INV R Temperature INV S Temperature INV T Power Module ID Temperature PFC Temperature TBD Temperature INV Temperature INV R Temperature INV S Temperature INV T Power Module ID Temperature PFC Temperature TBD Temperature INV Temperature INV R Temperature INV S Temperature INV T Power Module ID Temperature PFC Temperature TBD Temperature INV Temperature INV R Temperature
Operation continued Power Module Inverter Voltage Description Power Module ID Inverter Voltage R Inverter Voltage S Inverter Voltage T Power Module ID Inverter Voltage R Inverter Voltage S Inverter Voltage T Power Module ID Inverter Voltage R Inverter Voltage S Inverter Voltage T Power Module ID Inverter Voltage R Inverter Voltage S Inverter Voltage T Power Module ID Inverter Voltage R Inverter Voltage S Inverter Voltage T Reserved Reserved Address 0x04DA 0x04DB 0x04DC 0x04DD 0x04DE 0x04DB 0x04DC 0x04DD 0x
Operation continued Model Description Model Byte 0, 1 Model Byte 2, 3 Model Byte 4, 5 Model Byte 6, 7 Model Byte 8, 9 Model Byte 10, 11 Model Byte 12, 13 Model Byte 14, 15 Reserved Reserved Reserved Address 0x0503 0x0504 0x0505 0x0506 0x0507 0x0508 0x0509 0x050A 0x050B 0x050C 0x050D Value Lo: Byte 0, Hi: Byte 1 Lo: Byte 2, Hi: Byte 3 Lo: Byte 4, Hi: Byte 5 Lo: Byte 6, Hi: Byte 7 Lo: Byte 8, Hi: Byte 9 Lo: Byte 10, Hi: Byte 11 Lo: Byte 12, Hi: Byte 13 Lo: Byte 14, Hi: Byte 15 Unit Description Firmware Ve
Warranty & Warranty Registration LIMITED WARRANTY Seller warrants this product, if used in accordance with all applicable instructions, to be free from original defects in materials and workmanship for a period of 2 years (except internal UPS system batteries outside USA and Canada, 1 year) from the date of initial purchase. If the product should prove defective in material or workmanship within that period, Seller will repair or replace the product, in its sole discretion.